1SDA070164R1 ABB XT3N 250 TMD 63A 4P MCCB

1SDA070164R1 ABB XT3N 250 TMD 63A 4P MCCB

ABB 1SDA070164R1 is an XT3N 250 four-pole fixed moulded case circuit breaker with a 63 A TMD thermomagnetic release, front terminals and 36 kA ultimate short-circuit breaking capacity at 400 V AC.

SKU: 1SDA070164R1MPN: 1SDA070164R1
Price
List Price £1,054.05 ex VAT
Your Price (ex VAT) Save 25%
£790.54 25% OFF
You save £263.51 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £790.54
Trade pricing is personalised to your account

Manufacturer Lead Time

£790.54

Why Choose the ABB XT3N 250 TMD 1SDA070164R1 Circuit Breaker?

The ABB XT3N 250 TMD 1SDA070164R1 is a four-pole moulded case circuit breaker (MCCB) designed for dependable protection of low-voltage electrical distribution systems. Part of the ABB SACE Tmax XT3 range, it combines a 250 A frame with a 63 A TMD thermomagnetic trip unit for overload and short-circuit protection.

This XT3N circuit breaker is supplied in a fixed configuration with front terminals. Its TMD release has a rated current of 63 A, an adjustable thermal overload setting down to 44.1 A and an instantaneous magnetic short-circuit setting of 630 A, providing straightforward circuit protection without requiring an electronic trip unit.

The XT3N performance level provides a rated ultimate short-circuit breaking capacity of 36 kA at 400 V AC. Designed for operation with the trip unit calibrated at 50 °C, the 1SDA070164R1 is suitable for industrial, commercial and OEM distribution systems requiring a compact four-pole thermomagnetic MCCB.

Key Advantages

  • Reliable ABB SACE Tmax XT3N moulded case circuit breaker.
  • 63 A TMD thermomagnetic trip unit provides overload and short-circuit protection.
  • 36 kA Icu at 400 V AC for dependable fault interruption.
  • Four-pole configuration for three-phase systems requiring neutral switching.
  • Thermal overload setting adjustable from 44.1–63 A.
  • Fixed mounting with front terminals supports straightforward switchboard installation.

Key Features

  • ABB SACE Tmax XT3N 250 moulded case circuit breaker.
  • 63 A rated current.
  • 250 A rated uninterrupted current (Iu) for the XT3 frame.
  • Four-pole configuration.
  • TMD thermomagnetic release.
  • Adjustable thermal overload protection.
  • Instantaneous magnetic short-circuit protection.
  • 44.1–63 A overload release adjustment range.
  • 630 A instantaneous short-circuit release setting.
  • 36 kA Icu at 400 V AC, 50 Hz.
  • Rated voltage up to 690 V AC.
  • 50 °C trip-unit calibration.
  • Fixed construction with front-side bolt connections.
  • IP20 degree of protection.

Thermomagnetic Protection for Power Distribution

The TMD release combines two established protection principles in a single trip unit. The thermal element responds to sustained overload conditions, while the magnetic element provides rapid operation during high short-circuit currents. On the 1SDA070164R1, the thermal overload setting can be adjusted between 44.1 A and 63 A, while the instantaneous short-circuit release is set at 630 A.

This thermomagnetic arrangement provides robust circuit protection without the configuration requirements of an electronic release. Combined with the XT3N frame's 36 kA breaking capacity at 400 V AC, four-pole construction and fixed front-connected design, it makes the breaker well suited to conventional low-voltage distribution and panel-building applications.

Typical Applications

  • Industrial low-voltage power distribution systems.
  • Commercial building distribution switchboards.
  • Three-phase and neutral feeder protection.
  • Electrical control and distribution panels.
  • Industrial machinery and equipment supplies.
  • OEM switchgear and panel-building applications.

Technical Specifications

Series SACE Tmax XT
ABB product group T-Max XT 250 Range
ABB order code 1SDA070164R1
Alternate catalogue number XT3N54063AFF000XXX
Product type Moulded case circuit breaker
Frame / size XT3N 250
Number of poles 4
Rated current 63 A
Rated uninterrupted current (Iu) 250 A
Trip unit TMD thermomagnetic release
Overload release setting 44.1–63 A
Instantaneous short-circuit release setting 630 A
Short-circuit performance level N
Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC, 50 Hz 36 kA
Rated voltage Up to 690 V AC
Calibration temperature 50 °C
Mounting Fixed
Main circuit connection Bolt connection
Connection position Front
Operating element Toggle
Degree of protection IP20
Protection unit included Yes
Motor operator capability Optional
DIN rail mounting Optional
Standard IEC
Net weight Approx. 2.1 kg
Country of origin Italy
EAN 8015644709778
Customs tariff / HS code 85362090

Frequently Asked Questions

What is the ABB 1SDA070164R1?

The ABB 1SDA070164R1 is an XT3N 250 four-pole moulded case circuit breaker with a 63 A TMD thermomagnetic release, fixed mounting and front terminals.

What is the rated current of the ABB XT3N 1SDA070164R1?

The TMD protection unit has a rated current of 63 A, while the XT3 frame has a rated uninterrupted current (Iu) of 250 A.

What is the breaking capacity of the XT3N 250?

The N-performance XT3N 250 has a rated ultimate short-circuit breaking capacity of 36 kA at 400 V AC, 50 Hz.

What protection does the TMD trip unit provide?

The TMD thermomagnetic release provides thermal overload protection and instantaneous magnetic short-circuit protection. On this model, the overload setting is adjustable from 44.1–63 A and the instantaneous short-circuit release is set at 630 A.

What does 50°C mean in the ABB XT3N 250 product designation?

The 50 °C designation identifies the reference calibration temperature associated with the thermomagnetic release on this specific XT3N configuration.

Trusted Thermomagnetic Protection from ABB

ABB SACE Tmax XT moulded case circuit breakers combine compact construction, dependable short-circuit interruption and proven protection technology for industrial, commercial and OEM low-voltage power distribution systems.