ABB XT4N 160 3 pole Normal MCCB Electronic trip unit LSIG Ii=40A

ABB XT4N 160 3 pole Normal MCCB Electronic trip unit LSIG Ii=40A

ABB 1SDA068137R1 SACE Tmax XT4N 160 moulded case circuit breaker with Ekip C Dip LSIG electronic trip unit, 40 A rated current, three-pole fixed design and front terminals for low-voltage power distribution.

SKU: 1SDA068137R1Alt SKU: XT4N 160 Ekip LSIG In=40A 3p F FMPN: 1SDA068137R1
Price
List Price £1,854.82 ex VAT
Your Price (ex VAT) Save 25%
£1,391.12 25% OFF
You save £463.71 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,391.12
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,391.12

Why Choose the ABB 1SDA068137R1 XT4N 160 Ekip C Dip LSIG 40A 3P MCCB?

The ABB 1SDA068137R1 is a compact and dependable SACE Tmax XT4N moulded case circuit breaker (MCCB) designed to protect low-voltage electrical distribution systems against overloads, short-circuit faults and earth faults. Featuring an advanced Ekip C Dip LSIG electronic trip unit, this breaker provides long-time, short-time, instantaneous and ground fault protection for industrial, commercial and infrastructure applications.

As part of the trusted ABB SACE Tmax XT series, this fixed three-pole MCCB combines robust construction with precise solid-state protection. Its front terminal configuration allows straightforward installation inside switchboards, control panels, distribution boards and motor control centres where reliable operation, safety and accessibility are essential.

With a 40 A rated current, 690 V AC rated operational voltage and 36 kA breaking capacity at 415 V AC, the ABB 1SDA068137R1 is suitable for feeder protection, machinery circuits, sub-distribution systems and OEM control panels requiring dependable ABB circuit protection with LSIG functionality.

Key Advantages

  • Compact ABB SACE Tmax XT4N moulded case circuit breaker.
  • 40 A rated current for low-voltage power distribution.
  • Ekip C Dip LSIG electronic trip unit for accurate circuit protection.
  • LSIG protection functions including ground fault protection.
  • Three-pole fixed design with front terminal connections.
  • 36 kA short-circuit breaking capacity at 415 V AC.

Key Features

  • ABB SACE Tmax XT series.
  • Model: XT4N 160 Ekip C Dip LSIG In=40A 3P F F.
  • 40 A rated current.
  • 690 V AC rated operational voltage.
  • 36 kA Icu at 415 V AC.
  • Electronic Ekip C Dip LSIG protection release.
  • Three-pole fixed configuration.
  • Front terminals for practical panel installation.

Reliable LSIG Protection for Low-Voltage Systems

Moulded case circuit breakers such as the ABB XT4N help protect electrical installations by disconnecting circuits during overload, short-circuit or earth fault conditions. The Ekip C Dip LSIG electronic release provides accurate protection characteristics, supporting improved selectivity, safety and system reliability.

The SACE Tmax XT range is widely used by panel builders, electrical contractors, OEMs and industrial engineers who require compact, high-performance protection for modern low-voltage distribution networks.

Typical Applications

  • Industrial power distribution panels.
  • Motor control centres and machinery panels.
  • Commercial electrical installations.
  • Feeder and sub-distribution circuit protection.
  • OEM automation and control systems.
  • Infrastructure and process industry switchgear.

Technical Specifications

Tick the specs you need, then view products that match.

Mounting Type Fixed
Application Power distribution
Trip Unit LSIG
Current 40 A
Phase Three Phase
Poles 3-pole
Device Type MCCB
Breaking Capacity 36 kA
Manufacturer ABB
Series SACE Tmax XT
Product ID 1SDA068137R1
EAN 8015644020347
Extended product type XT4N 160 Ekip C Dip LSIG In=40A 3P F F
Product type Moulded Case Circuit Breaker (MCCB)
Rated current (In) 40 A
Rated uninterrupted current (Iu) 160 A
Frame size XT4
Number of poles 3
Rated operational voltage 690 V AC
Rated frequency 50 / 60 Hz
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 8 kV
Ultimate breaking capacity (Icu) 36 kA at 415 V AC
Service breaking capacity (Ics) 36 kA at 415 V AC
Trip unit Ekip C Dip LSIG electronic release
Protection functions LSIG
Terminal type Front terminals
Mounting type Fixed
Standards IEC 60947-2
Dimensions (H × W × D) approx. 160 × 105 × 82.5 mm
Weight approx. 2.5 kg
HS Code 85362090
Country of Manufacture Italy

Frequently Asked Questions

What is the ABB 1SDA068137R1 used for?

It is used to protect low-voltage electrical circuits from overloads, short-circuit faults and earth faults in industrial, commercial and infrastructure power distribution systems.

What is the rated current of this MCCB?

The ABB 1SDA068137R1 has a 40 A rated current.

What type of trip unit does this breaker use?

This model uses an Ekip C Dip LSIG electronic trip unit, providing long-time, short-time, instantaneous and ground fault protection functions.

How many poles does the ABB 1SDA068137R1 have?

This circuit breaker is a three-pole fixed MCCB with front terminal connections.

What is the breaking capacity of this MCCB?

The ABB 1SDA068137R1 has an ultimate short-circuit breaking capacity of 36 kA at 415 V AC.

Trusted by Electrical Professionals Worldwide

ABB SACE Tmax XT moulded case circuit breakers are trusted by panel builders, contractors and engineers worldwide for accurate electronic protection, compact construction and dependable performance in low-voltage electrical systems.