ABB 1SDA068292R1 XT4L 160 is a 160 A three-pole fixed Tmax XT4 breaking part with front terminals and 120 kA ultimate and service short-circuit breaking capacity at 415 V AC.
£539.82
The ABB 1SDA068292R1 XT4L 160 BREAKING PART 3p F F is a three-pole breaking part for the ABB SACE Tmax XT4 moulded case circuit breaker system. Designed as the switching and fault-interruption section of a modular XT4 assembly, it provides the breaker mechanism and L-level short-circuit performance while allowing a compatible ABB XT4 trip unit to be selected separately to suit the protection requirements of the installation.
The XT4L 160 breaking part has a rated uninterrupted current of 160 A and delivers an ultimate short-circuit breaking capacity of 120 kA at 415 V AC. Its high L performance level makes it particularly suitable for industrial and commercial distribution systems where high prospective fault currents demand substantial interruption capability.
Configured with three poles, fixed mounting and front terminals, the 1SDA068292R1 is designed for straightforward integration into low-voltage switchboards and distribution panels. It supports rated operational voltages up to 690 V AC and must be combined with a compatible ABB XT4 trip unit to create a complete protected moulded case circuit breaker assembly.
The ABB XT4L breaking part provides the switching mechanism and high-capacity fault-current interruption section of a modular Tmax XT4 circuit breaker. Its 120 kA Icu and Ics at 415 V AC make it particularly well suited to installations where substantial short-circuit levels must be accommodated, while its modular design allows the protection release to be chosen according to the specific requirements of the circuit.
The 1SDA068292R1 is not a complete protected circuit breaker when supplied as the breaking part alone. A compatible ABB SACE Tmax XT4 trip unit must be installed to provide the required overload and/or short-circuit protection functions. This modular approach allows the breaking part and protection release to be configured for the application while retaining the compact XT4 platform.
| Series | SACE Tmax XT |
|---|---|
| ABB product group | T-Max XT 250 Range |
| Order code | 1SDA068292R1 |
| Product type | MCCB breaking part |
| Compatible breaker platform | ABB SACE Tmax XT4 |
| Frame size | XT4 160 |
| Short-circuit performance level | L |
| Rated uninterrupted current (Iu) | 160 A |
| Rated operational voltage | up to 690 V AC / 500 V DC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Rated frequency | 50 / 60 Hz |
| Ultimate breaking capacity (Icu) at 220–240 V AC | 150 kA |
| Ultimate breaking capacity (Icu) at 380 V AC | 120 kA |
| Ultimate breaking capacity (Icu) at 415 V AC | 120 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 100 kA |
| Ultimate breaking capacity (Icu) at 500 V AC | 60 kA |
| Ultimate breaking capacity (Icu) at 525 V AC | 50 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 20 kA |
| Service breaking capacity (Ics) at 415 V AC | 120 kA |
| Number of poles | 3 |
| Execution | Fixed |
| Terminal arrangement | Front terminals |
| Main circuit connection | Bolt connection |
| Electrical durability | 8,000 operations |
| Mechanical durability | 25,000 operations |
| Dimensions (W × H × D) | 105 × 160 × 82.5 mm |
| Net weight | 1.65 kg |
| Standard | IEC 60947-2 |
| Country of origin | Italy |
| EAN / GTIN | 8015644022037 |
The ABB 1SDA068292R1 is an XT4L 160 three-pole breaking part for the ABB SACE Tmax XT4 moulded case circuit breaker platform, featuring fixed execution, front terminals and L-level short-circuit performance.
No. The 1SDA068292R1 is the breaking part of a modular Tmax XT4 circuit breaker. A compatible ABB XT4 trip unit must be combined with it to provide the required protection functions.
The XT4L 160 breaking part has a rated uninterrupted current of 160 A.
The XT4L performance level provides an ultimate short-circuit breaking capacity of 120 kA at 415 V AC. Its rated service short-circuit breaking capacity at 415 V AC is also 120 kA.
The 1SDA068292R1 is a three-pole, fixed breaking part with front terminals. It is designed for combination with a compatible ABB SACE Tmax XT4 trip unit to create the required MCCB assembly.
ABB SACE Tmax XT modular circuit breaker components provide flexible and dependable solutions for industrial and commercial power distribution, with the XT4L 160 breaking part delivering a 160 A three-pole platform and 120 kA short-circuit breaking performance at 415 V AC for demanding low-voltage installations.