1SDA069614R1 ABB XT4S 160 Ekip E-LSIG 160A 3P MCCB

1SDA069614R1 ABB XT4S 160 Ekip E-LSIG 160A 3P MCCB

ABB 1SDA069614R1 is an XT4S 160 three-pole fixed moulded case circuit breaker with a 160 A Ekip E-LSIG electronic trip unit, front terminals and 50 kA ultimate short-circuit breaking capacity at 415 V AC.

SKU: 1SDA069614R1MPN: 1SDA069614R1
Price
List Price £1,338.86 ex VAT
Your Price (ex VAT) Save 25%
£1,004.15 25% OFF
You save £334.72 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,004.15
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,004.15

Why Choose the ABB XT4S 160 Ekip E-LSIG 1SDA069614R1 Circuit Breaker?

The ABB XT4S 160 Ekip E-LSIG 1SDA069614R1 is a high-performance three-pole moulded case circuit breaker (MCCB) designed for reliable protection of low-voltage electrical distribution systems. Part of the advanced ABB SACE Tmax XT4 range, it combines a compact 160 A frame with an electronic Ekip E-LSIG trip unit for comprehensive overload, short-circuit and earth-fault protection.

This XT4S circuit breaker is supplied in a fixed configuration with front terminals and has a rated current of 160 A. The Ekip E-LSIG solid-state release provides adjustable protection functions, enabling the breaker to be configured for the requirements of industrial switchboards, distribution panels and other demanding low-voltage installations.

The XT4S performance level provides a rated ultimate short-circuit breaking capacity of 50 kA at 415 V AC, while the breaker supports operational voltages up to 690 V AC. Its combination of high breaking capacity, electronic protection and compact XT4 construction makes it suitable for dependable feeder and distribution circuit protection.

Key Advantages

  • High-performance ABB SACE Tmax XT4S moulded case circuit breaker.
  • 160 A rated current for industrial and commercial power distribution.
  • 50 kA breaking capacity at 415 V AC for demanding fault conditions.
  • Advanced Ekip E-LSIG electronic trip unit provides comprehensive circuit protection.
  • Three-pole fixed configuration with front terminals for straightforward switchboard installation.
  • Adjustable protection characteristics support coordination with the wider electrical distribution system.

Key Features

  • ABB SACE Tmax XT4S 160 moulded case circuit breaker.
  • 160 A rated current (In).
  • 160 A rated uninterrupted current (Iu).
  • Three-pole configuration.
  • Ekip E-LSIG solid-state electronic release.
  • Long-time, short-time, instantaneous and ground-fault protection functions.
  • 50 kA Icu at 415 V AC.
  • 690 V AC rated operational voltage.
  • 1,000 V rated insulation voltage (Ui).
  • 8 kV rated impulse withstand voltage (Uimp).
  • Fixed mounting with front terminal connections.
  • Adjustable long-time protection over the supported Ekip E-LSIG setting range.

Advanced Electronic Protection for Power Distribution

The Ekip E-LSIG electronic release provides multiple protection functions for electrical distribution circuits. Long-time protection guards against sustained overloads, short-time and instantaneous functions provide protection against high fault currents, and the ground-fault function adds protection against earth-fault conditions. Adjustable settings allow the protection characteristics to be coordinated with the requirements of the installation.

As part of the ABB SACE Tmax XT family, the XT4S combines high short-circuit performance with compact dimensions. Its fixed mounting arrangement and front terminals make it particularly suitable for integration into low-voltage switchboards where reliable protection, efficient use of panel space and configurable electronic protection are required.

Typical Applications

  • Industrial low-voltage power distribution systems.
  • Commercial building distribution switchboards.
  • Incoming and outgoing feeder protection.
  • Industrial machinery and production equipment.
  • Electrical control and distribution panels.
  • OEM switchgear and panel-building applications.

Technical Specifications

Series SACE Tmax XT
ABB product group T-Max XT 250 Range
ABB order code 1SDA069614R1
Product type Moulded case circuit breaker
Frame / size XT4S 160
Number of poles 3
Rated current (In) 160 A
Rated uninterrupted current (Iu) 160 A
Trip unit Ekip E-LSIG electronic release
Protection functions L / S / I / G
Short-circuit performance level S
Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC 50 kA
Rated service short-circuit breaking capacity (Ics) at 415 V AC 50 kA
Rated service short-circuit breaking capacity (Ics) at 380 V AC 50 kA
Rated service short-circuit breaking capacity (Ics) at 440 V AC 50 kA
Rated service short-circuit breaking capacity (Ics) at 500 V AC 36 kA
Rated service short-circuit breaking capacity (Ics) at 525 V AC 25 kA
Rated service short-circuit breaking capacity (Ics) at 690 V AC 12 kA
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1,000 V
Rated impulse withstand voltage (Uimp) 8 kV
Selectivity category A
Mounting Fixed
Terminal connection Front terminals
Dimensions (W × H × D) 105 × 160 × 82.5 mm
Net weight approx. 2.05 kg
Electrical durability 8,000 cycles
Maximum electrical operating frequency 120 cycles per hour
Standard IEC
Country of origin Italy
EAN 8015644703707
Customs tariff number 85362090

Frequently Asked Questions

What is the ABB 1SDA069614R1?

The ABB 1SDA069614R1 is an XT4S 160 three-pole moulded case circuit breaker with a 160 A Ekip E-LSIG electronic trip unit, fixed mounting and front terminals.

What is the rated current of the ABB XT4S 1SDA069614R1?

The circuit breaker has a rated current of 160 A and a rated uninterrupted current of 160 A.

What is the breaking capacity of the XT4S 160?

The S-performance XT4S 160 has a rated ultimate short-circuit breaking capacity of 50 kA at 415 V AC.

What protection does the Ekip E-LSIG trip unit provide?

The Ekip E-LSIG electronic release provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection functions.

How is the ABB 1SDA069614R1 installed?

The circuit breaker is designed for fixed mounting and is supplied with front terminals for connection within low-voltage switchboards and distribution panels.

Trusted Protection for Low-Voltage Distribution

ABB SACE Tmax XT moulded case circuit breakers combine compact construction, high short-circuit performance and advanced electronic protection to provide dependable circuit protection for industrial, commercial and OEM low-voltage distribution systems.