1SDA065743R1 ABB T8L 3200 PR332/P LSIG 3200 A 4-Pole Circuit Breaker

1SDA065743R1 ABB T8L 3200 PR332/P LSIG 3200 A 4-Pole Circuit Breaker

ABB 1SDA065743R1 is a fixed four-pole Tmax T8L 3200 A circuit breaker with rear vertical terminals and a PR332/P-LSIG electronic trip unit for comprehensive low-voltage power distribution protection.

SKU: 1SDA065743R1MPN: 1SDA065743R1
Price
List Price £35,441.50 ex VAT
Your Price (ex VAT) Save 25%
£26,581.13 25% OFF
You save £8,860.38 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £26,581.13
Trade pricing is personalised to your account

Manufacturer Lead Time

£26,581.13

Why Choose the ABB T8L 3200 PR332/P LSIG 1SDA065743R1 Circuit Breaker?

The ABB 1SDA065743R1 is a high-performance Tmax T8L 3200 moulded-case circuit breaker designed for protection and switching in demanding low-voltage power distribution systems. This fixed four-pole breaker combines a 3200 A rated current with the advanced PR332/P-LSIG solid-state electronic trip unit, providing comprehensive protection for high-current industrial and commercial electrical installations.

The PR332/P-LSIG protection release provides long-time, short-time, instantaneous and earth-fault protection, helping safeguard electrical systems against overloads, short circuits and ground faults. The electronic protection platform offers accurate and dependable circuit monitoring while supporting the coordination requirements of sophisticated low-voltage distribution networks.

Configured as a fixed four-pole breaker with rear vertical terminals, the T8L 3200 is suitable for high-current switchboards where robust electrical connections and efficient panel integration are required. Its rated operational voltage reaches 690 V AC, while the Tmax T8 platform combines high switching performance with ABB's established low-voltage protection technology.

Key Advantages

  • Heavy-duty 3200 A moulded-case circuit breaker for high-current distribution systems.
  • Advanced PR332/P-LSIG electronic trip unit for comprehensive circuit protection.
  • LSIG protection functions cover overload, short-time short circuit, instantaneous short circuit and earth faults.
  • Four-pole configuration suitable for switching and protecting multi-conductor power systems.
  • Fixed installation with rear vertical terminals for switchboard integration.
  • Rated for operation in low-voltage systems up to 690 V AC.

Key Features

  • ABB SACE Tmax T8L 3200 circuit breaker.
  • 3200 A rated current.
  • Four-pole construction.
  • PR332/P-LSIG solid-state electronic release.
  • Long-time, short-time, instantaneous and ground-fault protection.
  • Fixed (F) installation version.
  • Rear vertical (VR) terminals.
  • 690 V AC rated operational voltage.
  • 1000 V rated insulation voltage.
  • 8 kV rated impulse withstand voltage.
  • IP20 degree of protection.
  • Designed to IEC 60947 requirements.

Advanced Protection for High-Current Power Distribution

The ABB Tmax T8 platform is designed for demanding low-voltage distribution applications where high current capacity, dependable interruption and accurate electronic protection are essential. The T8L 3200 provides a robust switching and protection solution for main distribution boards, industrial power systems and other high-capacity electrical installations.

Its PR332/P-LSIG electronic release monitors electrical conditions and provides multiple protection functions within a single trip unit. Long-time protection responds to sustained overloads, short-time and instantaneous functions protect against short-circuit conditions, while ground-fault protection helps detect potentially damaging current paths to earth.

Typical Applications

  • Main low-voltage distribution switchboards.
  • Industrial power distribution systems.
  • Manufacturing and process plants.
  • Commercial and infrastructure electrical installations.
  • High-current feeder and distribution protection.
  • Power distribution systems requiring earth-fault protection.

Technical Specifications

Series SACE Tmax T
ABB order code 1SDA065743R1
Product type Automatic moulded-case circuit breaker
Frame / subtype T8L
Rated current (In) 3200 A
Rated uninterrupted current (Iu) 3200 A
Number of poles 4
Trip unit PR332/P-LSIG electronic release
Protection functions L, S, I and G
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 8 kV
Installation Fixed
Terminal configuration Rear vertical (VR)
Protection rating IP20
Electrical durability 3000 cycles
Mechanical durability 15000 cycles
Dimensions (W × H × D) 553 × 382 × 282 mm
Net weight 15 kg
Standard IEC 60947
EAN 8015644686543
ABB product group 310511-T-Max T4 - T8

Frequently Asked Questions

What is the ABB 1SDA065743R1 used for?

The ABB 1SDA065743R1 is a 3200 A four-pole Tmax T8L circuit breaker used for switching and protecting high-current low-voltage power distribution systems.

What protection unit is fitted to this circuit breaker?

The breaker is equipped with an ABB PR332/P-LSIG solid-state electronic trip unit, providing long-time, short-time, instantaneous and ground-fault protection.

What is the rated current of the ABB T8L 1SDA065743R1?

The circuit breaker has a rated current of 3200 A and is designed for high-current low-voltage distribution applications.

How is the 1SDA065743R1 installed and connected?

This model is a fixed four-pole circuit breaker configured with rear vertical terminals for integration into suitable low-voltage switchboards.

What does LSIG protection mean?

LSIG denotes long-time, short-time, instantaneous and ground-fault protection, providing comprehensive protection against overloads, short circuits and earth-fault conditions.

Trusted ABB Power Distribution Protection

ABB SACE Tmax circuit breakers are engineered for dependable switching and protection in low-voltage power distribution systems, combining robust breaker construction with electronic protection technology for demanding industrial and commercial installations.