Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA067703R1 XT2V 160 TMD 16-300 4p F F is a 16 A four-pole fixed moulded case circuit breaker with TMD thermomagnetic protection, an 11.2–16 A thermal setting range and 300 A instantaneous short-circuit protection.
£965.10
The ABB XT2V 160 TMD 16-300 4p F F, order code 1SDA067703R1, is a high-performance four-pole moulded case circuit breaker (MCCB) designed for dependable overload and short-circuit protection in low-voltage power distribution systems. As part of the ABB SACE Tmax XT series, it combines the compact XT2 frame with thermomagnetic protection and the high short-circuit performance of the XT2V configuration.
This circuit breaker incorporates an ABB TMD thermomagnetic release with a rated current of 16 A. Its thermal overload setting is adjustable from 11.2–16 A, while the instantaneous magnetic short-circuit setting is 300 A, providing coordinated protection against sustained overloads and high-current faults.
The XT2V 160 TMD 16-300 is a fixed four-pole circuit breaker with front terminals for straightforward integration into switchboards and distribution panels. It supports rated operational voltages up to 690 V AC / 500 V DC and provides an ultimate short-circuit breaking capacity of 150 kA at 415 V AC, making it suitable for demanding installations with high prospective fault currents.
Moulded case circuit breakers such as the ABB Tmax XT2 protect electrical distribution circuits against overload and short-circuit conditions. The TMD thermomagnetic release combines adjustable thermal overload protection with instantaneous magnetic operation, providing dependable protection without requiring an external power supply for the trip unit.
The Tmax XT platform is designed for compact industrial switchboards and power distribution systems where reliable interruption of high prospective fault currents is essential. The XT2V configuration offers high short-circuit performance, while its fixed front-connected construction supports efficient integration into switchboards, control panels and OEM electrical assemblies.
| Series | SACE Tmax XT |
|---|---|
| ABB order code | 1SDA067703R1 |
| Product type | Moulded case circuit breaker |
| Frame size | XT2 |
| Short-circuit performance level | V |
| Number of poles | 4 |
| Rated current (In) | 16 A |
| Rated uninterrupted current (Iu) | 160 A |
| Release type | TMD thermomagnetic |
| Thermal setting range | 11.2–16 A |
| Instantaneous short-circuit setting | 300 A |
| Rated operational voltage | up to 690 V AC / 500 V DC |
| Rated voltage (Ur) | 690 V |
| Rated insulation voltage (Ui) | 1,000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Rated frequency | 50 / 60 Hz |
| Ultimate breaking capacity (Icu) at 415 V AC | 150 kA |
| Service breaking capacity (Ics) at 415 V AC | 150 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 20 kA |
| Service breaking capacity (Ics) at 690 V AC | 15 kA |
| Power loss | 1.33 W per pole at rated operating conditions |
| Mechanical durability | 25,000 operations |
| Electrical durability | 8,000 operations |
| Mounting | Fixed |
| Terminal connection | Front |
| Terminal type | Bolt |
| Dimensions (W × H × D) | 120 × 130 × 82.5 mm |
| Net weight | approx. 1.6 kg |
| EAN | 8015644015992 |
| Standard | IEC 60947-2 |
The ABB 1SDA067703R1 is a four-pole moulded case circuit breaker designed to provide overload and short-circuit protection in low-voltage power distribution systems.
The circuit breaker has a rated current of 16 A, with an adjustable thermal protection setting range of 11.2–16 A.
The TMD thermomagnetic release has an instantaneous magnetic short-circuit setting of 300 A for rapid interruption of high-current faults.
The XT2V performance level provides an ultimate short-circuit breaking capacity of 150 kA at 415 V AC, making it suitable for installations with high prospective fault currents.
The XT2V 160 TMD 16-300 4p F F is a fixed four-pole circuit breaker with front terminals, designed for installation in electrical switchboards and distribution panels.
ABB SACE Tmax XT moulded case circuit breakers are widely used by panel builders, electrical engineers and industrial operators for compact, dependable protection of low-voltage power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.