ABB 1SDA068535R1 SACE Tmax XT4H 250 moulded case circuit breaker with Ekip Dip LS/I electronic release, 250 A rated current, four-pole fixed configuration, front terminals and 70 kA breaking capacity at 415 V AC.
£1,226.37
The ABB 1SDA068535R1 is a robust SACE Tmax XT4H moulded case circuit breaker (MCCB) designed for reliable protection in low voltage power distribution systems. Part of ABB’s advanced Tmax XT circuit breaker range, this fixed four-pole breaker provides high-performance overload and short-circuit protection for industrial, commercial and infrastructure applications.
This model is fitted with an Ekip Dip LS/I solid-state electronic release, offering long-time, short-time and instantaneous protection functions for improved selectivity and dependable circuit protection. Its front terminal fixed configuration supports straightforward installation within switchboards, distribution boards and electrical control panels.
With a rated current of 250 A, a 690 V AC rated operational voltage and a high breaking capacity of 70 kA at 415 V AC, the ABB 1SDA068535R1 is well suited to demanding installations where safety, continuity and electrical performance are essential.
Moulded case circuit breakers such as the ABB 1SDA068535R1 are used to protect electrical systems from overloads and short-circuit faults. By automatically disconnecting faulty circuits, they help protect cables, switchgear, machinery and downstream electrical equipment from damage.
The XT4H frame offers high short-circuit performance in a compact design, while the Ekip Dip LS/I electronic release provides adjustable protection characteristics for improved selectivity across power distribution networks. This makes the breaker suitable for installations where dependable operation and system coordination are critical.
Tick the specs you need, then view products that match.
| Mounting Type | Fixed | |
|---|---|---|
| Application | Power distribution | |
| Trip Unit | LS/I | |
| Current | 250 A | |
| Phase | Three Phase | |
| Poles | 4-pole | |
| Device Type | MCCB | |
| Breaking Capacity | 70 kA | |
| Manufacturer | ABB | |
| Series | SACE Tmax XT | |
| Model | XT4H 250 Ekip Dip LS/I In=250A 4p F F | |
| SKU | 1SDA068535R1 | |
| Product type | Moulded case circuit breaker | |
| Frame size | XT4 | |
| Sub-type | XT4H | |
| Rated current | 250 A | |
| Rated uninterrupted current | 250 A | |
| Number of poles | 4 | |
| Trip unit | Ekip Dip LS/I | |
| Release type | Electronic / solid-state | |
| Rated operational voltage | 690 V AC | |
| Rated insulation voltage | 1000 V | |
| Rated impulse withstand voltage | 8 kV | |
| Rated frequency | 50 / 60 Hz | |
| Breaking capacity | 70 kA at 415 V AC | |
| Terminal type | Front terminals | |
| Terminal connection | Bolt | |
| Mounting version | Fixed | |
| Standard | IEC 60947-2 | |
| Dimensions (H × W × D) | 160 × 140 × 82.5 mm | |
| Weight | approx. 2.933 kg | |
| HS Code | 85362090 | |
| Country of Manufacture | Italy |
The ABB 1SDA068535R1 is used to protect low voltage electrical circuits against overloads and short circuits in industrial and commercial power distribution systems.
This ABB XT4H MCCB has a rated current of 250 A.
The ABB 1SDA068535R1 is a four-pole fixed moulded case circuit breaker.
This breaker is fitted with an Ekip Dip LS/I electronic trip unit, providing long-time, short-time and instantaneous protection functions.
The ABB 1SDA068535R1 has a rated ultimate short-circuit breaking capacity of 70 kA at 415 V AC.
ABB SACE Tmax XT moulded case circuit breakers are trusted by panel builders, electrical engineers and industrial maintenance teams for reliable protection, compact installation and dependable low voltage power distribution performance.