1SDA067704R1 ABB XT2V 160 TMD 20-300 4P F F Moulded-Case Circuit Breaker

1SDA067704R1 ABB XT2V 160 TMD 20-300 4P F F Moulded-Case Circuit Breaker

ABB 1SDA067704R1 is a 20 A four-pole XT2V 160 moulded-case circuit breaker with a TMD thermomagnetic release, 14–20 A adjustable thermal overload protection, a 300 A magnetic short-circuit threshold, fixed mounting and front terminals.

SKU: 1SDA067704R1MPN: 1SDA067704R1
Price
List Price £1,286.80 ex VAT
Your Price (ex VAT) Save 25%
£965.10 25% OFF
You save £321.70 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £965.10
Trade pricing is personalised to your account

Manufacturer Lead Time

£965.10

Why Choose the ABB XT2V 160 TMD 20-300 4P F F Circuit Breaker?

The ABB 1SDA067704R1 is a high-performance moulded-case circuit breaker (MCCB) designed for dependable protection of low-voltage power distribution systems. Part of the ABB SACE Tmax XT series, the XT2V 160 combines a compact frame with a TMD thermomagnetic release and high short-circuit breaking performance for demanding industrial and commercial installations.

This circuit breaker features a fixed four-pole configuration with front terminals and a TMD thermomagnetic release. Its thermal element provides adjustable overload protection, while the magnetic element provides rapid short-circuit protection, helping safeguard cables, distribution circuits and connected equipment against damaging overcurrent conditions.

With a rated current of 20 A, an adjustable thermal overload setting of 14–20 A and a magnetic short-circuit threshold of 300 A, the XT2V 160 TMD 20-300 provides coordinated circuit protection. The XT2V platform offers high fault-interruption capability, while its fixed mounting and front-terminal arrangement simplify integration into low-voltage switchboards and distribution panels.

Key Advantages

  • High-performance ABB Tmax XT2V moulded-case circuit breaker for low-voltage power distribution.
  • 20 A rated current with adjustable thermal overload protection.
  • 300 A magnetic short-circuit threshold for rapid fault protection.
  • High-performance XT2V breaking-capacity class for installations with demanding prospective fault levels.
  • Four-pole fixed configuration for multipole power distribution systems.
  • Front terminals support straightforward integration into switchboards and electrical panels.

Key Features

  • ABB SACE Tmax XT2V 160 circuit breaker.
  • 20 A rated current.
  • 14–20 A adjustable thermal overload setting.
  • 300 A magnetic short-circuit threshold.
  • TMD thermomagnetic trip unit.
  • Four-pole configuration.
  • V short-circuit performance level.
  • Fixed mounting with front terminal connections.

High-Performance Thermomagnetic Circuit Protection

Thermomagnetic circuit breakers combine thermal and magnetic protection mechanisms to protect electrical installations against damaging overcurrent conditions. The adjustable thermal element responds to sustained overloads, while the magnetic element operates rapidly when short-circuit current reaches the specified protection threshold.

The ABB Tmax XT2V platform is engineered for applications requiring compact construction and high short-circuit interruption performance. The 1SDA067704R1 combines a 20 A TMD release with four-pole switching, fixed installation and front connections, making it a versatile protection solution for demanding low-voltage distribution systems.

Typical Applications

  • Industrial low-voltage distribution boards.
  • Commercial electrical distribution systems.
  • Electrical switchboards and control panels.
  • Four-pole power distribution circuits.
  • Cable, feeder and installation protection.
  • OEM electrical equipment and panel building.

Technical Specifications

Series SACE Tmax XT
Product group T-Max XT 250 Range
Order code 1SDA067704R1
Product type Moulded-case circuit breaker (MCCB)
Frame size XT2
Rated uninterrupted current (Iu) 160 A
Rated current (In) 20 A
Trip unit TMD thermomagnetic release
Thermal overload setting 14–20 A
Magnetic short-circuit threshold 300 A
Number of poles 4
Rated operational voltage up to 690 V AC
Rated DC voltage up to 500 V DC
Rated impulse withstand voltage (Uimp) 8 kV
Rated frequency 50 / 60 Hz
Short-circuit performance level V
Mounting type Fixed
Terminal connection Front
Terminal type Bolt
Tripping mechanism Thermal-magnetic
Dimensions (W × H × D) 120 × 130 × 82.5 mm
Net weight 1.55 kg
EAN 8015644016005
Country of origin Italy
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA067704R1 used for?

The ABB 1SDA067704R1 is a moulded-case circuit breaker designed to provide thermal overload and magnetic short-circuit protection for low-voltage power distribution circuits.

What is the rated current of the ABB XT2V 160 TMD 20-300?

The circuit breaker has a rated current of 20 A, with an adjustable thermal overload setting range of 14–20 A.

What does TMD mean on the ABB 1SDA067704R1?

TMD identifies the thermomagnetic trip unit, which combines adjustable thermal overload protection with magnetic short-circuit protection.

What is the magnetic short-circuit threshold of the ABB 1SDA067704R1?

The magnetic short-circuit threshold is 300 A, providing rapid operation when a high short-circuit current occurs.

How is the ABB 1SDA067704R1 installed?

The XT2V 160 is a fixed four-pole circuit breaker with front terminals, designed for integration into compatible low-voltage switchboards, distribution panels and electrical equipment.

Trusted ABB Circuit Protection

ABB SACE Tmax XT moulded-case circuit breakers provide compact and dependable protection for industrial and commercial power distribution systems, combining proven thermomagnetic protection with high short-circuit performance and flexible installation options.