1SDA067702R1 ABB XT2V 160 TMD 12,5-125 4p F F Moulded Case Circuit Breaker

1SDA067702R1 ABB XT2V 160 TMD 12,5-125 4p F F Moulded Case Circuit Breaker

ABB 1SDA067702R1 XT2V 160 TMD 12,5-125 4p F F is a 12.5 A four-pole fixed moulded case circuit breaker with TMD thermomagnetic protection, an 8.75–12.5 A thermal setting range and 125 A instantaneous short-circuit protection.

SKU: 1SDA067702R1MPN: 1SDA067702R1
Price
List Price £1,115.22 ex VAT
Your Price (ex VAT) Save 25%
£836.42 25% OFF
You save £278.81 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £836.42
Trade pricing is personalised to your account

Manufacturer Lead Time

£836.42

Why Choose the ABB XT2V 160 TMD 12,5-125 4p F F Circuit Breaker?

The ABB XT2V 160 TMD 12,5-125 4p F F, order code 1SDA067702R1, is a high-performance four-pole moulded case circuit breaker (MCCB) designed for reliable overload and short-circuit protection in low-voltage power distribution systems. As part of the proven ABB SACE Tmax XT series, it combines the compact XT2 frame with thermomagnetic protection and the high short-circuit performance of the XT2V configuration.

This circuit breaker incorporates an ABB TMD thermomagnetic release with a rated current of 12.5 A. Its thermal overload setting is adjustable from 8.75–12.5 A, while the instantaneous magnetic short-circuit setting is 125 A, providing dependable protection against both sustained overloads and high-current faults.

The XT2V 160 TMD 12,5-125 is a fixed four-pole circuit breaker with front terminals for straightforward integration into switchboards and distribution panels. It supports operational voltages up to 690 V AC / 500 V DC and provides an ultimate short-circuit breaking capacity of 150 kA at 415 V AC, making it suitable for demanding installations with high prospective fault currents.

Key Advantages

  • Compact four-pole moulded case circuit breaker for power distribution.
  • 12.5 A rated current with adjustable thermal overload protection.
  • TMD thermomagnetic release provides overload and short-circuit protection.
  • 8.75–12.5 A thermal setting range for circuit protection coordination.
  • 125 A instantaneous short-circuit setting for rapid fault interruption.
  • High 150 kA ultimate breaking capacity at 415 V AC.
  • Fixed mounting with front terminals simplifies switchboard integration.

Key Features

  • ABB SACE Tmax XT2 series.
  • XT2V 160 frame with V-level short-circuit performance.
  • Four-pole configuration.
  • 12.5 A rated current.
  • TMD thermomagnetic trip unit.
  • 8.75–12.5 A adjustable thermal setting range.
  • 125 A instantaneous magnetic setting.
  • Operational voltage up to 690 V AC / 500 V DC.
  • 1,000 V rated insulation voltage and 8 kV impulse withstand voltage.
  • Fixed circuit-breaker construction with front terminal connections.

Reliable Circuit Protection for Power Distribution

Moulded case circuit breakers such as the ABB Tmax XT2 protect electrical distribution circuits against overload and short-circuit conditions. The TMD thermomagnetic release combines adjustable thermal overload protection with instantaneous magnetic operation, providing dependable protection without requiring an external power supply for the trip unit.

The Tmax XT platform is designed for compact industrial switchboards and power distribution systems where reliable interruption of high prospective fault currents is essential. The XT2V configuration offers high short-circuit performance, while its fixed front-connected construction supports efficient integration into switchboards, control panels and OEM electrical assemblies.

Typical Applications

  • Industrial low-voltage power distribution systems.
  • Electrical switchboards and distribution panels.
  • Feeder and branch-circuit protection.
  • Machinery and automation control cabinets.
  • Commercial and industrial building services.
  • OEM electrical equipment and panel building.

Technical Specifications

Series SACE Tmax XT
ABB order code 1SDA067702R1
Product type Moulded case circuit breaker
Frame size XT2
Short-circuit performance level V
Number of poles 4
Rated current (In) 12.5 A
Rated uninterrupted current (Iu) 160 A
Release type TMD thermomagnetic
Thermal setting range 8.75–12.5 A
Instantaneous short-circuit setting 125 A
Rated operational voltage up to 690 V AC / 500 V DC
Rated voltage (Ur) 690 V
Rated insulation voltage (Ui) 1,000 V
Rated impulse withstand voltage (Uimp) 8 kV
Rated frequency 50 / 60 Hz
Ultimate breaking capacity (Icu) at 415 V AC 150 kA
Service breaking capacity (Ics) at 415 V AC 150 kA
Ultimate breaking capacity (Icu) at 690 V AC 20 kA
Power loss 1.05 W per pole at rated operating conditions
Mechanical durability 25,000 operations
Electrical durability 8,000 operations
Mounting Fixed
Terminal connection Front
Terminal type Bolt
Dimensions (W × H × D) 120 × 130 × 82.5 mm
Net weight approx. 1.45 kg
EAN 8015644015985
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA067702R1 used for?

The ABB 1SDA067702R1 is a four-pole moulded case circuit breaker designed to provide overload and short-circuit protection in low-voltage power distribution systems.

What current rating does the XT2V 160 TMD 12,5-125 have?

The circuit breaker has a rated current of 12.5 A, with an adjustable thermal protection setting range of 8.75–12.5 A.

What is the instantaneous short-circuit setting?

The TMD thermomagnetic release has an instantaneous magnetic short-circuit setting of 125 A for rapid interruption of high-current faults.

What is the breaking capacity of the ABB XT2V 160?

The XT2V performance level provides an ultimate short-circuit breaking capacity of 150 kA at 415 V AC, making it suitable for installations with high prospective fault currents.

How is the ABB 1SDA067702R1 installed?

The XT2V 160 TMD 12,5-125 4p F F is a fixed four-pole circuit breaker with front terminals, designed for installation in electrical switchboards and distribution panels.

Trusted by Electrical Professionals Worldwide

ABB SACE Tmax XT moulded case circuit breakers are widely used by panel builders, electrical engineers and industrial operators for compact, dependable protection of low-voltage power distribution systems.