Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA067918R1 is an XT2L 160 three-pole fixed moulded case circuit breaker with front terminals, a 160 A rated current and an Ekip LS/I electronic trip unit for high-performance low-voltage power distribution protection.
£734.10
The ABB XT2L 160 Ekip LS/I In=160A 3P F F is a high-performance moulded case circuit breaker (MCCB) designed for reliable protection of low-voltage power distribution circuits. As part of the ABB SACE Tmax XT2 series, it combines the compact XT2 frame with an electronic Ekip LS/I trip unit for accurate overload and short-circuit protection in industrial and commercial electrical installations.
This XT2L configuration features a fixed three-pole construction with front terminals, providing a practical arrangement for integration into switchboards, distribution panels and electrical control assemblies. The L short-circuit performance level provides an ultimate breaking capacity of 120 kA at 415 V AC, delivering robust fault-clearing performance for demanding low-voltage networks.
With a rated current of 160 A and an Ekip LS/I electronic trip unit, the breaker provides long-time overload and short-circuit protection. Its electronic protection technology, rated operational voltage of up to 690 V AC and compact fixed-frame construction make it suitable for modern power distribution systems requiring dependable protection and efficient panel integration.
Moulded case circuit breakers such as the ABB Tmax XT2 protect electrical distribution systems by automatically disconnecting circuits when overload or short-circuit conditions occur. The Ekip LS/I electronic trip unit provides accurate long-time overload and short-circuit protection, helping protect cables, distribution equipment and connected electrical systems against damaging overcurrents.
The XT2L combines electronic protection with high short-circuit interruption performance in a compact breaker frame. Its fixed three-pole construction and front terminal arrangement make it well suited to industrial switchboards, commercial distribution panels and OEM electrical assemblies requiring dependable protection and efficient panel integration.
| Series | SACE Tmax XT2 |
|---|---|
| ABB order code | 1SDA067918R1 |
| Product type | Moulded case circuit breaker |
| Frame size | XT2 |
| Rated uninterrupted current (Iu) | 160 A |
| Rated current (In) | 160 A |
| Protection release | Ekip DIP LS/I electronic |
| Protection functions | Long-time and short-circuit protection |
| Number of poles | 3 |
| Mounting | Fixed |
| Terminal arrangement | Front terminals |
| Current type | AC |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Rated frequency | 50 / 60 Hz |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 120 kA |
| Service short-circuit breaking capacity (Ics) at 415 V AC | 120 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 18 kA |
| Short-circuit performance level | L |
| Standard | IEC 60947-2 |
| Electrical durability | 8,000 cycles |
| Mechanical durability | 25,000 cycles |
| Dimensions (W × H × D) | 90 × 130 × 82.5 mm |
| Product net weight | approx. 1.2 kg |
| EAN | 8015644018146 |
The ABB 1SDA067918R1 is an XT2L 160 three-pole fixed moulded case circuit breaker with front terminals, a 160 A rated current and an Ekip LS/I electronic protection release.
This XT2L configuration has a rated current of 160 A, matching the rated uninterrupted current of the XT2 160 frame.
The Ekip LS/I electronic trip unit provides long-time overload and short-circuit protection for the connected low-voltage distribution circuit.
This XT2L configuration provides an ultimate short-circuit breaking capacity of 120 kA at 415 V AC.
The circuit breaker has a rated operational voltage of up to 690 V AC, making it suitable for a broad range of low-voltage distribution systems.
The breaker is supplied in a fixed three-pole configuration with front terminals for integration into suitable switchboards, distribution panels and electrical assemblies.
ABB SACE Tmax XT moulded case circuit breakers are widely used by panel builders, electrical engineers and industrial operators for dependable circuit protection, compact switchboard integration and high-performance low-voltage power distribution.