1SDA067959R1 ABB XT2L 160 Ekip LSI In=10A 4p F F Moulded Case Circuit Breaker

1SDA067959R1 ABB XT2L 160 Ekip LSI In=10A 4p F F Moulded Case Circuit Breaker

ABB 1SDA067959R1 XT2L 160 is a 10 A four-pole fixed moulded case circuit breaker with an Ekip LSI solid-state electronic trip unit, 690 V AC rating and 120 kA ultimate breaking capacity at 415 V AC.

SKU: 1SDA067959R1MPN: 1SDA067959R1
Price
List Price £1,602.27 ex VAT
Your Price (ex VAT) Save 25%
£1,201.70 25% OFF
You save £400.57 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,201.70
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,201.70

Why Choose the ABB XT2L 160 Ekip LSI In=10A 4p F F Circuit Breaker?

The ABB XT2L 160 Ekip LSI In=10A 4p F F, order code 1SDA067959R1, is a high-performance four-pole moulded case circuit breaker (MCCB) designed for precise protection of low-voltage electrical distribution systems. As part of the ABB SACE Tmax XT2 range, it combines a compact frame with an advanced electronic trip unit and high short-circuit breaking performance for industrial, commercial and infrastructure applications.

This fixed circuit breaker incorporates an ABB Ekip LSI solid-state electronic trip unit with a rated current of 10 A. The LSI release provides long-time overload, short-time short-circuit and instantaneous short-circuit protection, enabling accurate electronic protection and effective coordination with other protective devices within the electrical distribution system.

Rated for operation at up to 690 V AC, the XT2L 160 combines four-pole switching with fixed mounting and front terminals for straightforward integration into switchboards and distribution assemblies. The XT2L performance level provides a 120 kA ultimate short-circuit breaking capacity at 415 V AC, making this compact breaker suitable for demanding installations with high prospective fault currents.

Key Advantages

  • Compact ABB Tmax XT2 moulded case circuit breaker for low-voltage distribution protection.
  • 10 A Ekip LSI electronic trip unit for precise protection of lower-current circuits.
  • Provides long-time, short-time and instantaneous protection.
  • Four-pole configuration for three-phase four-wire distribution systems.
  • High 120 kA ultimate breaking capacity at 415 V AC.
  • Fixed construction with front terminals for straightforward switchboard integration.

Key Features

  • ABB SACE Tmax XT2 series.
  • XT2L 160 moulded case circuit breaker.
  • 10 A rated Ekip LSI release.
  • Four-pole configuration.
  • Ekip LSI solid-state electronic trip unit.
  • Long-time overload protection.
  • Short-time short-circuit protection.
  • Instantaneous short-circuit protection.
  • Rated operational voltage of 690 V AC.
  • Rated impulse withstand voltage of 8 kV.
  • Rated frequency of 50/60 Hz.
  • L short-circuit performance level.
  • Fixed installation with front terminals.
  • Compact four-pole dimensions of 120 × 130 × 82.5 mm.

Advanced Electronic Protection for Four-Pole Distribution Systems

Electronic circuit breakers such as the ABB XT2L with an Ekip LSI release provide precise protection against overload and short-circuit conditions. The LSI protection functions cover long-time overload protection, short-time short-circuit protection and instantaneous short-circuit protection, enabling effective coordination with downstream circuits and other protective devices.

The combination of a 10 A Ekip LSI electronic release, four-pole construction and the XT2L circuit breaker's high interruption capability makes the 1SDA067959R1 particularly useful for lower-current three-phase four-wire circuits where accurate electronic protection is required. Its compact dimensions also help optimise available space within modern low-voltage switchboards.

Typical Applications

  • Three-phase four-wire low-voltage distribution systems.
  • Industrial electrical switchboards.
  • Commercial distribution panels.
  • Lower-current feeder and branch-circuit protection.
  • Industrial machinery and production systems.
  • Building-services electrical distribution.
  • Control panels and automation systems.

Technical Specifications

Series SACE Tmax XT2
Product group T-Max XT 250 Range
Order code 1SDA067959R1
Product type Moulded case circuit breaker
Frame size XT2 160
Short-circuit performance level L
Rated current 10 A
Rated uninterrupted current 160 A
Number of poles 4
Trip unit Ekip LSI
Release technology Solid-state electronic
Protection functions Long-time, short-time and instantaneous
Rated operational voltage 690 V AC
Rated impulse withstand voltage 8 kV
Rated frequency 50/60 Hz
Ultimate breaking capacity Icu at 415 V AC 120 kA
Mounting type Fixed
Terminal arrangement Front terminals
Standards / approvals IEC, CE, RoHS
Product net width 120 mm
Product net height 130 mm
Product net depth 82.5 mm
Country of origin Italy

Frequently Asked Questions

What is the ABB 1SDA067959R1 used for?

The ABB 1SDA067959R1 is a four-pole moulded case circuit breaker designed to protect low-voltage electrical distribution circuits against overload and short-circuit faults using an electronic Ekip LSI trip unit.

What is the rated current of the ABB XT2L 160 Ekip LSI?

The Ekip LSI electronic release fitted to this circuit breaker has a rated current of 10 A.

What protection functions does the Ekip LSI trip unit provide?

The Ekip LSI electronic trip unit provides long-time overload protection, short-time short-circuit protection and instantaneous short-circuit protection.

What is the breaking capacity of the ABB XT2L 160?

The XT2L version provides an ultimate short-circuit breaking capacity of 120 kA at 415 V AC, giving it high fault-current interruption capability for demanding low-voltage distribution systems.

How is the ABB XT2L 160 Ekip LSI installed?

This model is a fixed four-pole circuit breaker with front terminals, designed for installation within electrical switchboards, distribution panels and industrial power distribution assemblies.

Trusted ABB Electronic Circuit Protection

ABB SACE Tmax XT moulded case circuit breakers combine compact construction, high short-circuit performance and advanced Ekip electronic protection to provide dependable circuit protection for modern industrial, commercial and infrastructure electrical distribution systems.