ABB 1SDA067955R1 is an XT2L 160 four-pole fixed moulded case circuit breaker with front terminals, a 63 A rated current and an Ekip I solid-state electronic trip unit for instantaneous short-circuit protection.
£796.67
The ABB XT2L 160 Ekip I In=63A 4P F F is a high-performance moulded case circuit breaker (MCCB) designed for short-circuit protection in low-voltage power distribution systems. As part of the ABB SACE Tmax XT2 series, it combines the compact XT2 frame with an Ekip I solid-state electronic trip unit for dependable protection in industrial and commercial electrical installations.
This XT2L configuration features a fixed four-pole construction with front terminals, providing a practical arrangement for installation within switchboards, distribution panels and electrical assemblies. The L short-circuit performance level provides an ultimate breaking capacity of 120 kA at 415 V AC and 18 kA at 690 V AC, delivering robust fault interruption across a wide range of low-voltage applications.
With a rated current of 63 A and an Ekip I electronic trip unit, the breaker provides instantaneous short-circuit protection with a magnetic-equivalent electronic setting adjustable from 1–10 × In. Its four-pole configuration, rated operational voltage of 690 V AC and compact fixed design make it suitable for three-phase four-wire distribution systems requiring reliable electronic fault protection.
Moulded case circuit breakers such as the ABB Tmax XT2 protect electrical distribution systems by automatically disconnecting circuits when severe fault currents occur. The Ekip I solid-state release provides instantaneous electronic short-circuit protection, allowing rapid interruption of fault currents while offering an adjustable protection threshold for coordination with the electrical distribution system.
The XT2L combines electronic protection with high short-circuit interruption performance in a compact breaker frame. Its four-pole fixed construction and front terminal arrangement make it well suited to three-phase four-wire switchboards, commercial distribution panels and OEM electrical assemblies requiring dependable fault protection and efficient panel integration.
| Series | SACE Tmax XT2 |
|---|---|
| ABB order code | 1SDA067955R1 |
| Product type | Moulded case circuit breaker |
| Frame size | XT2 |
| Rated uninterrupted current (Iu) | 160 A |
| Rated current (In) | 63 A |
| Protection release | Ekip DIP I solid-state electronic |
| Protection function | Instantaneous short-circuit protection |
| Instantaneous protection adjustment | 1–10 × In |
| Number of poles | 4 |
| Mounting | Fixed |
| Terminal arrangement | Front terminals |
| Current type | AC |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Rated frequency | 50 / 60 Hz |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 120 kA |
| Service short-circuit breaking capacity (Ics) at 415 V AC | 120 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 18 kA |
| Service short-circuit breaking capacity (Ics) at 690 V AC | 15 kA |
| Short-circuit performance level | L |
| Standard | IEC 60947-2 |
| Dimensions (H × W × D) | 130 × 120 × 82.5 mm |
| Product net weight | approx. 1.6 kg |
| EAN | 8015644018511 |
The ABB 1SDA067955R1 is an XT2L 160 four-pole fixed moulded case circuit breaker with front terminals, a 63 A rated current and an Ekip I solid-state electronic protection release.
This XT2L configuration has a rated current of 63 A and uses the ABB Tmax XT2 160 frame.
The Ekip I electronic trip unit provides instantaneous short-circuit protection, with the protection threshold adjustable over a range of 1–10 times the rated current.
This XT2L configuration provides an ultimate short-circuit breaking capacity of 120 kA at 415 V AC and 18 kA at 690 V AC.
The breaker has a four-pole configuration, making it suitable for appropriate three-phase four-wire low-voltage distribution systems.
The circuit breaker is supplied in a fixed four-pole configuration with front terminals for integration into suitable switchboards, distribution panels and electrical assemblies.
ABB SACE Tmax XT moulded case circuit breakers are widely used by panel builders, electrical engineers and industrial operators for dependable electronic circuit protection, compact switchboard integration and high-performance low-voltage power distribution.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.