Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA067965R1 XT2L 160 is a four-pole Tmax XT moulded case circuit breaker with a 10 A Ekip LSIG electronic trip unit, integrated earth-fault protection and 120 kA ultimate breaking capacity at 400 V AC.
£1,353.33
The ABB 1SDA067965R1 XT2L 160 Ekip LSIG In=10A 4p F F is a high-performance four-pole moulded case circuit breaker (MCCB) designed for comprehensive protection and isolation in industrial and commercial low-voltage power distribution systems. As part of the advanced ABB SACE Tmax XT range, it combines the compact XT2 160 frame with electronic protection and high short-circuit breaking capability.
This fixed circuit breaker is equipped with an ABB Ekip LSIG electronic trip unit rated at 10 A. The LSIG release provides long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection, delivering comprehensive electronic protection for critical distribution circuits. Its overload release setting is adjustable from 4–10 A, while both short-time delayed and instantaneous short-circuit settings cover 10–100 A.
The XT2L performance level provides an ultimate short-circuit breaking capacity of 120 kA at 400 V AC. With a rated voltage range of 220–690 V AC, four-pole configuration, fixed mounting and front terminals, the 1SDA067965R1 is well suited to switchboards and distribution systems requiring precise electronic protection, integrated earth-fault protection and high fault-clearing capability.
Moulded case circuit breakers such as the ABB Tmax XT2 protect electrical circuits and connected equipment against potentially damaging overloads, short circuits and earth faults. The Ekip LSIG electronic release provides four principal protection functions, allowing the breaker to respond appropriately to long-duration overloads, delayed short-circuit conditions, severe instantaneous faults and earth-fault currents.
The XT2L combines this comprehensive electronic protection with high short-circuit interruption capability in a compact four-pole MCCB format. Its integrated earth-fault protection, configurable trip characteristics, fixed configuration and front terminals make it particularly suitable for low-voltage switchboards where dependable protection, coordination and efficient use of panel space are required.
| Series | SACE Tmax XT2 |
|---|---|
| ABB product group | T-Max XT 250 Range |
| Order code | 1SDA067965R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Frame size | XT2 160 |
| Short-circuit performance level | L |
| Trip unit rated current | 10 A |
| Rated uninterrupted current | 160 A |
| Trip unit | Ekip LSIG |
| Release type | Electronic / solid-state |
| Protection functions | Long-time, short-time, instantaneous and earth-fault (LSIG) |
| Overload release setting | 4–10 A |
| Short-time delayed short-circuit setting | 10–100 A |
| Instantaneous short-circuit setting | 10–100 A |
| Integrated earth-fault protection | Yes |
| Rated voltage | 220–690 V AC |
| Rated frequency | 50 / 60 Hz |
| Ultimate breaking capacity at 400 V AC | 120 kA |
| Number of poles | 4 |
| Mounting type | Fixed |
| Terminal arrangement | Front terminals |
| Motor operator | Optional |
| Electrical durability | 8,000 cycles |
| Mechanical durability | 25,000 cycles |
| Dimensions (H × W × D) | 130 × 120 × 82.5 mm |
| Weight | approx. 1.5 kg |
The ABB 1SDA067965R1 is a four-pole moulded case circuit breaker designed to provide electronic overload, short-circuit and earth-fault protection in industrial and commercial low-voltage power distribution systems.
The circuit breaker is fitted with an Ekip LSIG trip unit rated at 10 A, with an adjustable overload release setting of 4–10 A.
The XT2L performance level provides an ultimate short-circuit breaking capacity of 120 kA at 400 V AC.
The Ekip LSIG electronic trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection.
Yes. The Ekip LSIG trip unit includes integrated earth-fault protection, in addition to overload and short-circuit protection functions.
ABB SACE Tmax XT moulded case circuit breakers are widely used in industrial and commercial power distribution systems where compact installation, configurable electronic protection, earth-fault protection and high short-circuit performance are required.
We use cookies