1SDA068176R1 ABB XT4L 250 BREAKING PART 3p F F

1SDA068176R1 ABB XT4L 250 BREAKING PART 3p F F

ABB 1SDA068176R1 XT4L 250 is a three-pole fixed moulded case circuit breaker breaking part with front terminals, a 250 A rated uninterrupted current and 120 kA ultimate breaking capacity at 415 V AC.

SKU: 1SDA068176R1MPN: 1SDA068176R1
Price
List Price £679.32 ex VAT
Your Price (ex VAT) Save 25%
£509.49 25% OFF
You save £169.83 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £509.49
Trade pricing is personalised to your account

Manufacturer Lead Time

£509.49

Why Choose the ABB XT4L 250 Breaking Part 3p F F?

The ABB XT4L 250 BREAKING PART 3p F F, order code 1SDA068176R1, is a three-pole breaking part for ABB SACE Tmax XT4 moulded case circuit breakers. Part of the ABB T-Max XT 250 Range, it provides the breaker body and interruption capability required to assemble a complete XT4L 250 circuit breaker with a compatible ABB trip unit.

Designed with the XT4L high-breaking-capacity performance level, this breaking part has a rated uninterrupted current of 250 A and an ultimate short-circuit breaking capacity of 120 kA at 415 V AC. The breaking part does not itself provide overload or short-circuit trip characteristics; these are determined by the compatible TMA, MA or Ekip electronic trip unit selected for the complete XT4 assembly.

The 1SDA068176R1 features a fixed three-pole configuration with front terminals and a rated voltage of up to 690 V AC. Its compact 105 × 160 × 82.5 mm construction makes it suitable for industrial switchboards, motor control centres and power distribution assemblies requiring high fault-current interruption performance.

Key Advantages

  • Genuine ABB SACE Tmax XT4L 250 breaking part for modular circuit-breaker assembly.
  • 250 A rated uninterrupted current.
  • High 120 kA ultimate breaking capacity at 415 V AC.
  • Three-pole configuration for three-phase electrical systems.
  • Compatible with appropriate ABB XT4 trip units for flexible protection selection.
  • Supports thermomagnetic, magnetic and electronic protection configurations when paired with the applicable trip unit.
  • Fixed construction with front terminals for practical switchboard integration.
  • Compact XT4 frame helps optimise space in electrical distribution assemblies.

Key Features

  • ABB SACE Tmax XT4 series.
  • XT4L 250 breaking part.
  • 250 A rated uninterrupted current.
  • Three-pole configuration.
  • L short-circuit performance level.
  • 120 kA Icu at 415 V AC.
  • Rated voltage up to 690 V AC.
  • Rated frequency of 50/60 Hz.
  • Fixed installation.
  • Front terminals.
  • Designed to accept compatible ABB Tmax XT4 trip units.
  • Compact dimensions of 105 × 160 × 82.5 mm.

Flexible High-Capacity Protection with the Tmax XT4 Platform

The modular construction of the ABB Tmax XT4 platform allows the circuit-breaker breaking part and protection trip unit to be selected separately. The XT4L 250 breaking part provides the current-carrying and fault-interruption capability, while the selected compatible trip unit determines the overload, short-circuit and other protection characteristics of the completed circuit breaker.

With an ultimate breaking capacity of 120 kA at 415 V AC, the 1SDA068176R1 is particularly suited to electrical systems with high prospective short-circuit currents. Its 250 A frame and compatibility with multiple XT4 protection releases allow engineers to configure the finished breaker for distribution, motor protection and other demanding low-voltage applications.

Typical Applications

  • Industrial low-voltage switchboards.
  • Power distribution panels.
  • Motor control centres.
  • Industrial machinery and production systems.
  • Commercial and infrastructure distribution.
  • Feeder and cable protection assemblies.
  • Installations with high prospective short-circuit currents.

Technical Specifications

Series SACE Tmax XT4
Product group T-Max XT 250 Range
Order code 1SDA068176R1
Product type Moulded case circuit breaker breaking part
Frame size XT4 250
Short-circuit performance level L
Rated uninterrupted current 250 A
Number of poles 3
Rated voltage up to 690 V AC
Rated frequency 50/60 Hz
Ultimate breaking capacity Icu at 415 V AC 120 kA
Mounting type Fixed
Terminal arrangement Front terminals
Trip unit Ordered separately
Product net width 105 mm
Product net height 160 mm
Product net depth 82.5 mm
Product net weight 1.65 kg
EAN 8015644020736
Customs tariff number 85362090

Frequently Asked Questions

What is the ABB 1SDA068176R1?

The ABB 1SDA068176R1 is an XT4L 250 three-pole breaking part for ABB SACE Tmax XT4 moulded case circuit breakers, featuring fixed mounting, front terminals and a 120 kA ultimate breaking capacity at 415 V AC.

Is the ABB 1SDA068176R1 a complete circuit breaker?

No. The 1SDA068176R1 is the breaking part of an XT4L 250 circuit breaker. A compatible ABB XT4 trip unit must be selected and ordered to provide the required protection functions and complete the circuit-breaker assembly.

What is the breaking capacity of the ABB XT4L 250 breaking part?

The XT4L 250 breaking part provides an ultimate short-circuit breaking capacity of 120 kA at 415 V AC, making it suitable for installations with high prospective fault-current levels.

What is the current rating of the ABB 1SDA068176R1?

The XT4L 250 breaking part has a rated uninterrupted current of 250 A. The actual protection settings of the completed breaker depend on the compatible trip unit fitted to the breaking part.

What trip units can be used with the ABB XT4L 250 breaking part?

The breaking part is designed to be combined with compatible ABB Tmax XT4 protection trip units. Depending on the required application and configuration, compatible releases include thermomagnetic, magnetic-only and Ekip electronic trip units.

Trusted ABB Circuit Protection

ABB SACE Tmax XT circuit breakers use a flexible modular architecture that combines high-performance breaking parts with application-specific protection releases, providing dependable and configurable protection for industrial, commercial and infrastructure electrical systems.