1SDA069630R1 ABB XT4H 250 Ekip E-LSIG In=250A 4p F F

1SDA069630R1 ABB XT4H 250 Ekip E-LSIG In=250A 4p F F

ABB 1SDA069630R1 XT4H 250 Ekip E-LSIG is a 250 A four-pole fixed moulded case circuit breaker with front terminals, electronic LSIG protection, integrated energy metering and 70 kA ultimate breaking capacity at 380–415 V AC.

SKU: 1SDA069630R1Alt SKU: XT4H 250MPN: 1SDA069630R1
Price
List Price £3,866.05 ex VAT
Your Price (ex VAT) Save 25%
£2,899.54 25% OFF
You save £966.51 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £2,899.54
Trade pricing is personalised to your account

Manufacturer Lead Time

£2,899.54

Why Choose the ABB XT4H 250 Ekip E-LSIG In=250A 4p F F?

The ABB XT4H 250 Ekip E-LSIG In=250A 4p F F, order code 1SDA069630R1, is a 250 A four-pole moulded case circuit breaker (MCCB) from the ABB SACE Tmax XT range. It combines the XT4H high-breaking-capacity platform with an advanced Ekip E-LSIG electronic trip unit for comprehensive protection, energy metering and electrical measurement in low-voltage power-distribution systems.

The Ekip E-LSIG release provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection. This combination provides adjustable electronic protection against the principal overcurrent and earth-fault conditions encountered in industrial and commercial electrical distribution.

With a 250 A rated current, four-pole construction, fixed mounting and front terminals, the 1SDA069630R1 is designed for permanent integration into low-voltage switchboards. The XT4H performance level provides an ultimate short-circuit breaking capacity of 70 kA at 380–415 V AC, while the Ekip E-LSIG platform adds integrated energy metering, individual protection LEDs and advanced electrical measurements.

Key Advantages

  • 250 A four-pole MCCB for demanding low-voltage power-distribution applications.
  • 70 kA ultimate breaking capacity at 380–415 V AC.
  • Ekip E-LSIG electronic trip unit provides L, S, I and G protection functions.
  • Electronic protection enables adjustable protection characteristics for distribution-system coordination.
  • Integrated energy metering provides greater visibility of electrical consumption.
  • Advanced measurement capabilities include power, energy, frequency, power factor, harmonics and THD.
  • Fixed mounting and front terminals provide straightforward switchboard integration.

Key Features

  • ABB SACE Tmax XT4H 250 moulded case circuit breaker.
  • 250 A rated current.
  • 4-pole configuration.
  • Ekip E-LSIG electronic protection release.
  • Long-time overload protection (L).
  • Short-time short-circuit protection (S).
  • Instantaneous short-circuit protection (I).
  • Ground-fault protection (G).
  • Integrated energy metering.
  • Individual protection indication LEDs.
  • Internal bus for compatible HMI connectivity.
  • Advanced power and energy measurement functionality.
  • Fixed mounting.
  • Front terminals.
  • Designed for low-voltage power-distribution applications.

High-Performance Ekip E-LSIG Protection and Energy Measurement

The Ekip E-LSIG electronic release combines four key protection functions within the XT4H 250 platform. Long-time protection responds to sustained overloads, short-time protection provides delayed response to high fault currents, instantaneous protection reacts to severe short circuits, and ground-fault protection addresses earth-fault conditions. Together, these functions provide comprehensive protection for demanding low-voltage distribution circuits.

Beyond protection, the Ekip E platform incorporates integrated energy metering and advanced electrical measurement functions. Measurements include parameters such as power factor, frequency, energy, power, harmonic analysis and total harmonic distortion, while an internal bus supports compatible HMI connectivity. Combined with the XT4H's high short-circuit interruption capability, these features make the 1SDA069630R1 suitable for systems requiring both robust protection and improved electrical-performance visibility.

Typical Applications

  • Industrial low-voltage power distribution.
  • Main and sub-main distribution switchboards.
  • Commercial building electrical distribution.
  • Four-pole circuits requiring ground-fault protection.
  • Distribution systems with high prospective short-circuit currents.
  • Power-distribution systems requiring integrated energy metering.
  • Manufacturing and process-industry switchboards.
  • Infrastructure and utility distribution panels.
  • OEM switchgear and power-control assemblies.

Technical Specifications

Series SACE Tmax XT
Product group T-Max XT 250 Range
Order code 1SDA069630R1
EAN 8015644703868
Product type Moulded case circuit breaker (MCCB)
Application Power distribution
Frame XT4 250
Performance level H
Rated current (In) 250 A
Number of poles 4
Trip unit Ekip E-LSIG electronic release
Protection functions Long-time, short-time, instantaneous and ground-fault (LSIG)
Ultimate breaking capacity (Icu) at 220–240 V AC 100 kA
Ultimate breaking capacity (Icu) at 380–415 V AC 70 kA
Ultimate breaking capacity (Icu) at 440 V AC 65 kA
Ultimate breaking capacity (Icu) at 500 V AC 50 kA
Ultimate breaking capacity (Icu) at 525 V AC 45 kA
Ultimate breaking capacity (Icu) at 690 V AC 15 kA
Rated operational voltage Up to 690 V AC
Mounting Fixed
Terminal arrangement Front terminals
Release technology Electronic
Energy measurement Integrated
Measurement functions Power factor, frequency, energy, power, harmonic analysis and THD
HMI connectivity Internal bus support
Product net weight 3.5 kg
Country of origin Italy
Customs tariff / HS code 85362090
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA069630R1?

The ABB 1SDA069630R1 is an XT4H 250 four-pole fixed moulded case circuit breaker rated at 250 A, equipped with front terminals and an Ekip E-LSIG electronic trip unit.

What protection functions does the ABB Ekip E-LSIG trip unit provide?

The Ekip E-LSIG provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection, represented by the L, S, I and G functions.

What is the breaking capacity of the ABB 1SDA069630R1?

The XT4H 250 provides an ultimate short-circuit breaking capacity of 70 kA at 380–415 V AC, making it suitable for distribution systems with demanding prospective fault levels.

Does the ABB 1SDA069630R1 provide energy measurement?

Yes. The Ekip E-LSIG platform provides integrated energy metering and advanced electrical measurements including power, energy, frequency, power factor, harmonic analysis and total harmonic distortion.

How is the ABB 1SDA069630R1 installed?

The 1SDA069630R1 is a four-pole fixed MCCB with front terminals, designed for permanent installation within compatible low-voltage switchboards and power-distribution assemblies.

Trusted ABB High-Performance Protection for Low-Voltage Distribution

ABB SACE Tmax XT circuit breakers combine high-performance short-circuit interruption with advanced electronic protection and energy-management capabilities, providing a compact solution for demanding industrial, commercial and OEM low-voltage distribution systems.