1SDA067944R1 ABB XT2L 160 Ekip M-I In=32A 3P F F Moulded-Case Circuit Breaker

1SDA067944R1 ABB XT2L 160 Ekip M-I In=32A 3P F F Moulded-Case Circuit Breaker

ABB 1SDA067944R1 is a 32 A three-pole XT2L 160 moulded-case circuit breaker with an Ekip M-I electronic release, adjustable 192–448 A instantaneous short-circuit protection, fixed mounting and front terminals.

SKU: 1SDA067944R1MPN: 1SDA067944R1
Price
List Price £1,522.20 ex VAT
Your Price (ex VAT) Save 25%
£1,141.65 25% OFF
You save £380.55 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,141.65
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,141.65

Why Choose the ABB XT2L 160 Ekip M-I In=32A 3P F F Circuit Breaker?

The ABB 1SDA067944R1 is a high-performance moulded-case circuit breaker (MCCB) designed for motor and installation protection in low-voltage electrical systems. Part of the ABB SACE Tmax XT series, this XT2L 160 combines a 32 A rated current with an Ekip M-I solid-state electronic release for precise motor short-circuit protection.

The Ekip M-I electronic release is specifically suited to motor-protection applications where overload protection is coordinated separately. Its adjustable instantaneous magnetic protection range of 192–448 A, equivalent to 6–14 times the 32 A rated current, allows the breaker to tolerate normal motor starting currents while rapidly interrupting genuine short-circuit faults.

This model is supplied as a fixed three-pole circuit breaker with front terminals. The XT2L short-circuit performance level provides a rated ultimate short-circuit breaking capacity of 120 kA at 415 V AC, combining electronic motor protection with high fault-clearing capability in the compact Tmax XT2 platform.

Key Advantages

  • 32 A rated current for motor and industrial circuit-protection applications.
  • Ekip M-I electronic release optimised for motor short-circuit protection.
  • 192–448 A adjustable instantaneous protection range for coordination with motor starting currents.
  • High 120 kA ultimate breaking capacity at 415 V AC.
  • Three-pole fixed configuration suited to three-phase electrical systems.
  • Front terminals support straightforward integration into motor control centres and switchboards.

Key Features

  • ABB SACE Tmax XT2L 160 circuit breaker.
  • 32 A rated current.
  • Ekip M-I solid-state electronic trip unit.
  • 192–448 A adjustable instantaneous short-circuit setting.
  • 6–14 × In instantaneous adjustment range.
  • Three-pole configuration.
  • L short-circuit performance level.
  • Fixed mounting with front bolt terminal connections.

Electronic Short-Circuit Protection for Motor Circuits

Motor circuits require short-circuit protection that can distinguish between a genuine electrical fault and the high inrush current that occurs during normal motor starting. The Ekip M-I electronic release provides adjustable instantaneous protection designed for this purpose, while motor overload protection can be coordinated through an appropriate separate protection device.

For the ABB 1SDA067944R1, the 192–448 A instantaneous setting range provides adjustment from 6–14 times the 32 A rated current. Combined with the XT2L platform's 120 kA breaking capacity at 415 V AC, this makes the breaker a robust solution for three-phase motor circuits and demanding industrial installations.

Typical Applications

  • Three-phase motor circuits with coordinated overload protection.
  • Industrial motor control centres.
  • Machinery and automation control panels.
  • Pumps, fans, compressors and conveyor systems.
  • Industrial low-voltage switchboards.
  • OEM machinery and electrical panel building.

Technical Specifications

Series SACE Tmax XT
Product group T-Max XT 250 Range
Order code 1SDA067944R1
Product type Moulded-case circuit breaker (MCCB)
Application Motor and installation protection
Frame size XT2
Frame rated uninterrupted current (Iu) 160 A
Rated current (In) 32 A
Trip unit Ekip M-I electronic release
Instantaneous short-circuit setting (Im) 192–448 A
Instantaneous adjustment range 6–14 × In
Number of poles 3
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 8 kV
Rated frequency 50 / 60 Hz
Short-circuit performance level L
Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC 120 kA
Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC 120 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC 60 kA
Rated ultimate short-circuit breaking capacity (Icu) at 525 V AC 36 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 18 kA
Rated service short-circuit breaking capacity (Ics) at 415 V AC 120 kA
Mounting type Fixed
Terminal connection Front
Terminal type Bolt
Main-circuit tightening torque 6 N·m
Dimensions (W × H × D) 90 × 130 × 82.5 mm
Net weight 1.12 kg
GTIN / EAN 8015644018405
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA067944R1 used for?

The ABB 1SDA067944R1 is a 32 A moulded-case circuit breaker equipped with an Ekip M-I electronic release for short-circuit protection in low-voltage motor and installation applications.

What is the instantaneous protection range of the ABB XT2L 160 Ekip M-I 32A?

The instantaneous short-circuit protection can be adjusted from 192–448 A, corresponding to 6–14 times the 32 A rated current.

What does Ekip M-I mean on the ABB 1SDA067944R1?

Ekip M-I identifies ABB's electronic protection release for motor applications, providing adjustable instantaneous short-circuit protection suitable for coordination with motor starting characteristics.

What is the breaking capacity of the ABB 1SDA067944R1?

The XT2L version has a rated ultimate short-circuit breaking capacity of 120 kA at 415 V AC, providing high fault-interruption capability for demanding low-voltage installations.

How is the ABB 1SDA067944R1 installed?

The ABB 1SDA067944R1 is a fixed three-pole circuit breaker with front bolt terminals, designed for integration into compatible motor control centres, switchboards and electrical panels.

Trusted ABB Motor Circuit Protection

ABB SACE Tmax XT moulded-case circuit breakers combine compact construction, high short-circuit performance and advanced electronic protection, providing dependable solutions for motor control, machinery and industrial low-voltage distribution systems.