ABB 1SDA069630R1 XT4H 250 Ekip E-LSIG is a 250 A four-pole fixed moulded case circuit breaker with front terminals, electronic LSIG protection, integrated energy metering and 70 kA ultimate breaking capacity at 380–415 V AC.
£2,899.54
The ABB XT4H 250 Ekip E-LSIG In=250A 4p F F, order code 1SDA069630R1, is a 250 A four-pole moulded case circuit breaker (MCCB) from the ABB SACE Tmax XT range. It combines the XT4H high-breaking-capacity platform with an advanced Ekip E-LSIG electronic trip unit for comprehensive protection, energy metering and electrical measurement in low-voltage power-distribution systems.
The Ekip E-LSIG release provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection. This combination provides adjustable electronic protection against the principal overcurrent and earth-fault conditions encountered in industrial and commercial electrical distribution.
With a 250 A rated current, four-pole construction, fixed mounting and front terminals, the 1SDA069630R1 is designed for permanent integration into low-voltage switchboards. The XT4H performance level provides an ultimate short-circuit breaking capacity of 70 kA at 380–415 V AC, while the Ekip E-LSIG platform adds integrated energy metering, individual protection LEDs and advanced electrical measurements.
The Ekip E-LSIG electronic release combines four key protection functions within the XT4H 250 platform. Long-time protection responds to sustained overloads, short-time protection provides delayed response to high fault currents, instantaneous protection reacts to severe short circuits, and ground-fault protection addresses earth-fault conditions. Together, these functions provide comprehensive protection for demanding low-voltage distribution circuits.
Beyond protection, the Ekip E platform incorporates integrated energy metering and advanced electrical measurement functions. Measurements include parameters such as power factor, frequency, energy, power, harmonic analysis and total harmonic distortion, while an internal bus supports compatible HMI connectivity. Combined with the XT4H's high short-circuit interruption capability, these features make the 1SDA069630R1 suitable for systems requiring both robust protection and improved electrical-performance visibility.
| Series | SACE Tmax XT |
|---|---|
| Product group | T-Max XT 250 Range |
| Order code | 1SDA069630R1 |
| EAN | 8015644703868 |
| Product type | Moulded case circuit breaker (MCCB) |
| Application | Power distribution |
| Frame | XT4 250 |
| Performance level | H |
| Rated current (In) | 250 A |
| Number of poles | 4 |
| Trip unit | Ekip E-LSIG electronic release |
| Protection functions | Long-time, short-time, instantaneous and ground-fault (LSIG) |
| Ultimate breaking capacity (Icu) at 220–240 V AC | 100 kA |
| Ultimate breaking capacity (Icu) at 380–415 V AC | 70 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 65 kA |
| Ultimate breaking capacity (Icu) at 500 V AC | 50 kA |
| Ultimate breaking capacity (Icu) at 525 V AC | 45 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 15 kA |
| Rated operational voltage | Up to 690 V AC |
| Mounting | Fixed |
| Terminal arrangement | Front terminals |
| Release technology | Electronic |
| Energy measurement | Integrated |
| Measurement functions | Power factor, frequency, energy, power, harmonic analysis and THD |
| HMI connectivity | Internal bus support |
| Product net weight | 3.5 kg |
| Country of origin | Italy |
| Customs tariff / HS code | 85362090 |
| Standard | IEC 60947-2 |
The ABB 1SDA069630R1 is an XT4H 250 four-pole fixed moulded case circuit breaker rated at 250 A, equipped with front terminals and an Ekip E-LSIG electronic trip unit.
The Ekip E-LSIG provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection, represented by the L, S, I and G functions.
The XT4H 250 provides an ultimate short-circuit breaking capacity of 70 kA at 380–415 V AC, making it suitable for distribution systems with demanding prospective fault levels.
Yes. The Ekip E-LSIG platform provides integrated energy metering and advanced electrical measurements including power, energy, frequency, power factor, harmonic analysis and total harmonic distortion.
The 1SDA069630R1 is a four-pole fixed MCCB with front terminals, designed for permanent installation within compatible low-voltage switchboards and power-distribution assemblies.
ABB SACE Tmax XT circuit breakers combine high-performance short-circuit interruption with advanced electronic protection and energy-management capabilities, providing a compact solution for demanding industrial, commercial and OEM low-voltage distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.