1SDA067973R1 ABB XT2V 160 Ekip LS/I In=63A 3P Fixed Circuit Breaker

1SDA067973R1 ABB XT2V 160 Ekip LS/I In=63A 3P Fixed Circuit Breaker

ABB 1SDA067973R1 is an XT2V 160 three-pole fixed moulded case circuit breaker with front terminals, a 63 A rated current and an Ekip DIP LS/I solid-state electronic trip unit for low-voltage power distribution protection.

SKU: 1SDA067973R1MPN: 1SDA067973R1
Price
List Price £1,317.26 ex VAT
Your Price (ex VAT) Save 25%
£987.95 25% OFF
You save £329.32 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £987.95
Trade pricing is personalised to your account

Manufacturer Lead Time

£987.95

Why Choose the ABB XT2V 160 Ekip LS/I In=63A 3P Fixed Circuit Breaker?

The ABB XT2V 160 Ekip LS/I In=63A 3P F F is a high-performance moulded case circuit breaker (MCCB) designed for reliable protection of low-voltage AC power distribution circuits. As part of the ABB SACE Tmax XT2 series, it combines the compact XT2 frame with an Ekip DIP LS/I solid-state electronic trip unit for accurate overload and short-circuit protection.

This XT2V configuration features a fixed three-pole construction with front terminals, providing a practical arrangement for integration into industrial switchboards, commercial distribution panels and OEM electrical assemblies. The V short-circuit performance level provides an ultimate short-circuit breaking capacity of 150 kA at 415 V AC, supporting demanding installations with high prospective fault currents.

With a rated current of 63 A and an Ekip LS/I electronic protection release, the breaker provides long-time overload, short-time and instantaneous short-circuit protection. Its overload setting range of 25.2–63 A, rated operational voltage up to 690 V AC and high breaking performance provide flexible and dependable protection for modern low-voltage distribution systems.

Key Advantages

  • High-performance ABB SACE Tmax XT2V moulded case circuit breaker.
  • 63 A rated current for low-voltage AC power distribution.
  • Ekip DIP LS/I electronic trip unit for overload and short-circuit protection.
  • Adjustable overload setting range of 25.2–63 A.
  • High 150 kA ultimate breaking capacity at 415 V AC.
  • Three-pole fixed construction with front terminals for efficient switchboard integration.

Key Features

  • ABB SACE Tmax XT2 series.
  • XT2V 160 configuration.
  • 63 A rated current.
  • Ekip DIP LS/I solid-state electronic protection release.
  • Long-time, short-time and instantaneous protection functions.
  • Three-pole configuration.
  • Fixed mounting arrangement.
  • Front terminal connections.
  • V short-circuit performance level.
  • Rated operational voltage up to 690 V AC.

Reliable Electronic Protection for Power Distribution

The ABB Tmax XT2V protects low-voltage electrical distribution systems by disconnecting circuits when damaging overload or short-circuit conditions occur. Its Ekip LS/I solid-state electronic release provides adjustable long-time overload protection together with short-time and instantaneous short-circuit protection, helping safeguard cables, distribution equipment and connected electrical loads.

The XT2V combines configurable electronic protection with high short-circuit interruption capability in a compact breaker platform. Its fixed three-pole construction and front terminal arrangement make it well suited to industrial switchboards, commercial distribution panels and OEM electrical assemblies requiring dependable protection, selective coordination and efficient panel integration.

Typical Applications

  • Industrial low-voltage distribution switchboards.
  • Commercial electrical distribution panels.
  • Feeder and branch circuit protection.
  • Power distribution systems with high prospective fault currents.
  • Industrial machinery and automation panels.
  • Infrastructure and building electrical systems.
  • OEM switchgear and electrical distribution assemblies.

Technical Specifications

Series SACE Tmax XT2
ABB order code 1SDA067973R1
Product type Moulded case circuit breaker
Frame size XT2
Rated uninterrupted current (Iu) 160 A
Rated current (In) 63 A
Protection release Ekip DIP LS/I solid-state electronic
Protection functions Long-time, short-time and instantaneous protection
Overload release current setting 25.2–63 A
Short-time short-circuit adjustment 63–630 A
Instantaneous short-circuit adjustment 63–630 A
Number of poles 3
Mounting Fixed
Terminal arrangement Front terminals
Terminal type Bolt
Current type AC
Rated operational voltage 220–690 V AC
Rated frequency 50 / 60 Hz
Ultimate short-circuit breaking capacity (Icu) at 415 V AC 150 kA
Ultimate short-circuit breaking capacity (Icu) at 690 V AC 20 kA
Service short-circuit breaking capacity (Ics) at 690 V AC 15 kA
Short-circuit performance level V
Standard IEC 60947-2
Dimensions (W × H × D) 90 × 130 × 82.5 mm
Product net weight 1.12 kg
EAN 8015644018696

Frequently Asked Questions

What is the ABB 1SDA067973R1?

The ABB 1SDA067973R1 is an XT2V 160 three-pole fixed moulded case circuit breaker with front terminals, a 63 A rated current and an Ekip DIP LS/I solid-state electronic protection release.

What is the rated current of this XT2V circuit breaker?

This XT2V configuration has a rated current of 63 A within the ABB Tmax XT2 160 frame, with an overload release setting range of 25.2–63 A.

What protection does the Ekip LS/I release provide?

The Ekip LS/I electronic release provides long-time overload protection together with short-time and instantaneous short-circuit protection for the connected low-voltage distribution circuit.

What is the breaking capacity of the ABB XT2V 160?

This XT2V configuration provides an ultimate short-circuit breaking capacity of 150 kA at 415 V AC and 20 kA at 690 V AC.

What voltage is the ABB 1SDA067973R1 rated for?

The circuit breaker is designed for AC operation with a rated operational voltage range of 220–690 V AC.

How is the ABB 1SDA067973R1 installed?

The breaker is supplied in a fixed three-pole configuration with front terminals for integration into suitable low-voltage switchboards, distribution panels and electrical assemblies.

Trusted by Electrical Professionals Worldwide

ABB SACE Tmax XT moulded case circuit breakers are widely used by panel builders, electrical engineers and industrial operators for dependable electronic circuit protection, compact switchboard integration and high-performance low-voltage power distribution.