ABB 1SDA065730R1 is a 2000 A four-pole fixed SACE Tmax T8L moulded case circuit breaker with a PR331/P-LSIG electronic trip unit providing long-time, short-time, instantaneous and ground-fault protection for industrial AC power distribution.
£19,364.61
The ABB 1SDA065730R1 is a high-current SACE Tmax T8L 2000 moulded case circuit breaker (MCCB) designed for demanding industrial power distribution applications. Identified by ABB as T8L 2000 PR331/P LSIG In=2000A 4p F F, it combines a 2000 A current rating, four-pole construction and a PR331/P-LSIG solid-state electronic trip unit.
The PR331/P-LSIG trip unit provides comprehensive electronic protection functions covering long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground-fault protection (G). This combination makes the breaker suitable for installations requiring coordinated protection against multiple electrical fault conditions.
Designed for 690 V AC systems, the 1SDA065730R1 features fixed construction with front terminals and a rated uninterrupted current of 2000 A. Its T8L frame, electronic protection and four-pole configuration make it particularly suitable for high-current industrial switchboards, main distribution systems and three-phase four-wire power networks.
High-current power distribution systems require protection that can distinguish between overloads, short-duration fault conditions, severe short circuits and ground faults. The ABB PR331/P-LSIG electronic release combines these functions within the T8L platform, providing long-time, short-time, instantaneous and ground-fault protection for coordinated industrial distribution applications.
The ABB 1SDA065730R1 combines this LSIG protection with a 2000 A four-pole circuit breaker rated for operation at 690 V AC. Fixed mounting and front connections make it well suited to main switchboards, distribution assemblies and other installations requiring a permanently installed high-current protection device.
| Series | SACE Tmax T8 |
|---|---|
| Breaker version | T8L 2000 |
| ABB product group | 310511-T-Max T4 - T8 |
| Order code / SKU | 1SDA065730R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Rated current (In) | 2000 A |
| Rated uninterrupted current (Iu) | 2000 A |
| Rated operational voltage | 690 V AC |
| Number of poles | 4 |
| Trip unit | PR331/P-LSIG solid-state electronic release |
| Protection functions | Long-time, short-time, instantaneous and ground-fault (LSIG) |
| Mounting | Fixed |
| Main-circuit connection position | Front |
| Electrical endurance | 4,500 cycles at up to 20 cycles/hour |
| Mechanical endurance | 15,000 cycles at up to 60 cycles/hour |
| Dimensions (W × H × D) | 553 × 382 × 282 mm |
| Net weight | 12.5 kg |
| EAN | 8015644686376 |
The ABB 1SDA065730R1 is a 2000 A four-pole SACE Tmax T8L moulded case circuit breaker designed for switching and electronic protection of high-current industrial power distribution systems.
The circuit breaker has a rated uninterrupted current of 2000 A and is designed for a rated operational voltage of 690 V AC.
The 1SDA065730R1 uses an ABB PR331/P-LSIG solid-state electronic trip unit.
LSIG identifies long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection functions.
The 1SDA065730R1 is a fixed four-pole circuit breaker with front terminals, designed for permanent integration into compatible industrial switchboards and power distribution assemblies.
ABB SACE Tmax T8 circuit breakers combine high current capacity with advanced electronic protection, providing dependable overload, short-circuit and ground-fault protection for demanding industrial power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.