ABB 1SDA067707R1 XT2V 160 four-pole fixed moulded-case circuit breaker with front terminals, a 40 A TMA thermomagnetic release and adjustable 200–400 A instantaneous magnetic protection.
£965.10
The ABB XT2V 160 TMA 40-400 4p F F, order code 1SDA067707R1, is a high-performance four-pole moulded-case circuit breaker (MCCB) designed for protection and switching in low-voltage power distribution systems. Part of the ABB SACE Tmax XT2 range, it combines the compact XT2 160 frame with a TMA thermomagnetic trip unit rated at 40 A.
The TMA release provides thermal overload protection together with adjustable instantaneous magnetic short-circuit protection. Its instantaneous magnetic setting is adjustable from 200–400 A, allowing the protection characteristics to be coordinated with connected cables, feeders and electrical equipment.
This XT2V configuration features a fixed four-pole construction with front terminals. It is rated for operation up to 690 V AC, while the high-performance V version provides strong short-circuit interruption capability for demanding industrial and commercial distribution applications.
The ABB XT2V 160 TMA uses thermal and magnetic protection technologies to protect electrical circuits against overloads and short circuits. The thermal element responds to sustained overcurrent conditions, while the adjustable magnetic element provides rapid interruption during severe short-circuit faults.
With its compact XT2 construction, four-pole configuration and adjustable 200–400 A magnetic setting, the 1SDA067707R1 provides a practical protection solution for demanding low-voltage distribution systems where dependable fault interruption and installation flexibility are required.
| Series | SACE Tmax XT |
|---|---|
| ABB order code | 1SDA067707R1 |
| Product type | Moulded-case circuit breaker (MCCB) |
| Frame | XT2 |
| Frame rating | 160 A |
| Performance level | V |
| Rated current | 40 A |
| Rated uninterrupted current | 160 A |
| Trip unit | TMA thermomagnetic release |
| Instantaneous magnetic setting I3 | 200–400 A |
| Number of poles | 4 |
| Rated operational voltage | 690 V AC |
| Rated DC voltage | 500 V DC |
| Rated frequency | 50 / 60 Hz |
| Rated impulse withstand voltage | 8 kV |
| Mounting | Fixed |
| Terminal arrangement | Front terminals |
| Tripping mechanism | Thermal magnetic |
| Dimensions (W × H × D) | 120 × 130 × 82.5 mm |
| Net weight | 1.45 kg |
| EAN | 8015644016036 |
The ABB 1SDA067707R1 is a four-pole moulded-case circuit breaker designed to provide overload and short-circuit protection in low-voltage power distribution systems.
The circuit breaker has a rated current of 40 A and uses a TMA thermomagnetic protection release.
The TMA release provides an adjustable instantaneous magnetic setting from 200–400 A.
This model has a four-pole configuration, making it suitable for compatible three-phase four-wire low-voltage distribution systems.
This model is a fixed four-pole circuit breaker with front terminals, designed for permanent installation in compatible low-voltage switchboards and distribution assemblies.
ABB SACE Tmax XT moulded-case circuit breakers are designed for dependable low-voltage power distribution, combining compact construction, thermomagnetic protection and high short-circuit performance for industrial and commercial electrical systems.