1SDA067928R1 ABB XT2L 160 Ekip LSI In=160A 3p F F Moulded Case Circuit Breaker

1SDA067928R1 ABB XT2L 160 Ekip LSI In=160A 3p F F Moulded Case Circuit Breaker

ABB 1SDA067928R1 XT2L 160 is a 160 A three-pole fixed moulded case circuit breaker with an Ekip LSI electronic trip unit, front terminals and 120 kA ultimate breaking capacity at 415 V AC.

SKU: 1SDA067928R1MPN: 1SDA067928R1
Price
List Price £1,696.04 ex VAT
Your Price (ex VAT) Save 25%
£1,272.03 25% OFF
You save £424.01 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,272.03
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,272.03

Why Choose the ABB XT2L 160 Ekip LSI In=160A 3p F F Circuit Breaker?

The ABB XT2L 160 Ekip LSI In=160A 3p F F, order code 1SDA067928R1, is a high-performance three-pole moulded case circuit breaker (MCCB) designed for reliable protection of low-voltage electrical distribution systems. As part of the ABB SACE Tmax XT2 range, it combines compact construction with an advanced electronic trip unit and high short-circuit breaking performance for demanding industrial, commercial and infrastructure applications.

This fixed circuit breaker incorporates an ABB Ekip DIP LSI solid-state electronic trip unit with a rated current of 160 A. The LSI release provides long-time overload, short-time short-circuit and instantaneous short-circuit protection, enabling accurate protection settings and effective coordination within modern electrical distribution systems.

With a rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of 120 kA at 415 V AC, the XT2L 160 is suitable for demanding installations with high prospective fault currents. Its fixed three-pole construction and front bolt terminals enable straightforward integration into switchboards, distribution panels and industrial power distribution assemblies.

Key Advantages

  • High-performance ABB Tmax XT2 moulded case circuit breaker for low-voltage distribution protection.
  • 160 A rated current for industrial and commercial power distribution circuits.
  • Ekip DIP LSI electronic trip unit provides precise solid-state protection.
  • Integrated long-time, short-time and instantaneous protection functions.
  • High 120 kA ultimate breaking capacity at 415 V AC.
  • Fixed three-pole design with front terminals for straightforward switchboard installation.

Key Features

  • ABB SACE Tmax XT2 series.
  • XT2L 160 moulded case circuit breaker.
  • 160 A rated current.
  • Three-pole configuration.
  • Ekip DIP LSI solid-state electronic trip unit.
  • Long-time overload protection.
  • Short-time short-circuit protection.
  • Instantaneous short-circuit protection.
  • Rated operational voltage of 690 V AC.
  • 120 kA Icu at 415 V AC.
  • L short-circuit performance level.
  • Fixed installation with front bolt terminals.

Advanced Electronic Protection for Electrical Distribution

Electronic circuit breakers such as the ABB XT2L with an Ekip LSI release provide precise protection against overload and short-circuit conditions. The LSI protection functions cover long-time overload protection, short-time short-circuit protection and instantaneous short-circuit protection, providing greater flexibility for protection coordination within industrial and commercial distribution networks.

The combination of the 160 A Ekip LSI electronic release and the XT2L circuit breaker's high interruption capability makes the 1SDA067928R1 suitable for demanding distribution systems. Its electronic protection technology supports accurate circuit protection while the compact XT2 frame helps optimise space within modern low-voltage switchboards.

Typical Applications

  • Industrial low-voltage distribution boards.
  • Electrical switchboards and panelboards.
  • Transformer and generator distribution circuits.
  • Cable and feeder protection.
  • Industrial machinery and production systems.
  • Commercial and infrastructure power distribution.
  • Industrial control panels and automation systems.

Technical Specifications

Series SACE Tmax XT2
Product group T-Max XT 250 Range
Order code 1SDA067928R1
Alternate catalogue number XT2LE3160FFF000XXX
Product type Moulded case circuit breaker
Frame size XT2
Short-circuit performance level L
Rated current 160 A
Rated uninterrupted current 160 A
Number of poles 3
Trip unit Ekip DIP LSI
Release technology Electronic / solid-state
Protection functions Long-time, short-time and instantaneous
Rated operational voltage 690 V AC
Rated insulation voltage 1000 V
Rated impulse withstand voltage 8 kV
Rated frequency 50 / 60 Hz
Ultimate breaking capacity Icu at 220–240 V AC 150 kA
Ultimate breaking capacity Icu at 380 V AC 120 kA
Ultimate breaking capacity Icu at 415 V AC 120 kA
Ultimate breaking capacity Icu at 440 V AC 100 kA
Ultimate breaking capacity Icu at 500 V AC 60 kA
Ultimate breaking capacity Icu at 525 V AC 36 kA
Ultimate breaking capacity Icu at 690 V AC 18 kA
Service breaking capacity Ics at 415 V AC 120 kA
Mounting type Fixed
Terminal arrangement Front terminals
Terminal type Bolt
Terminal tightening torque 6 N·m
Standard IEC 60947-2
Weight approx. 1.22 kg
EAN 8015644018245
Country of origin Italy

Frequently Asked Questions

What is the ABB 1SDA067928R1 used for?

The ABB 1SDA067928R1 is a three-pole moulded case circuit breaker designed to protect low-voltage electrical distribution circuits against overload and short-circuit faults using an electronic Ekip LSI trip unit.

What is the rated current of the ABB XT2L 160 Ekip LSI?

The Ekip LSI electronic release fitted to this circuit breaker has a rated current of 160 A.

What protection functions does the Ekip LSI trip unit provide?

The Ekip LSI electronic trip unit provides long-time overload protection, short-time short-circuit protection and instantaneous short-circuit protection.

What is the breaking capacity of the ABB XT2L 160?

The 1SDA067928R1 has an ultimate short-circuit breaking capacity of 120 kA at 415 V AC, providing high fault-current interruption capability for demanding electrical distribution systems.

How is the ABB XT2L 160 Ekip LSI installed?

This model is a fixed three-pole circuit breaker with front bolt terminals, designed for installation within electrical switchboards, distribution panels and industrial power distribution assemblies.

Trusted ABB Electronic Circuit Protection

ABB SACE Tmax XT moulded case circuit breakers combine compact construction, high short-circuit performance and advanced Ekip electronic protection to provide dependable circuit protection for modern industrial and commercial electrical distribution systems.