1SDA067955R1 ABB XT2L 160 Ekip I In=63A 4P Fixed Circuit Breaker

1SDA067955R1 ABB XT2L 160 Ekip I In=63A 4P Fixed Circuit Breaker

ABB 1SDA067955R1 is an XT2L 160 four-pole fixed moulded case circuit breaker with front terminals, a 63 A rated current and an Ekip I solid-state electronic trip unit for instantaneous short-circuit protection.

SKU: 1SDA067955R1MPN: 1SDA067955R1
Price
List Price £1,062.22 ex VAT
Your Price (ex VAT) Save 25%
£796.67 25% OFF
You save £265.56 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £796.67
Trade pricing is personalised to your account

Manufacturer Lead Time

£796.67

Why Choose the ABB XT2L 160 Ekip I In=63A 4P Fixed Circuit Breaker?

The ABB XT2L 160 Ekip I In=63A 4P F F is a high-performance moulded case circuit breaker (MCCB) designed for short-circuit protection in low-voltage power distribution systems. As part of the ABB SACE Tmax XT2 series, it combines the compact XT2 frame with an Ekip I solid-state electronic trip unit for dependable protection in industrial and commercial electrical installations.

This XT2L configuration features a fixed four-pole construction with front terminals, providing a practical arrangement for installation within switchboards, distribution panels and electrical assemblies. The L short-circuit performance level provides an ultimate breaking capacity of 120 kA at 415 V AC and 18 kA at 690 V AC, delivering robust fault interruption across a wide range of low-voltage applications.

With a rated current of 63 A and an Ekip I electronic trip unit, the breaker provides instantaneous short-circuit protection with a magnetic-equivalent electronic setting adjustable from 1–10 × In. Its four-pole configuration, rated operational voltage of 690 V AC and compact fixed design make it suitable for three-phase four-wire distribution systems requiring reliable electronic fault protection.

Key Advantages

  • High-performance ABB SACE Tmax XT2L moulded case circuit breaker.
  • 63 A rated current for low-voltage power distribution.
  • Ekip I solid-state electronic trip unit for short-circuit protection.
  • Adjustable instantaneous protection over a 1–10 × In range.
  • High 120 kA ultimate breaking capacity at 415 V AC.
  • Four-pole fixed construction with front terminals for efficient switchboard integration.

Key Features

  • ABB SACE Tmax XT2 series.
  • XT2L 160 frame configuration.
  • 63 A rated current.
  • Ekip DIP I solid-state electronic protection release.
  • Instantaneous short-circuit protection.
  • 1–10 × In adjustable protection range.
  • Four-pole configuration.
  • Fixed mounting arrangement.
  • Front terminal connections.
  • Rated operational voltage of 690 V AC.

Reliable Electronic Short-Circuit Protection for Power Distribution

Moulded case circuit breakers such as the ABB Tmax XT2 protect electrical distribution systems by automatically disconnecting circuits when severe fault currents occur. The Ekip I solid-state release provides instantaneous electronic short-circuit protection, allowing rapid interruption of fault currents while offering an adjustable protection threshold for coordination with the electrical distribution system.

The XT2L combines electronic protection with high short-circuit interruption performance in a compact breaker frame. Its four-pole fixed construction and front terminal arrangement make it well suited to three-phase four-wire switchboards, commercial distribution panels and OEM electrical assemblies requiring dependable fault protection and efficient panel integration.

Typical Applications

  • Industrial low-voltage distribution switchboards.
  • Commercial electrical distribution panels.
  • Three-phase four-wire power distribution systems.
  • Circuits requiring electronic instantaneous short-circuit protection.
  • Industrial machinery and automation electrical panels.
  • Infrastructure and building electrical systems.
  • OEM switchgear and electrical distribution assemblies.

Technical Specifications

Series SACE Tmax XT2
ABB order code 1SDA067955R1
Product type Moulded case circuit breaker
Frame size XT2
Rated uninterrupted current (Iu) 160 A
Rated current (In) 63 A
Protection release Ekip DIP I solid-state electronic
Protection function Instantaneous short-circuit protection
Instantaneous protection adjustment 1–10 × In
Number of poles 4
Mounting Fixed
Terminal arrangement Front terminals
Current type AC
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 8 kV
Rated frequency 50 / 60 Hz
Ultimate short-circuit breaking capacity (Icu) at 415 V AC 120 kA
Service short-circuit breaking capacity (Ics) at 415 V AC 120 kA
Ultimate short-circuit breaking capacity (Icu) at 690 V AC 18 kA
Service short-circuit breaking capacity (Ics) at 690 V AC 15 kA
Short-circuit performance level L
Standard IEC 60947-2
Dimensions (H × W × D) 130 × 120 × 82.5 mm
Product net weight approx. 1.6 kg
EAN 8015644018511

Frequently Asked Questions

What is the ABB 1SDA067955R1?

The ABB 1SDA067955R1 is an XT2L 160 four-pole fixed moulded case circuit breaker with front terminals, a 63 A rated current and an Ekip I solid-state electronic protection release.

What is the rated current of this XT2L circuit breaker?

This XT2L configuration has a rated current of 63 A and uses the ABB Tmax XT2 160 frame.

What protection does the Ekip I trip unit provide?

The Ekip I electronic trip unit provides instantaneous short-circuit protection, with the protection threshold adjustable over a range of 1–10 times the rated current.

What is the breaking capacity of the ABB XT2L 160?

This XT2L configuration provides an ultimate short-circuit breaking capacity of 120 kA at 415 V AC and 18 kA at 690 V AC.

How many poles does the ABB 1SDA067955R1 have?

The breaker has a four-pole configuration, making it suitable for appropriate three-phase four-wire low-voltage distribution systems.

How is the ABB 1SDA067955R1 installed?

The circuit breaker is supplied in a fixed four-pole configuration with front terminals for integration into suitable switchboards, distribution panels and electrical assemblies.

Trusted by Electrical Professionals Worldwide

ABB SACE Tmax XT moulded case circuit breakers are widely used by panel builders, electrical engineers and industrial operators for dependable electronic circuit protection, compact switchboard integration and high-performance low-voltage power distribution.