1SDA065795R1 ABB T8V 3200 PR332/P LSIG 3200 A 3-Pole Fixed Circuit Breaker

1SDA065795R1 ABB T8V 3200 PR332/P LSIG 3200 A 3-Pole Fixed Circuit Breaker

ABB 1SDA065795R1 is a SACE Tmax T8V 3200 A three-pole fixed moulded case circuit breaker with rear vertical terminals and a PR332/P LSIG electronic protection release.

SKU: 1SDA065795R1MPN: 1SDA065795R1
Price
List Price £32,876.13 ex VAT
Your Price (ex VAT) Save 25%
£24,657.10 25% OFF
You save £8,219.03 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £24,657.10
Trade pricing is personalised to your account

Manufacturer Lead Time

£24,657.10

Why Choose the ABB T8V 3200 PR332/P LSIG Circuit Breaker?

The ABB T8V 3200 PR332/P LSIG is a high-performance Tmax T8 moulded case circuit breaker designed for protection and switching of high-current low-voltage power distribution systems. Supplied under ABB order code 1SDA065795R1, this three-pole breaker combines a 3200 A rated current with ABB's advanced PR332/P LSIG electronic protection release.

As part of the ABB SACE Tmax T8 series, the T8V is engineered for demanding industrial and commercial electrical installations where high breaking capacity and comprehensive electronic protection are required. The PR332/P LSIG trip unit provides long-time, short-time, instantaneous and ground-fault protection functions to protect distribution circuits against overloads, short circuits and earth faults.

This model is supplied in a fixed three-pole configuration with rear vertical terminals (VR). It has a rated operational voltage of 690 V AC and the T8V performance level provides an ultimate short-circuit breaking capacity of 130 kA at 415 V AC, making it suitable for installations with high prospective fault currents.

Key Advantages

  • High-current 3200 A Tmax T8 circuit breaker for demanding power distribution systems.
  • PR332/P LSIG electronic trip unit provides comprehensive circuit protection.
  • 130 kA ultimate breaking capacity at 415 V AC for high fault-level installations.
  • 690 V AC rated operational voltage supports industrial low-voltage distribution networks.
  • Three-pole fixed configuration for three-phase electrical systems.
  • Rear vertical terminals support integration into high-current switchboards and distribution assemblies.

Key Features

  • ABB SACE Tmax T8V series.
  • 3200 A rated current.
  • Three-pole construction.
  • PR332/P LSIG electronic release.
  • Long-time, short-time, instantaneous and ground-fault protection.
  • 130 kA Icu at 415 V AC.
  • 100 kA Ics at 415 V AC.
  • 690 V AC rated operational voltage.
  • 1000 V rated insulation voltage.
  • 8 kV rated impulse withstand voltage.
  • Fixed mounting with rear vertical terminals.

Reliable Protection for High-Current Power Distribution

The ABB Tmax T8 platform is designed for high-current low-voltage distribution systems where dependable switching and interruption of electrical faults are essential. The T8V performance level combines a high short-circuit breaking capacity with electronic protection, allowing the breaker to protect critical feeders and distribution circuits in demanding electrical installations.

The PR332/P LSIG electronic release provides long-time protection against overloads, short-time and instantaneous protection against short circuits, and ground-fault protection. Combined with the fixed mounting arrangement and rear vertical terminals, the T8V 3200 is well suited to integration into industrial switchboards, power distribution panels and power-control assemblies.

Typical Applications

  • Main low-voltage distribution switchboards.
  • Industrial power distribution systems.
  • High-current feeder protection.
  • Transformer secondary distribution systems.
  • Commercial and infrastructure electrical installations.
  • Power-control centres and switchgear assemblies.

Technical Specifications

Series SACE Tmax T8
ABB order code 1SDA065795R1
Product type Moulded case circuit breaker
Rated current (In) 3200 A
Rated uninterrupted current (Iu) 3200 A
Number of poles 3
Trip unit PR332/P
Protection functions LSIG
Release type Electronic
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 8 kV
Ultimate breaking capacity (Icu) at 415 V AC 130 kA
Service breaking capacity (Ics) at 415 V AC 100 kA
Mounting type Fixed
Terminal arrangement Rear vertical (VR)
Standard IEC 60947
ABB product group 310511-T-Max T4 - T8

Frequently Asked Questions

What is the ABB 1SDA065795R1?

The ABB 1SDA065795R1 is a Tmax T8V 3200 three-pole fixed moulded case circuit breaker with rear vertical terminals and a PR332/P LSIG electronic protection release.

What is the rated current of the ABB T8V 3200?

The T8V 3200 has a rated current of 3200 A and is designed for high-current low-voltage power distribution applications.

What protection functions does the PR332/P LSIG trip unit provide?

The PR332/P LSIG electronic release provides long-time, short-time, instantaneous and ground-fault protection functions.

What is the breaking capacity of the ABB T8V 3200?

The T8V version has an ultimate short-circuit breaking capacity of 130 kA at 415 V AC and a service breaking capacity of 100 kA at 415 V AC.

What voltage is the ABB 1SDA065795R1 rated for?

The breaker has a rated operational voltage of 690 V AC, a rated insulation voltage of 1000 V and a rated impulse withstand voltage of 8 kV.

How is the ABB T8V 3200 installed?

This version is supplied as a fixed three-pole circuit breaker with rear vertical terminals (VR) for integration into low-voltage switchboards and power distribution assemblies.

Trusted by Electrical Professionals Worldwide

ABB SACE Tmax circuit breakers are widely used in industrial, commercial and infrastructure power distribution systems to provide dependable switching, electronic protection and fault interruption in demanding low-voltage installations.