ABB 1SDA067990R1 XT2V 160 is a 160 A three-pole fixed moulded case circuit breaker with an Ekip DIP LSIG electronic trip unit, integrated ground-fault protection and 150 kA ultimate breaking capacity at 400 V AC.
£1,916.33
The ABB XT2V 160 Ekip LSIG In=160A 3p F F, order code 1SDA067990R1, is a high-performance three-pole moulded case circuit breaker (MCCB) designed for comprehensive protection of demanding low-voltage electrical distribution systems. As part of the ABB SACE Tmax XT2 range, it combines compact construction with an advanced Ekip electronic trip unit and very high short-circuit interruption performance for industrial, commercial and infrastructure applications.
This fixed circuit breaker incorporates an ABB Ekip DIP LSIG solid-state electronic trip unit rated at 160 A. The LSIG release provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection, offering a comprehensive protection package with adjustable characteristics for effective coordination within modern electrical distribution networks.
Rated for operation from 220–690 V AC, the XT2V 160 provides an ultimate short-circuit breaking capacity of 150 kA at 400 V AC. Its fixed three-pole construction, front terminals and compact 90 × 130 × 82.5 mm dimensions make it well suited to switchboards, distribution panels, industrial machinery and other installations where high fault-current performance and advanced electronic protection are required.
Electronic circuit breakers equipped with an ABB Ekip LSIG release provide protection against the principal fault conditions encountered in low-voltage distribution systems. The long-time function protects against sustained overloads, the short-time and instantaneous functions respond to short-circuit conditions, and the ground-fault function adds protection against current flowing through unintended earth-fault paths.
The combination of the 160 A Ekip DIP LSIG release, adjustable protection characteristics and the XT2V circuit breaker's 150 kA Icu at 400 V AC makes the 1SDA067990R1 particularly suitable for demanding distribution networks. Its compact XT2 frame also helps optimise panel space while providing comprehensive electronic protection and high fault-current interruption capability.
| Series | SACE Tmax XT2 |
|---|---|
| Product group | T-Max XT 250 Range |
| Order code | 1SDA067990R1 |
| Product type | Moulded case circuit breaker |
| Frame size | XT2 160 |
| Short-circuit performance level | V |
| Rated current | 160 A |
| Rated uninterrupted current | 160 A |
| Number of poles | 3 |
| Trip unit | Ekip DIP LSIG |
| Release technology | Solid-state electronic |
| Protection functions | Long-time, short-time, instantaneous and ground fault |
| Overload release adjustment | 64–160 A |
| Short-time short-circuit adjustment | 160–1600 A |
| Instantaneous short-circuit adjustment | 160–1600 A |
| Ground-fault protection | Integrated |
| Rated voltage | 220–690 V AC |
| Ultimate breaking capacity Icu at 400 V AC | 150 kA |
| Mounting type | Fixed |
| Terminal arrangement | Front terminals |
| DIN rail mounting | Optional |
| Motor drive | Optional |
| Standard | IEC |
| Product net width | 90 mm |
| Product net height | 130 mm |
| Product net depth | 82.5 mm |
| Product net weight | 1.12 kg |
| EAN | 8015644018863 |
| Customs tariff number | 85362090 |
| Country of origin | Italy |
The ABB 1SDA067990R1 is a three-pole moulded case circuit breaker designed to protect low-voltage electrical distribution circuits against overload, short-circuit and ground-fault conditions using an electronic Ekip DIP LSIG trip unit.
The Ekip DIP LSIG electronic release fitted to this circuit breaker has a rated current of 160 A, with an overload release adjustment range of 64–160 A.
The Ekip DIP LSIG electronic trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection.
The 1SDA067990R1 provides an ultimate short-circuit breaking capacity of 150 kA at 400 V AC, making it suitable for demanding installations with high prospective fault currents.
Yes. The G function in the Ekip LSIG trip unit provides integrated ground-fault protection in addition to long-time, short-time and instantaneous protection functions.
ABB SACE Tmax XT moulded case circuit breakers combine compact construction, advanced Ekip electronic protection and high short-circuit performance to provide dependable protection for modern industrial, commercial and infrastructure electrical distribution systems.