ABB 1SDA067947R1 XT2L 160 is a four-pole Tmax XT moulded case circuit breaker with a 10 A Ekip LS/I electronic trip unit, adjustable overload and short-circuit protection, fixed mounting and 120 kA ultimate breaking capacity at 415 V AC.
£726.78
The ABB 1SDA067947R1 XT2L 160 Ekip LS/I In=10A 4p F F is a high-performance four-pole moulded case circuit breaker (MCCB) designed for reliable protection and isolation in industrial and commercial low-voltage power distribution systems. As part of the advanced ABB SACE Tmax XT range, it combines the compact XT2 160 frame with an electronic trip unit and high short-circuit breaking performance.
This fixed circuit breaker is equipped with an ABB Ekip LS/I electronic trip unit rated at 10 A. The electronic release provides long-time overload protection together with short-circuit protection, offering an adjustable overload setting of 4–10 A and a short-circuit protection threshold of 10–100 A. This allows protection characteristics to be configured for the requirements of the connected circuit.
The XT2L performance level provides an ultimate short-circuit breaking capacity of 120 kA at 415 V AC. With a four-pole configuration, rated operational voltage up to 690 V AC, fixed mounting and front terminals, the 1SDA067947R1 is well suited to switchboards and distribution systems requiring precise electronic protection and high fault-clearing capability.
Moulded case circuit breakers such as the ABB Tmax XT2 protect electrical circuits and connected equipment against potentially damaging overload and short-circuit currents. The Ekip LS/I electronic release provides configurable long-time overload and short-circuit protection, allowing the breaker characteristics to be matched more closely to the requirements of the protected circuit.
The XT2L combines this electronic protection with high short-circuit interruption capability in a compact four-pole MCCB format. Its fixed configuration and front terminals make it particularly suitable for low-voltage switchboards and distribution assemblies where dependable protection, high fault-clearing performance and efficient use of panel space are required.
| Series | SACE Tmax XT2 |
|---|---|
| ABB product group | T-Max XT 250 Range |
| Order code | 1SDA067947R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Frame size | XT2 160 |
| Short-circuit performance level | L |
| Trip unit rated current | 10 A |
| Trip unit | Ekip LS/I |
| Release type | Electronic / solid-state |
| Overload setting | 4–10 A |
| Short-circuit setting | 10–100 A |
| Rated operational voltage | up to 690 V AC |
| Rated impulse withstand voltage | 8 kV |
| Rated frequency | 50 / 60 Hz |
| Ultimate breaking capacity at 415 V AC | 120 kA |
| Ultimate breaking capacity at 440 V AC | 100 kA |
| Ultimate breaking capacity at 500 V AC | 60 kA |
| Ultimate breaking capacity at 690 V AC | 18 kA |
| Number of poles | 4 |
| Mounting type | Fixed |
| Terminal arrangement | Front terminals |
| Terminal type | Bolt |
| Standard | IEC 60947-2 |
| Dimensions (H × W × D) | 130 × 120 × 82.5 mm |
| Weight | approx. 1.5 kg |
| Country of origin | Italy |
The ABB 1SDA067947R1 is a four-pole moulded case circuit breaker designed to provide electronic overload and short-circuit protection in industrial and commercial low-voltage power distribution systems.
The circuit breaker is fitted with an Ekip LS/I trip unit rated at 10 A, with an adjustable overload setting of 4–10 A.
The XT2L performance level provides an ultimate short-circuit breaking capacity of 120 kA at 415 V AC.
The Ekip LS/I electronic trip unit provides long-time overload and short-circuit protection, with a 4–10 A overload setting and a 10–100 A short-circuit setting.
The breaker is a fixed four-pole unit with front terminals, designed for installation within low-voltage switchboards, distribution panels and industrial electrical assemblies.
ABB SACE Tmax XT moulded case circuit breakers are widely used in industrial and commercial power distribution systems where compact installation, configurable electronic protection and high short-circuit performance are required.