ABB 1SDA068111R1 XT4N 250 moulded case circuit breaker with 250 A thermal magnetic TMA trip unit, four pole fixed design, front terminals and fully rated neutral for low voltage power distribution.
£951.44
The ABB 1SDA068111R1 is a robust ABB SACE Tmax XT4N moulded case circuit breaker (MCCB) designed to provide reliable protection for low voltage electrical distribution systems. Built for industrial, commercial and OEM applications, this fixed four-pole breaker combines dependable overload and short circuit protection with the compact performance of the ABB Tmax XT range.
This MCCB is fitted with a 250 A thermal magnetic TMA trip unit, providing effective protection against overloads and high fault currents. Its fully rated neutral and four-pole configuration make it suitable for three-phase systems where neutral protection and switching are required. The fixed design with front terminals supports straightforward installation within switchboards, distribution panels and control cabinets.
As part of the ABB XT4N 250 series, the 1SDA068111R1 is engineered for demanding electrical environments requiring compact dimensions, reliable switching and consistent circuit protection. With a rated operational voltage up to 690 V AC and instantaneous trip setting from 1250 to 2500 A, it is well suited to modern power distribution systems.
Moulded case circuit breakers such as the ABB XT4N are used to protect electrical circuits against overloads and short circuits. The thermal element responds to sustained overload conditions, while the magnetic element provides rapid tripping during short circuit events, helping reduce equipment damage and improve installation safety.
The ABB 1SDA068111R1 is well suited for switchboard builders, electrical contractors and industrial engineers requiring a compact, high-quality breaker for three-phase power distribution. Its four-pole arrangement and fully rated neutral make it suitable for systems where neutral isolation and protection are important.
Tick the specs you need, then view products that match.
| Mounting Type | Fixed | |
|---|---|---|
| Application | Power distribution | |
| Current | 250 A | |
| Phase | Three Phase | |
| Poles | 4-pole | |
| Device Type | MCCB | |
| Trip Unit | Thermal-magnetic | |
| Manufacturer | ABB | |
| Series | SACE Tmax XT | |
| Model | XT4N 250 TMA 250-2500 4p F F InN=100% | |
| Product code | 1SDA068111R1 | |
| EAN | 8015644695927 | |
| Product type | Moulded Case Circuit Breaker (MCCB) | |
| Frame size | XT4 | |
| Rated current | 250 A | |
| Number of poles | 4 | |
| Neutral rating | 100% fully rated neutral | |
| Trip unit | Thermal Magnetic TMA R 250 | |
| Instantaneous trip setting | 1250 to 2500 A | |
| Rated operational voltage | Up to 690 V AC | |
| Rated insulation voltage | 1000 V | |
| Rated impulse withstand voltage | 8 kV | |
| Frequency | 50 / 60 Hz | |
| Terminal type | Front terminals | |
| Mounting type | Fixed | |
| Dimensions (H × W × D) | approx. 160 × 140 × 82.5 mm | |
| Weight | approx. 2.872 kg | |
| HS Code | 85362090 | |
| Country of Manufacture | Italy |
It is used to protect low voltage electrical circuits against overloads and short circuits in industrial, commercial and OEM power distribution systems.
The ABB 1SDA068111R1 has a rated current of 250 A.
This model is a four-pole fixed MCCB with a fully rated neutral.
It is fitted with a thermal magnetic TMA R 250 trip unit for overload and short circuit protection.
The ABB 1SDA068111R1 uses front terminals, making it suitable for installation in switchboards and electrical panels.
ABB SACE Tmax XT moulded case circuit breakers are widely used by panel builders, electrical contractors and industrial engineers for reliable protection, compact installation and dependable performance in low voltage power distribution systems.