Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA067690R1 XT2V 160 TMA 100-1000 3p F F is a fixed three-pole moulded-case circuit breaker with front terminals, a 100 A TMA thermomagnetic trip unit, adjustable 70–100 A thermal overload protection and adjustable 500–1000 A instantaneous magnetic short-circuit protection.
£809.66
The ABB 1SDA067690R1 is an ABB SACE Tmax XT2V 160 three-pole moulded-case circuit breaker equipped with a TMA thermomagnetic trip unit. Rated at 100 A, it provides adjustable thermal overload protection together with adjustable instantaneous magnetic short-circuit protection for dependable low-voltage power distribution.
The XT2V is a very-high-breaking-capacity version of the XT2 frame, providing an ultimate short-circuit breaking capacity (Icu) of 150 kA at 415 V AC. This makes the breaker particularly suitable for industrial and commercial installations where substantial prospective fault currents require robust interruption capability.
Configured as a fixed three-pole circuit breaker with front terminals, the 1SDA067690R1 uses a TMA release with a 100 A rated current. Its thermal overload setting is adjustable from 70–100 A, while the instantaneous magnetic short-circuit release is adjustable from 500–1000 A, allowing protection to be coordinated with the characteristics of the protected circuit.
The ABB TMA trip unit combines adjustable thermal and magnetic protection within the circuit breaker. Its thermal element can be set from 70–100 A, allowing the overload threshold to be coordinated with the protected cables and equipment while helping prevent damage caused by sustained overcurrent conditions.
For short-circuit protection, the instantaneous magnetic release is adjustable from 500–1000 A. This flexibility allows the magnetic trip threshold to be matched more closely to the electrical installation, while the XT2V breaking part provides the very high interruption capability required to safely disconnect severe fault currents.
| Series | SACE Tmax XT |
|---|---|
| Product group | T-Max XT 250 Range |
| Order code | 1SDA067690R1 |
| Product type | Moulded-case circuit breaker (MCCB) |
| Frame | XT2 |
| Breaking-capacity version | V |
| Frame rated current (Iu) | 160 A |
| Trip unit | TMA thermomagnetic |
| Rated current (In) | 100 A |
| Thermal overload setting range | 70–100 A |
| Instantaneous magnetic trip setting (I3) | 500–1000 A |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 150 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 150 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 70 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 20 kA |
| Number of poles | 3 |
| Installation | Fixed (F) |
| Terminal arrangement | Front terminals (F) |
| Protection | Adjustable thermal overload and magnetic short-circuit protection |
| Reference standard | IEC/EN 60947-2 |
| Product net dimensions (W × H × D) | 90 × 130 × 82.5 mm |
| Product net weight | 1.2 kg |
| GTIN / EAN | 8015644015862 |
| Customs tariff number | 85362000 |
| Country of origin | Italy |
The ABB 1SDA067690R1 is an XT2V 160 three-pole moulded-case circuit breaker with a TMA thermomagnetic trip unit rated at 100 A, adjustable thermal overload protection and adjustable magnetic short-circuit protection.
TMA identifies the adjustable thermomagnetic trip unit. The breaker has a rated current of 100 A, a thermal overload adjustment range of 70–100 A and an instantaneous magnetic short-circuit adjustment range of 500–1000 A.
The XT2V version has an ultimate short-circuit breaking capacity (Icu) of 150 kA at 415 V AC. Its breaking capacity varies with operating voltage, including 70 kA at 500 V AC and 20 kA at 690 V AC.
3p means the circuit breaker has three poles. The first F identifies a fixed installation and the second F identifies front terminals.
The TMA trip unit provides adjustable thermal overload protection and adjustable magnetic short-circuit protection, while the XT2V breaking part provides the high interruption capability required to safely disconnect severe fault currents.
ABB SACE Tmax XT moulded-case circuit breakers combine compact construction, adjustable thermomagnetic protection and high short-circuit interruption performance for demanding industrial and commercial low-voltage electrical installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.