ABB XT2S 160 TMD 5-50 3P F F moulded case circuit breaker with thermomagnetic TMD trip unit, fixed three-pole configuration and front terminals for industrial power distribution.
£325.03
The ABB 1SDA067545R1 is a high performance ABB SACE Tmax XT2S moulded case circuit breaker (MCCB) engineered to provide dependable protection for low voltage electrical distribution systems. Designed for industrial installations, commercial buildings and OEM machinery, this three-pole circuit breaker combines robust short circuit protection with reliable overload protection in a compact, space-saving design.
Part of the trusted ABB SACE Tmax XT series, this breaker features a thermomagnetic TMD trip unit with an adjustable thermal setting from 3.5 to 5 A and a magnetic trip at 50 A. The XT2S frame delivers high breaking capacity and excellent operational reliability, helping protect cables, switchboards and connected equipment from electrical faults.
With a 160 A frame size, three-pole configuration, front terminals and support for systems up to 690 V AC, the ABB 1SDA067545R1 is ideal for power distribution applications where dependable protection, long service life and straightforward installation are essential.
The ABB XT2S series is designed to safeguard electrical distribution systems against overloads and short circuits while maintaining high operational continuity. Its thermomagnetic protection provides dependable fault detection and fast disconnection, helping minimise equipment damage and downtime.
Suitable for industrial control panels, switchboards and OEM equipment, the XT2S range offers excellent electrical performance together with ABB's renowned engineering quality, making it a trusted choice for demanding low voltage installations.
Tick the specs you need, then view products that match.
| Mounting Type | Fixed | |
|---|---|---|
| Application | Power distribution | |
| Trip Unit | Thermal-magnetic | |
| Current | 5 A | |
| Phase | Three Phase | |
| Poles | 3-pole | |
| Device Type | MCCB | |
| Manufacturer | ABB | |
| Series | SACE Tmax XT | |
| Model | XT2S 160 TMD 5-50 3P F F | |
| Product code | 1SDA067545R1 | |
| Product type | Moulded Case Circuit Breaker (MCCB) | |
| Frame size | XT2 | |
| Number of poles | 3 | |
| Rated uninterrupted current (Iu) | 160 A | |
| Rated current (In) | 5 A | |
| Thermal setting range | 3.5 to 5 A | |
| Magnetic trip setting | 50 A | |
| Rated operational voltage | Up to 690 V AC | |
| Rated insulation voltage (Ui) | 1000 V | |
| Rated impulse withstand voltage (Uimp) | 8 kV | |
| Frequency | 50 / 60 Hz | |
| Terminal type | Front terminals | |
| Mounting | Fixed | |
| Standards | IEC 60947-2 | |
| Dimensions (H × W × D) | 130 × 90 × 82.5 mm | |
| Weight | Approx. 1.1 kg | |
| HS Code | 85362090 | |
| Country of Manufacture | Italy |
It is a moulded case circuit breaker designed to protect low voltage electrical systems against overloads and short circuits.
This model is supplied as a three-pole (3P) fixed circuit breaker.
The breaker incorporates an adjustable thermomagnetic TMD trip unit providing both overload and magnetic short circuit protection.
The ABB XT2S 160 is suitable for electrical systems operating at up to 690 V AC.
It is commonly installed in industrial control panels, switchboards, distribution boards and OEM electrical equipment.
ABB SACE Tmax XT moulded case circuit breakers are trusted by panel builders, electrical contractors and industrial engineers for delivering dependable protection, high performance and long-term reliability across demanding power distribution applications.