1SDA070707R1 ABB E1.2B 630 Ekip G Touch LSIG 630 A 3-Pole Fixed Air Circuit Breaker

1SDA070707R1 ABB E1.2B 630 Ekip G Touch LSIG 630 A 3-Pole Fixed Air Circuit Breaker

ABB 1SDA070707R1 E1.2B 630 is a 630 A three-pole fixed SACE Emax 2 air circuit breaker with front terminals and an Ekip G Touch LSIG electronic trip unit designed for generator protection and low-voltage power distribution.

SKU: 1SDA070707R1MPN: 1SDA070707R1
Price
List Price £8,285.98 ex VAT
Your Price (ex VAT) Save 25%
£6,214.49 25% OFF
You save £2,071.50 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £6,214.49
Trade pricing is personalised to your account

Manufacturer Lead Time

£6,214.49

Why Choose the ABB E1.2B 630 Ekip G Touch LSIG 3-Pole Air Circuit Breaker?

The ABB 1SDA070707R1 is a SACE Emax 2 E1.2B air circuit breaker equipped with ABB's advanced Ekip G Touch LSIG electronic trip unit. Rated at 630 A, this three-pole breaker is specifically configured for applications requiring sophisticated protection, measurement and generator-oriented functionality within low-voltage power systems.

The Ekip G Touch LSIG trip unit provides long-time (L), short-time (S), instantaneous (I) and ground-fault (G) protection. The Ekip G Touch family is designed with generator applications in mind, combining electronic protection with measurement capabilities suitable for protecting generators and associated electrical distribution systems.

The 1SDA070707R1 has a three-pole fixed (F) construction with front terminals (F). The E1.2B platform provides a rated ultimate short-circuit breaking capacity of 42 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s, providing dependable performance in demanding low-voltage installations.

Key Advantages

  • Advanced ABB SACE Emax 2 E1.2B air circuit breaker.
  • 630 A rated current for generator and high-current distribution applications.
  • Ekip G Touch LSIG electronic trip unit with generator-oriented protection and measurement functionality.
  • Long-time, short-time, instantaneous and ground-fault protection.
  • 42 kA ultimate short-circuit breaking capacity at 440 V AC.
  • 42 kA short-time withstand current for 1 s.
  • Three-pole fixed construction for permanent switchboard installation.
  • Front terminals provide a practical connection arrangement for compatible switchgear.

Key Features

  • ABB SACE Emax 2 E1.2B 630 air circuit breaker.
  • 630 A rated current.
  • Three-pole construction.
  • Fixed (F) installation.
  • Front (F) terminals.
  • Ekip G Touch LSIG electronic trip unit.
  • L protection: long-time overload protection.
  • S protection: short-time selective short-circuit protection.
  • I protection: instantaneous short-circuit protection.
  • G protection: ground-fault protection.
  • Designed with protection and measurement functionality for generator applications.
  • 690 V rated voltage.
  • Four auxiliary change-over contacts.
  • Open/closed status indication.

Advanced Generator Protection with Ekip G Touch

The ABB Ekip G Touch is a measurement and protection trip unit developed for generator applications. Generator protection requires reliable response to electrical faults while accounting for operating characteristics that can differ from conventional utility-fed distribution systems. The Ekip G Touch platform provides dedicated functionality for this type of application while retaining the advanced measurement and user-interface capabilities of ABB's Ekip Touch family.

With LSIG protection, the 1SDA070707R1 provides protection against sustained overloads, selective short circuits, severe instantaneous short circuits and ground faults. Combined with the 630 A E1.2B breaker platform and its 42 kA short-circuit performance at 440 V AC, it provides a capable solution for generator and low-voltage power distribution switchboards.

Typical Applications

  • Low-voltage generator protection systems.
  • Generator switchboards and control panels.
  • Emergency and standby generation systems.
  • Industrial power generation installations.
  • Low-voltage main distribution switchboards.
  • Manufacturing and process plant power systems.
  • Infrastructure and critical-power installations.
  • Three-phase systems requiring LSIG and generator-oriented protection.

Technical Specifications

Series SACE Emax 2
Order code 1SDA070707R1
Product group Emax2 Air Circuit Breaker
Product type Air circuit breaker
Frame E1.2
Performance level B
Rated current 630 A
Rated voltage 690 V
Number of poles 3
Installation Fixed (F)
Terminal type Front (F)
Trip unit Ekip G Touch LSIG
Protection functions Long-time, short-time, instantaneous and ground-fault (LSIG)
Ultimate short-circuit breaking capacity at 440 V AC 42 kA
Short-time withstand current 42 kA for 1 s
Integrated ground-fault protection Yes
Auxiliary contacts 4 change-over contacts
Open/closed indication Yes
Main circuit connection Bolt connection
Degree of protection IP30
Net weight 14 kg
EAN 8015644745578

Frequently Asked Questions

What is the ABB 1SDA070707R1?

The ABB 1SDA070707R1 is a SACE Emax 2 E1.2B 630 three-pole fixed air circuit breaker with front terminals and an Ekip G Touch LSIG electronic protection and measurement trip unit.

What is the rated current of the ABB E1.2B 630?

The ABB E1.2B 630 is rated at 630 A and is suitable for high-current low-voltage power distribution and generator protection applications.

What does Ekip G Touch LSIG provide?

The Ekip G Touch LSIG provides measurement and generator-oriented protection functionality together with long-time, short-time, instantaneous and ground-fault protection functions.

What is the short-circuit performance of the ABB E1.2B 630?

The E1.2B platform provides a rated ultimate short-circuit breaking capacity of 42 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s.

What mounting and terminal configuration does the ABB 1SDA070707R1 use?

The 1SDA070707R1 has a fixed (F) three-pole construction with front (F) terminals for permanent integration into compatible low-voltage switchgear.

Advanced Generator Protection from ABB

ABB SACE Emax 2 circuit breakers with Ekip G Touch protection combine robust short-circuit performance, electronic protection and generator-oriented measurement capabilities for dependable operation in demanding low-voltage power systems.