1SDA067660R1 ABB XT2L 160 TMD 20-300 4p F F Circuit Breaker

1SDA067660R1 ABB XT2L 160 TMD 20-300 4p F F Circuit Breaker

ABB 1SDA067660R1 XT2L 160 four-pole fixed moulded-case circuit breaker with front terminals, a 20 A TMD thermomagnetic release and 300 A instantaneous magnetic protection.

SKU: 1SDA067660R1MPN: 1SDA067660R1
Price
List Price £698.88 ex VAT
Your Price (ex VAT) Save 25%
£524.16 25% OFF
You save £174.72 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £524.16
Trade pricing is personalised to your account

Manufacturer Lead Time

£524.16

Why Choose the ABB XT2L 160 TMD 20-300 4p F F Circuit Breaker?

The ABB XT2L 160 TMD 20-300 4p F F, order code 1SDA067660R1, is a compact four-pole moulded-case circuit breaker (MCCB) designed for reliable protection and switching in low-voltage electrical distribution systems. Part of the ABB SACE Tmax XT2 range, it combines the XT2 160 frame with a TMD thermomagnetic trip unit rated at 20 A.

The TMD release provides thermal overload protection together with instantaneous magnetic short-circuit protection. The thermal overload setting is adjustable from 14–20 A, while the magnetic protection is specified at 300 A, providing dependable protection against both sustained overload conditions and high fault currents.

This XT2L configuration uses a fixed mounting arrangement with front terminals and a four-pole construction. With a rated operational voltage of 690 V AC, it is designed for industrial and commercial power distribution installations requiring compact four-pole circuit protection.

Key Advantages

  • Compact ABB SACE Tmax XT2 moulded-case circuit breaker.
  • 20 A TMD thermomagnetic release for overload and short-circuit protection.
  • Adjustable 14–20 A thermal overload setting.
  • 300 A instantaneous magnetic protection for short-circuit faults.
  • Four-pole configuration for low-voltage distribution systems requiring neutral switching.
  • Fixed mounting with front terminals for straightforward switchboard installation.

Key Features

  • ABB SACE Tmax XT2L 160 circuit breaker.
  • 20 A rated current.
  • TMD thermomagnetic trip unit.
  • Thermal overload adjustment: 14–20 A.
  • Instantaneous magnetic trip: 300 A.
  • Four-pole construction.
  • Fixed mounting.
  • Front terminals.
  • 690 V AC rated operational voltage.
  • Complete circuit breaker with integrated protection unit.

Reliable Thermomagnetic Circuit Protection

Thermomagnetic moulded-case circuit breakers such as the ABB XT2L use a thermal element to respond to sustained overload conditions and a magnetic element to provide rapid protection against short-circuit currents. This combination delivers dependable circuit protection without requiring a separate electronic trip unit.

The SACE Tmax XT2 platform is designed for compact low-voltage switchboards and distribution assemblies where reliable switching, flexible protection and efficient use of installation space are important. The fixed front-terminal arrangement of this model supports straightforward integration into industrial and commercial electrical systems.

Typical Applications

  • Industrial low-voltage distribution boards.
  • Commercial building electrical distribution.
  • Four-pole feeder and branch-circuit protection.
  • Electrical switchboards and switchgear assemblies.
  • Machine and production-line power distribution.
  • Industrial control panels and OEM electrical equipment.

Technical Specifications

Series SACE Tmax XT
ABB order code 1SDA067660R1
Product type Moulded-case circuit breaker (MCCB)
Frame size XT2 160
Performance level L
Rated current 20 A
Trip unit TMD thermomagnetic release
Thermal overload setting 14–20 A
Instantaneous magnetic trip 300 A
Number of poles 4
Rated operational voltage 690 V AC
Mounting Fixed
Terminal arrangement Front terminals
Standard IEC
GTIN / EAN 8015644015565

Frequently Asked Questions

What is the ABB 1SDA067660R1 used for?

The ABB 1SDA067660R1 is a four-pole moulded-case circuit breaker designed to provide overload and short-circuit protection in low-voltage electrical distribution systems.

What is the rated current of the XT2L 160 TMD 20-300?

The circuit breaker has a rated current of 20 A, with its thermal overload protection adjustable from 14–20 A.

What protection unit does this circuit breaker use?

It uses a TMD thermomagnetic trip unit, combining thermal overload protection with instantaneous magnetic short-circuit protection.

What is the magnetic trip setting of the ABB 1SDA067660R1?

The instantaneous magnetic short-circuit protection is specified at 300 A.

How is the ABB XT2L 160 TMD 20-300 installed?

This model is a fixed four-pole circuit breaker with front terminals, designed for permanent installation in compatible low-voltage switchboards and distribution assemblies.

Trusted ABB Circuit Protection