ABB XT2S 160 3 pole Standard MCCB Adjustable Thermal/Fixed Magnetic Release In=16A Ii=160A

ABB XT2S 160 3 pole Standard MCCB Adjustable Thermal/Fixed Magnetic Release In=16A Ii=160A

ABB XT2S 160 TMG 16-160 three-pole moulded case circuit breaker with thermomagnetic generator protection release, 16 A rated current and 50 kA breaking capacity at 415 V AC.

SKU: 1SDA067738R1Alt SKU: XT2S 160 TMG 16-160 3p F FMPN: 1SDA067738R1
Price
List Price £410.14 ex VAT
Your Price (ex VAT) Save 25%
£307.61 25% OFF
You save £102.54 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £307.61
Trade pricing is personalised to your account

Manufacturer Lead Time

£307.61

Why Choose the ABB 1SDA067738R1 XT2S 160 TMG 16-160 3P MCCB?

The ABB 1SDA067738R1 is a compact and reliable SACE Tmax XT2S moulded case circuit breaker (MCCB) designed for generator protection and low-voltage power distribution applications. Built for industrial, commercial and OEM electrical systems, this three-pole breaker provides dependable overload and short-circuit protection in a robust fixed installation format.

Equipped with a thermomagnetic TMG trip unit, the XT2S 160 is specifically suited to generator protection applications where stable, accurate circuit protection is required. Its front terminal connections support straightforward installation into switchboards, control panels and distribution assemblies.

With a 16 A rated current, 160 A frame size and 50 kA breaking capacity at 415 V AC, the ABB 1SDA067738R1 offers dependable performance for demanding electrical installations requiring compact dimensions, reliable operation and long service life.

Key Advantages

  • Compact ABB SACE Tmax XT2S moulded case circuit breaker.
  • Three-pole fixed MCCB for generator and distribution protection.
  • 16 A rated current within a 160 A frame size.
  • Thermomagnetic TMG release for generator protection applications.
  • 50 kA breaking capacity at 415 V AC.
  • Front terminal design for efficient panel installation.

Key Features

  • ABB SACE Tmax XT series.
  • Product ID: 1SDA067738R1.
  • Model: XT2S 160 TMG 16-160 3P F F.
  • 160 A frame size.
  • 16 A rated current (In).
  • Thermomagnetic TMG release.
  • Instantaneous short-circuit setting 160 A.
  • Three-pole fixed configuration.
  • Front terminal connections.
  • Manufactured in accordance with IEC 60947-2.

Reliable Protection for Generator and Distribution Circuits

The ABB SACE Tmax XT range is engineered to deliver dependable protection for low-voltage installations where operational reliability is essential. The TMG release is designed for generator protection duties, helping safeguard electrical systems against overloads and short-circuit faults.

Its compact construction, high short-circuit performance and robust ABB design make the XT2S 160 suitable for generator panels, industrial switchboards, OEM assemblies and commercial distribution systems requiring safe and reliable circuit protection.

Typical Applications

  • Generator protection panels.
  • Industrial power distribution systems.
  • Commercial switchboards.
  • OEM electrical assemblies.
  • Machine control panels.
  • Infrastructure and building services.

Technical Specifications

Tick the specs you need, then view products that match.

Mounting Type Fixed
Application Generator protection
Current 16 A
Phase Three Phase
Poles 3-pole
Device Type MCCB
Breaking Capacity 50 kA
Trip Unit Thermal-magnetic
Manufacturer ABB
Series SACE Tmax XT
Model XT2S 160 TMG 16-160 3P F F
Product ID 1SDA067738R1
EAN 8015644016340
Product type Moulded Case Circuit Breaker (MCCB)
Application type Generator protection
Frame size XT2 160
Rated current (In) 16 A
Rated uninterrupted current (Iu) 160 A
Trip unit Thermomagnetic TMG
Setting range 11.2 to 16 A
Instantaneous short-circuit setting (Ii) 160 A
Number of poles 3
Rated operational voltage Up to 690 V AC / 500 V DC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 8 kV
Breaking capacity (Icu at 415 V AC) 50 kA
Frequency 50 / 60 Hz
Terminal type Front terminals
Mounting Fixed installation
Standards IEC 60947-2
Dimensions (H × W × D) Approx. 130 × 90 × 82.5 mm
Weight Approx. 1.1 kg
HS Code 85362090
Country of Manufacture Italy

Frequently Asked Questions

What is the ABB 1SDA067738R1 used for?

It is a three-pole moulded case circuit breaker designed for generator protection and low-voltage power distribution applications.

What is the rated current of this MCCB?

The ABB 1SDA067738R1 has a 16 A rated current within the XT2 160 frame size.

What type of trip unit is fitted?

This breaker is fitted with a thermomagnetic TMG trip unit, commonly used for generator protection applications.

How many poles does this breaker have?

The ABB 1SDA067738R1 is a three-pole (3P) moulded case circuit breaker.

Where is this MCCB typically installed?

It is commonly installed in generator panels, industrial switchboards, OEM equipment and low-voltage distribution systems.

Trusted by Electrical Professionals Worldwide

ABB SACE Tmax XT moulded case circuit breakers are trusted by panel builders, OEM manufacturers and electrical engineers worldwide for reliable circuit protection, compact installation and dependable performance in critical power applications.