Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA069605R1 XT4N 250 is a 250 A three-pole fixed moulded case circuit breaker with front terminals, an Ekip E-LSIG electronic trip unit, energy-measurement functionality and a 36 kA breaking capacity at 380–415 V AC.
£1,440.14
The ABB XT4N 250 Ekip E-LSIG In=250A 3p F F, order code 1SDA069605R1, is a high-performance moulded case circuit breaker (MCCB) designed for protection, switching and energy monitoring in low-voltage electrical distribution systems. As part of the ABB SACE Tmax XT4 series, it combines a compact 250 A frame with an advanced Ekip E-LSIG electronic trip unit rated at 250 A.
The Ekip E-LSIG release provides long-time, short-time, instantaneous and ground-fault protection, helping protect feeders and electrical equipment against overload, short-circuit and earth-fault conditions. This Ekip E version is also designed for energy measurement, making the breaker suitable for intelligent switchboards where protection and electrical-energy monitoring are required from the same device.
This XT4N model is supplied as a three-pole fixed circuit breaker with front terminals. It is rated at 250 A and provides an ultimate short-circuit breaking capacity of 36 kA at 380–415 V AC, with operation supported at system voltages up to 690 V AC.
Electronic moulded case circuit breakers provide precise protection for low-voltage feeders while offering greater adjustment and monitoring capability than conventional thermomagnetic devices. The Ekip E-LSIG release combines overload, selective short-circuit, instantaneous short-circuit and ground-fault protection, enabling coordinated protection of important electrical distribution circuits.
The ABB XT4N 1SDA069605R1 also provides energy-measurement functionality, making it particularly useful in modern switchboards where electrical protection and energy management are closely integrated. Its compact fixed construction and front terminals simplify installation within industrial and commercial low-voltage distribution panels.
| Series | SACE Tmax XT |
|---|---|
| ABB order code | 1SDA069605R1 |
| EAN | 8015644703592 |
| Product type | Moulded case circuit breaker (MCCB) |
| Frame | XT4 |
| Performance level | N |
| Rated current | 250 A |
| Trip unit | Ekip E-LSIG electronic release |
| Protection functions | Long-time, short-time, instantaneous and ground fault (LSIG) |
| Number of poles | 3 |
| Execution | Fixed |
| Terminal type | Front terminals |
| Ultimate breaking capacity (Icu) at 220–230 V AC | 65 kA |
| Ultimate breaking capacity (Icu) at 380–415 V AC | 36 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 36 kA |
| Ultimate breaking capacity (Icu) at 500 V AC | 30 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 10 kA |
| Dimensions (H × W × D) | 160 × 105 × 82.5 mm |
| Product net weight | 2.05 kg |
It is a moulded case circuit breaker designed to protect low-voltage distribution circuits while providing electronic LSIG protection and energy-measurement functionality.
The XT4N circuit breaker and its Ekip E-LSIG electronic release are rated at 250 A.
The Ekip E-LSIG release provides long-time, short-time, instantaneous and ground-fault protection for comprehensive low-voltage circuit protection.
The XT4N has an ultimate short-circuit breaking capacity of 36 kA at 380–415 V AC, with breaking capacity varying according to the system voltage.
Yes. The Ekip E-LSIG version is designed with energy-measurement functionality for applications requiring both circuit protection and electrical-energy monitoring.
This model is supplied as a three-pole fixed circuit breaker with front terminals for installation in compatible low-voltage switchboards and distribution panels.
ABB SACE Tmax XT moulded case circuit breakers are widely used in industrial and commercial power distribution systems to provide dependable protection, flexible electronic trip functionality and intelligent energy management.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.