ABB XT1B 160 4 pole Basic MCCB Fixed Thermal/Adjustable Magnetic Release In=20A Ii=450A

ABB XT1B 160 4 pole Basic MCCB Fixed Thermal/Adjustable Magnetic Release In=20A Ii=450A

ABB XT1B 160 TMD 20-450 4P F F moulded case circuit breaker with thermomagnetic trip unit, 20 A rated current, four poles and fixed front terminals for industrial power distribution.

SKU: 1SDA066811R1Alt SKU: XT1B 160 TMD 20-450 4p F FMPN: 1SDA066811R1
Price
List Price £372.62 ex VAT
Your Price (ex VAT) Save 25%
£279.47 25% OFF
You save £93.16 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £279.47
Trade pricing is personalised to your account

Manufacturer Lead Time

£279.47

Why Choose the ABB XT1B 160 TMD 20-450 4P F F Moulded Case Circuit Breaker?

The ABB 1SDA066811R1 XT1B 160 TMD 20-450 4P F F is a high performance moulded case circuit breaker (MCCB) from the trusted ABB SACE Tmax XT series. Designed for reliable circuit protection in commercial and industrial electrical installations, it provides dependable protection against overloads and short circuits while maintaining continuity of service.

Featuring a thermomagnetic TMD trip unit, this four-pole MCCB combines adjustable thermal overload protection with instantaneous magnetic short circuit protection. Its compact fixed design with front terminals allows straightforward installation within switchboards, distribution panels and industrial control systems.

With a 20 A rated current, a 690 V AC operating voltage and a breaking capacity of up to 18 kA at 415 V AC, the ABB XT1B offers reliable protection for power distribution systems across a wide range of industrial and commercial applications.

Key Advantages

  • Compact ABB SACE Tmax XT moulded case circuit breaker.
  • 20 A rated current for dependable circuit protection.
  • Four-pole design for complete phase and neutral protection.
  • Thermomagnetic TMD trip unit for overload and short circuit protection.
  • 18 kA breaking capacity at 415 V AC.
  • Fixed version with front terminal connections for simple installation.
  • Designed in accordance with IEC 60947-2.
  • Suitable for industrial, commercial and OEM electrical systems.

Key Features

  • ABB SACE Tmax XT series.
  • Model: XT1B 160 TMD 20-450 4P F F.
  • Product ID: 1SDA066811R1.
  • 20 A rated current (In).
  • 160 A frame size.
  • Four-pole construction.
  • Thermomagnetic TMD adjustable trip unit.
  • Front terminal configuration.
  • Fixed mounting version.
  • Suitable for AC and DC applications.

Reliable Protection for Industrial Power Distribution

The ABB XT1B series is engineered to protect electrical installations by disconnecting circuits quickly during overload or short circuit conditions. The thermomagnetic release provides accurate long-term overload protection while reacting rapidly to severe fault currents, helping minimise equipment damage and improve operational safety.

Its compact dimensions, proven reliability and compliance with international standards make the XT1B range an excellent choice for switchboards, distribution panels, machinery and OEM electrical equipment where dependable circuit protection is essential.

Typical Applications

  • Industrial power distribution systems.
  • Electrical switchboards and panel builders.
  • OEM machinery.
  • Motor and feeder protection.
  • Commercial electrical installations.
  • Manufacturing facilities.
  • Infrastructure and utility applications.

Technical Specifications

Tick the specs you need, then view products that match.

Mounting Type Fixed
Application Power distribution
Current 20 A
Phase Three Phase
Poles 4-pole
Device Type MCCB
Breaking Capacity 18 kA
Trip Unit Thermal-magnetic
Manufacturer ABB
Series SACE Tmax XT
Model XT1B 160 TMD 20-450 4P F F
Product code 1SDA066811R1
Product type Moulded Case Circuit Breaker (MCCB)
Frame size XT1 160
Rated current (In) 20 A
Rated uninterrupted current (Iu) 160 A
Number of poles 4
Trip unit Thermomagnetic TMD
Thermal setting range 14 to 20 A
Instantaneous magnetic setting 450 A
Rated operational voltage Up to 690 V AC / 500 V DC
Breaking capacity (Icu) 18 kA at 415 V AC
Standards IEC 60947-2
Terminal type Front terminals
Mounting Fixed
Frequency 50 / 60 Hz
Protection rating IP20 (device)
Dimensions (H × W × D) Approx. 130 × 101.6 × 70 mm
Weight Approx. 1.4 kg
HS Code 85362090
Country of Manufacture Italy

Frequently Asked Questions

What is the ABB 1SDA066811R1 used for?

It is a moulded case circuit breaker designed to protect electrical circuits against overloads and short circuits in industrial and commercial power distribution systems.

What is the rated current of this MCCB?

The breaker has a 20 A rated current with a 160 A frame size.

How many poles does this circuit breaker have?

This model features a four-pole (4P) configuration for complete circuit protection.

What type of trip unit is fitted?

The breaker incorporates an adjustable thermomagnetic TMD trip unit that provides overload and short circuit protection.

Where is this MCCB typically installed?

It is commonly installed in electrical distribution boards, switchgear assemblies, industrial control panels and OEM equipment.

Trusted by Electrical Professionals Worldwide

ABB SACE Tmax XT moulded case circuit breakers are trusted by panel builders, OEMs and electrical engineers worldwide for delivering reliable circuit protection, excellent performance and long service life in demanding industrial environments.