Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA064728R1 is a SACE New Emax DC E4H 3200 A three-pole fixed air circuit breaker with a PR123/DC electronic overcurrent release and breaking capacity up to 100 kA at 500 V DC.
£23,285.48
The ABB 1SDA064728R1 is a high-performance DC air circuit breaker designed for reliable switching and overcurrent protection in demanding direct-current electrical distribution systems. Configured as an E4H 3200 three-pole fixed circuit breaker, it combines a 3200 A rated current with the advanced PR123/DC electronic overcurrent release for dependable protection of high-current DC networks.
Part of the ABB SACE New Emax DC series, this circuit breaker is specifically engineered for applications requiring high fault-interruption capability and sophisticated electronic protection. The E4H configuration provides ABB's H short-circuit performance level, making it well suited to industrial switchboards and critical DC power distribution installations.
With a rated operational voltage of 750 V DC, the 1SDA064728R1 delivers rated ultimate and service short-circuit breaking capacities of 100 kA at 500 V DC and 65 kA at 750 V DC. Its fixed construction uses a rear main-circuit connection arrangement, providing a robust solution for permanent installation within compatible switchgear.
Direct-current networks require circuit breakers specifically engineered to interrupt DC fault currents because direct current does not provide the natural current-zero points present in alternating-current systems. The ABB SACE Emax DC range addresses these requirements with dedicated interruption technology and electronic protection designed for reliable operation in demanding high-current DC distribution installations.
The PR123/DC electronic release fitted to the 1SDA064728R1 combines with the E4H platform to provide dependable overcurrent protection and exceptional fault-interruption capability. With a 3200 A current rating, 100 kA breaking capacity at 500 V DC and fixed switchgear construction, this circuit breaker is particularly suited to installations where high current capacity and robust short-circuit protection are essential.
| Product group | New Emax DC |
|---|---|
| Series | SACE Emax DC |
| ABB order code | 1SDA064728R1 |
| Product type | DC air circuit breaker |
| Current type | DC |
| Frame | E4 |
| Performance level | H |
| Rated current (In) | 3200 A |
| Rated operational current (Ie) | 3200 A |
| Rated uninterrupted current (Iu) | 3200 A |
| Rated operational voltage | 750 V DC |
| Rated voltage (Ur) | 750 V |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 3 |
| Release | PR123/DC |
| Release type | Electronic |
| Overload release setting | 1280 A |
| Undelayed short-circuit release setting | 4800 A |
| Rated ultimate short-circuit breaking capacity (Icu) | 100 kA at 500 V DC; 65 kA at 750 V DC |
| Rated service short-circuit breaking capacity (Ics) | 100 kA at 500 V DC; 65 kA at 750 V DC |
| Construction | Fixed circuit breaker |
| Main-circuit connection position | Rear |
| Main-circuit connection type | Bolted connection |
| Auxiliary contacts | 4 change-over contacts |
| Actuating element | Push-button contact |
| Trip signalling relay | Available |
| Motor drive | Optional |
| Integrated motor drive | No |
| Integrated undervoltage release | No |
| Integrated earth-fault protection | No |
| Protection rating | IP30 |
| Power loss | 312 W |
| Electrical durability | 7000 cycles at 1000 V |
| Mechanical durability | 15,000 cycles |
| Maximum operating frequency | 60 cycles per hour |
| Dimensions (W × H × D) | 566 × 418 × 302 mm |
| Net weight | 81 kg |
| Standards | IEC |
| EAN | 8015644676216 |
| Customs tariff number | 85362090 |
The ABB 1SDA064728R1 is a 3200 A three-pole DC air circuit breaker designed for switching and protecting high-current direct-current electrical distribution systems.
The circuit breaker has a 3200 A rated current and a 750 V DC rated operational voltage.
The 1SDA064728R1 is fitted with an ABB PR123/DC electronic overcurrent release designed for protection of direct-current electrical systems.
The E4H configuration provides rated ultimate and service short-circuit breaking capacities of 100 kA at 500 V DC and 65 kA at 750 V DC.
The 1SDA064728R1 is a fixed three-pole circuit breaker with a rear main-circuit connection arrangement for permanent installation within compatible ABB SACE Emax DC switchgear.
ABB SACE Emax DC air circuit breakers are engineered for dependable protection of demanding direct-current installations, combining dedicated electronic DC protection, high short-circuit breaking performance and robust switchgear configurations for industrial and critical power distribution systems.
We use cookies