ABB 1SDA067663R1 XT2L 160 TMA 40-400 4p F F is a fixed four-pole moulded-case circuit breaker with front terminals, a 40 A TMA thermomagnetic trip unit, adjustable 28–40 A thermal overload protection and adjustable 200–400 A instantaneous magnetic short-circuit protection.
£524.16
The ABB 1SDA067663R1 is an ABB SACE Tmax XT2L 160 four-pole moulded-case circuit breaker equipped with a TMA thermomagnetic trip unit. Rated at 40 A, it combines adjustable thermal overload protection with adjustable instantaneous magnetic short-circuit protection for dependable low-voltage power distribution.
The XT2L version offers high short-circuit interruption performance, with an ultimate short-circuit breaking capacity (Icu) of 120 kA at 400/415 V AC. This makes the breaker well suited to industrial and commercial installations where substantial prospective fault currents may be present.
Configured as a fixed four-pole circuit breaker with front terminals, the 1SDA067663R1 has a 40 A TMA release. Its thermal overload setting is adjustable from 28–40 A, while the instantaneous magnetic short-circuit release is adjustable from 200–400 A, allowing protection to be coordinated with the characteristics of the protected circuit.
The ABB TMA trip unit combines adjustable thermal and magnetic protection within the circuit breaker. Its thermal element can be set from 28–40 A, allowing the overload threshold to be coordinated with the protected cables and equipment while helping prevent damage caused by sustained overcurrent conditions.
For short-circuit protection, the magnetic release can be adjusted from 200–400 A. This flexibility allows the instantaneous trip threshold to be matched more closely to the installation, while the high-breaking-capacity XT2L platform provides the interruption performance required to safely disconnect severe fault currents.
| Series | SACE Tmax XT |
|---|---|
| Product group | T-Max XT 250 Range |
| Order code | 1SDA067663R1 |
| Product type | Moulded-case circuit breaker (MCCB) |
| Frame | XT2 |
| Breaking-capacity version | L |
| Frame rated current (Iu) | 160 A |
| Trip unit | TMA thermomagnetic |
| Rated current | 40 A |
| Thermal overload setting range | 28–40 A |
| Instantaneous magnetic trip setting | 200–400 A |
| Ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 120 kA |
| Rated voltage | up to 690 V AC |
| Number of poles | 4 |
| Installation | Fixed |
| Terminal arrangement | Front terminals |
| Protection | Adjustable thermal overload and magnetic short-circuit protection |
| Integrated earth-fault protection | No |
| Optional motor operator | Yes |
| Product net weight | 1.55 kg |
| GTIN / EAN | 8015644015596 |
| Customs tariff number | 85362000 |
| Country of origin | Italy |
The ABB 1SDA067663R1 is an XT2L 160 four-pole moulded-case circuit breaker with a TMA thermomagnetic trip unit rated at 40 A, adjustable thermal overload protection and adjustable magnetic short-circuit protection.
TMA identifies the adjustable thermomagnetic trip unit. The breaker has a rated current of 40 A, a thermal overload adjustment range of 28–40 A and an instantaneous magnetic short-circuit adjustment range of 200–400 A.
The XT2L version has an ultimate short-circuit breaking capacity (Icu) of 120 kA at 400/415 V AC, providing high fault interruption capability for demanding installations.
4p means the circuit breaker has four poles. The first F identifies a fixed installation and the second F identifies front terminals.
The TMA trip unit provides adjustable thermal overload protection and adjustable magnetic short-circuit protection, while the XT2L breaking part provides the interruption capability required to safely disconnect high fault currents.
ABB SACE Tmax XT moulded-case circuit breakers combine compact construction, adjustable thermomagnetic protection and high short-circuit interruption performance for demanding industrial and commercial low-voltage electrical installations.