1SDA067706R1 ABB XT2V 160 TMD 32-320 4p F F Circuit Breaker

1SDA067706R1 ABB XT2V 160 TMD 32-320 4p F F Circuit Breaker

ABB 1SDA067706R1 XT2V 160 four-pole fixed moulded-case circuit breaker with front terminals, a 32 A TMD thermomagnetic release, 22.4–32 A overload adjustment and 320 A instantaneous short-circuit protection.

SKU: 1SDA067706R1MPN: 1SDA067706R1
Price
List Price £1,286.80 ex VAT
Your Price (ex VAT) Save 25%
£965.10 25% OFF
You save £321.70 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £965.10
Trade pricing is personalised to your account

Manufacturer Lead Time

£965.10

Why Choose the ABB XT2V 160 TMD 32-320 4p F F Circuit Breaker?

The ABB XT2V 160 TMD 32-320 4p F F, order code 1SDA067706R1, is a high-performance four-pole moulded-case circuit breaker (MCCB) designed for protection and switching in low-voltage power distribution systems. Part of the ABB SACE Tmax XT2 range, it combines the compact XT2 160 frame with a TMD thermomagnetic trip unit rated at 32 A.

The TMD thermomagnetic release provides dependable overload and short-circuit protection. Its thermal overload setting is adjustable from 22.4–32 A, while the instantaneous magnetic short-circuit setting is 320 A, enabling effective protection of cables, feeders and connected electrical equipment.

This XT2V configuration features a fixed four-pole construction with front terminals. It has a rated operational voltage of 690 V AC and the V short-circuit performance level provides an ultimate breaking capacity of 150 kA at 415 V AC, making it suitable for demanding industrial and commercial distribution systems with high prospective fault currents.

Key Advantages

  • Compact ABB SACE Tmax XT2V 160 moulded-case circuit breaker.
  • 32 A TMD thermomagnetic release for overload and short-circuit protection.
  • Adjustable 22.4–32 A thermal overload setting.
  • 320 A instantaneous magnetic short-circuit protection.
  • 150 kA Icu at 415 V AC for demanding electrical distribution systems.
  • Fixed four-pole design with front terminals for straightforward switchboard integration.

Key Features

  • ABB SACE Tmax XT2V 160 circuit breaker.
  • 32 A rated current.
  • 160 A rated uninterrupted frame current.
  • TMD thermomagnetic trip unit.
  • Thermal setting range: 22.4–32 A.
  • Instantaneous magnetic trip: 320 A.
  • Four-pole construction.
  • Fixed mounting with front terminals.
  • 690 V AC rated operational voltage.
  • Designed in accordance with IEC 60947-2.

High-Performance Thermomagnetic Circuit Protection

Thermomagnetic moulded-case circuit breakers such as the ABB XT2V combine thermal overload protection with rapid magnetic short-circuit protection. The thermal element responds to sustained overcurrent conditions, while the magnetic element provides fast interruption when a significant short-circuit fault occurs.

The SACE Tmax XT2 platform combines compact construction with flexible installation and high short-circuit performance. The four-pole XT2V configuration is particularly suitable for demanding three-phase distribution systems requiring dependable switching and protection within a compact switchboard footprint.

Typical Applications

  • Industrial low-voltage distribution boards.
  • Commercial building electrical distribution.
  • Three-phase four-wire distribution systems.
  • Feeder and branch-circuit protection.
  • Electrical switchboards and switchgear assemblies.
  • Installations with high prospective short-circuit currents.

Technical Specifications

Series SACE Tmax XT
ABB order code 1SDA067706R1
Product type Moulded-case circuit breaker (MCCB)
Frame XT2
Frame rating 160 A
Short-circuit performance level V
Rated current 32 A
Rated uninterrupted current 160 A
Trip unit TMD thermomagnetic release
Thermal setting range 22.4–32 A
Instantaneous short-circuit setting 320 A
Number of poles 4
Rated operational voltage 690 V AC / 500 V DC
Rated insulation voltage 1000 V
Rated impulse withstand voltage 8 kV
Rated frequency 50 / 60 Hz
Ultimate breaking capacity Icu at 415 V AC 150 kA
Service breaking capacity Ics at 415 V AC 150 kA
Mounting Fixed
Terminal arrangement Front terminals
Standard IEC 60947-2
Dimensions (W × H × D) 120 × 130 × 82.5 mm
Weight 1.45 kg
EAN 8015644016029

Frequently Asked Questions

What is the ABB 1SDA067706R1 used for?

The ABB 1SDA067706R1 is a four-pole moulded-case circuit breaker designed to provide overload and short-circuit protection in low-voltage power distribution systems.

What is the rated current of the XT2V 160 TMD 32-320?

The circuit breaker has a rated current of 32 A, with its thermal overload protection adjustable from 22.4–32 A.

What is the instantaneous short-circuit setting?

The TMD thermomagnetic release provides an instantaneous magnetic short-circuit setting of 320 A.

What is the breaking capacity of the ABB XT2V 160?

This XT2V configuration provides an ultimate short-circuit breaking capacity of 150 kA at 415 V AC.

How is the ABB XT2V 160 TMD 32-320 installed?

This model is a fixed four-pole circuit breaker with front terminals, designed for permanent installation in compatible low-voltage switchboards and distribution assemblies.

Trusted ABB Circuit Protection

ABB SACE Tmax XT moulded-case circuit breakers are designed for dependable low-voltage power distribution, combining compact construction, reliable thermomagnetic protection and high short-circuit performance for demanding industrial and commercial electrical systems.