ABB 1SDA066819R1 XT1B 160 TMD 125-1250 4P F F InN=50% moulded case circuit breaker with 125 A rated current, four poles, 50% neutral rating, thermomagnetic TMD release and fixed front terminals for low voltage power distribution.
£409.67
The ABB 1SDA066819R1 XT1B 160 TMD 125-1250 4P F F InN=50% is a compact and reliable moulded case circuit breaker (MCCB) from the ABB SACE Tmax XT series. Designed for dependable low voltage power distribution, it protects electrical circuits against overloads and short circuits in industrial, commercial and OEM applications.
This four-pole MCCB is equipped with an adjustable thermomagnetic TMD trip unit, providing thermal overload protection and magnetic short circuit protection. The neutral pole is rated at 50% of the phase current, making it suitable for applications where a reduced neutral rating is required. Its fixed construction with front terminals supports straightforward installation in switchboards, distribution panels and control cabinet assemblies.
With a 125 A rated current, XT1 160 A frame size and 18 kA breaking capacity at 415 V AC, the ABB XT1B 160 TMD 125-1250 4P F F InN=50% is well suited to feeder protection, machinery supplies and general low voltage distribution systems requiring reliable ABB circuit protection.
The ABB XT1B range is engineered to protect electrical circuits by disconnecting power during overload or short circuit conditions. The thermomagnetic release provides a dependable combination of time-delayed overload protection and rapid magnetic fault interruption, helping protect cables, equipment and downstream devices.
Its compact fixed design, four-pole layout and front terminal arrangement make this MCCB suitable for panel builders, electrical contractors and machine manufacturers requiring reliable protection in demanding low voltage installations.
Tick the specs you need, then view products that match.
| Mounting Type | Fixed | |
|---|---|---|
| Application | Power distribution | |
| Current | 125 A | |
| Phase | Three Phase | |
| Poles | 4-pole | |
| Device Type | MCCB | |
| Breaking Capacity | 18 kA | |
| Trip Unit | Thermal-magnetic | |
| Manufacturer | ABB | |
| Series | SACE Tmax XT | |
| Model | XT1B 160 TMD 125-1250 4P F F InN=50% | |
| Product code | 1SDA066819R1 | |
| EAN | 8015644007263 | |
| Product type | Moulded Case Circuit Breaker (MCCB) | |
| Frame size | XT1 160 | |
| Rated current (In) | 125 A | |
| Rated uninterrupted current (Iu) | 160 A | |
| Neutral rating | 50% of phase current | |
| Number of poles | 4 | |
| Trip unit | Thermomagnetic TMD | |
| Thermal setting range | 87.5 to 125 A | |
| Instantaneous magnetic setting | 1250 A | |
| Rated operational voltage | Up to 690 V AC / 500 V DC | |
| Rated insulation voltage | 800 V | |
| Rated impulse withstand voltage | 8 kV | |
| Breaking capacity (Icu) | 18 kA at 415 V AC | |
| Terminal type | Front terminals | |
| Mounting type | Fixed | |
| Frequency | 50 / 60 Hz | |
| Standards | IEC 60947-2 | |
| Protection rating | IP20 device rating | |
| Dimensions (H × W × D) | approx. 130 × 101.6 × 70 mm | |
| Weight | approx. 1.4 kg | |
| HS Code | 85362090 | |
| Country of Manufacture | Italy |
It is used to protect low voltage electrical circuits against overloads and short circuits in industrial, commercial and OEM power distribution systems.
The ABB 1SDA066819R1 has a 125 A rated current and is built on the XT1 160 A frame size.
InN=50% means the neutral pole is rated at 50% of the phase current, which is suitable for selected four-pole distribution applications.
The breaker is fitted with an adjustable thermomagnetic TMD trip unit for overload and short circuit protection.
This fixed MCCB uses front terminals, making it suitable for standard installation in switchboards, control panels and distribution assemblies.
ABB SACE Tmax XT moulded case circuit breakers are trusted by panel builders, electrical contractors and industrial engineers for dependable circuit protection, compact installation and long service life in demanding low voltage systems.