ABB XT4S 250 4 pole Standard MCCB Adjustable Thermal-Magnetic Release In=200A Ii=2000A

ABB XT4S 250 4 pole Standard MCCB Adjustable Thermal-Magnetic Release In=200A Ii=2000A

ABB 1SDA068324R1 SACE Tmax XT4S four-pole moulded case circuit breaker with 160 A TMA thermomagnetic trip unit and fully rated neutral for industrial power distribution.

SKU: 1SDA068324R1Alt SKU: XT4S 250 TMA 200-2000 4p F F InN=50%MPN: 1SDA068324R1
Price
List Price £1,176.99 ex VAT
Your Price (ex VAT) Save 25%
£882.74 25% OFF
You save £294.25 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £882.74
Trade pricing is personalised to your account

Manufacturer Lead Time

£882.74

Why Choose the ABB 1SDA068324R1 Tmax XT4S Moulded Case Circuit Breaker?

The ABB 1SDA068324R1 is a high performance Tmax XT4S moulded case circuit breaker (MCCB) designed to provide dependable overload and short circuit protection for low voltage electrical distribution systems. As part of the trusted ABB SACE Tmax XT series, it delivers reliable four-pole protection for industrial, commercial and infrastructure applications.

This fixed four-pole MCCB incorporates a TMA thermomagnetic trip unit with adjustable thermal overload protection and adjustable instantaneous magnetic protection. The neutral pole is fully rated (100%), making it ideal for installations where full neutral current capacity is required, including systems with significant single-phase loading.

With a 160 A rated current, 690 V AC operating voltage and a 50 kA breaking capacity at 415 V AC, the ABB 1SDA068324R1 provides dependable protection for feeders, switchboards, industrial machinery and commercial electrical distribution systems.

Key Advantages

  • High quality ABB Tmax XT4S moulded case circuit breaker.
  • 160 A rated current for industrial power distribution.
  • Four-pole fixed MCCB with fully rated neutral.
  • TMA thermomagnetic release for overload and short circuit protection.
  • Adjustable instantaneous trip setting from 800 to 1600 A.
  • 50 kA breaking capacity at 415 V AC.
  • Compact XT4 frame simplifies switchboard installation.
  • Manufactured in accordance with IEC 60947-2.

Key Features

  • ABB SACE Tmax XT4S series.
  • Product code: 1SDA068324R1.
  • Rated current: 160 A.
  • 160 A frame size.
  • Four-pole fixed configuration.
  • Fully rated neutral (100%).
  • TMA thermomagnetic trip unit.
  • Thermal setting range: 112 to 160 A.
  • Instantaneous trip setting: 800 to 1600 A.
  • Front terminal connections.

Reliable Protection for Industrial Power Distribution

The ABB Tmax XT4S range is engineered to disconnect electrical circuits safely during overload and short circuit conditions, helping to protect cables, switchgear and connected equipment while maintaining reliable operation throughout industrial power distribution systems.

The ABB 1SDA068324R1 combines compact dimensions, high interrupting capacity and adjustable thermomagnetic protection with a fully rated neutral pole, making it particularly suitable for installations where neutral currents may equal phase currents.

Typical Applications

  • Main and sub-distribution boards.
  • Industrial switchboards.
  • Commercial electrical installations.
  • Four-pole distribution circuits.
  • Motor feeder protection.
  • OEM machinery and control panels.
  • Infrastructure projects.
  • Low voltage electrical systems.

Technical Specifications

Tick the specs you need, then view products that match.

Mounting Type Fixed
Application Power distribution
Current 200 A
Phase Three Phase
Poles 4-pole
Device Type MCCB
Breaking Capacity 50 kA
Trip Unit Thermal-magnetic
Manufacturer ABB
Series SACE Tmax XT
Model XT4S 160 TMA 160-1600 4P F F InN=100%
Product code 1SDA068324R1
Product type Moulded Case Circuit Breaker (MCCB)
Number of poles 4
Frame size XT4
Rated current (In) 160 A
Neutral rating 100% of phase current
Trip unit TMA thermomagnetic
Thermal setting range 112 to 160 A
Instantaneous trip setting (Ii) 800 to 1600 A
Rated operational voltage 690 V AC / 750 V DC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 8 kV
Frequency 50 / 60 Hz
Breaking capacity (Icu) 50 kA at 415 V AC
Short circuit performance level S
Protection rating IP20
Terminal type Front terminals
Mounting Fixed
Dimensions (H × W × D) approx. 160 × 140 × 82.5 mm
Weight approx. 3.5 kg
HS Code 85362090
Country of Manufacture Italy

Frequently Asked Questions

What is the ABB 1SDA068324R1 used for?

It protects low voltage electrical distribution systems against overloads and short circuits in industrial and commercial applications.

What is the rated current of this MCCB?

The ABB 1SDA068324R1 has a 160 A rated current.

What does a fully rated neutral mean?

The neutral pole is rated at 100% of the phase current, making it suitable for installations where the neutral conductor may carry the same current as the phase conductors.

What type of trip unit is fitted?

The breaker incorporates a TMA thermomagnetic trip unit with adjustable overload and magnetic protection.

Where is this breaker typically installed?

It is commonly installed in industrial switchboards, OEM machinery, commercial distribution panels and electrical power distribution systems.

Trusted by Electrical Professionals Worldwide

ABB SACE Tmax XT circuit breakers are trusted worldwide by panel builders, OEM manufacturers and electrical engineers for dependable protection, long service life and reliable operation in demanding industrial environments.