ABB 1SDA063088R1 T7L 1600 is a 1600 A four-pole fixed motorisable moulded case circuit breaker with a PR332/P-LSIRc electronic trip unit, residual-current protection and 120 kA breaking capacity at 380–415 V AC for high-current low-voltage power distribution.
£17,169.26
The ABB 1SDA063088R1, extended product type T7L 1600 PR332/P LSIRc In=1600A 4p F F M, is a high-performance moulded case circuit breaker (MCCB) designed for protection and switching in demanding low-voltage power distribution systems. Part of the ABB SACE Tmax T7 series, it combines a 1600 A rated uninterrupted current, four-pole construction and the advanced PR332/P-LSIRc electronic trip unit.
The PR332/P-LSIRc electronic release provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection together with residual-current protection. Its adjustable protection characteristics allow the breaker to be coordinated with the requirements of high-current distribution networks while adding protection against residual-current faults.
The T7L 1600 provides a rated ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC, with breaking capacity reaching 200 kA at 220–230 V AC. This version is a fixed four-pole, front-terminal, motorisable circuit breaker, making it particularly suitable for industrial switchboards, infrastructure and high-capacity distribution systems requiring comprehensive electronic protection and remote switching capability.
Moulded case circuit breakers such as the ABB Tmax T7L protect low-voltage electrical distribution systems against damaging overload and short-circuit currents. The four-pole construction of the 1SDA063088R1 makes it suitable for three-phase four-wire networks, while the PR332/P-LSIRc electronic trip unit extends the protection capability to include residual-current fault detection.
Combining comprehensive electronic protection with a 120 kA breaking capacity at 380–415 V AC and 20 kA for 1 s short-time withstand capability, the 1SDA063088R1 is well suited to high-current distribution systems where protection coordination and dependable fault interruption are essential. Its motorisable configuration also supports applications requiring remote or automated circuit breaker operation.
| Series | SACE Tmax T7 |
|---|---|
| ABB product group | 310511-T-Max T4 - T8 |
| Order code | 1SDA063088R1 |
| EAN | 8015644656379 |
| Product type | Moulded case circuit breaker (MCCB) |
| Breaker frame | T7L 1600 |
| Rated current (In) | 1600 A |
| Rated uninterrupted current (Iu) | 1600 A |
| Number of poles | 4 |
| Trip unit | PR332/P-LSIRc electronic release |
| Release type | Electronic |
| Protection functions | Long-time, short-time delayed, instantaneous and residual-current protection |
| Long-time protection adjustment | 640–1600 A |
| Instantaneous protection adjustment | 2400–24000 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Ultimate breaking capacity (Icu) at 220–230 V AC | 200 kA |
| Ultimate breaking capacity (Icu) at 380–415 V AC | 120 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 100 kA |
| Ultimate breaking capacity (Icu) at 500 V AC | 85 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 50 kA |
| Service breaking capacity (Ics) at 220–230 V AC | 200 kA |
| Service breaking capacity (Ics) at 380–415 V AC | 120 kA |
| Service breaking capacity (Ics) at 440 V AC | 100 kA |
| Service breaking capacity (Ics) at 500 V AC | 64 kA |
| Service breaking capacity (Ics) at 690 V AC | 37.5 kA |
| Rated short-time withstand current (Icw) | 20 kA for 1 s |
| Power loss at rated conditions | 77 W per pole |
| Electrical durability | 2,000 cycles |
| Mechanical durability | 10,000 cycles |
| Installation version | Fixed |
| Terminal position | Front |
| Operating configuration | Motorisable |
| Dimensions (H × W × D) | 268 × 280 × 178 mm |
| Net weight | 14 kg |
| Standard | IEC |
The ABB 1SDA063088R1 is a 1600 A four-pole moulded case circuit breaker designed for switching and protection of high-current low-voltage distribution circuits against overload, short-circuit and residual-current fault conditions.
The circuit breaker has a rated uninterrupted current of 1600 A, with long-time protection adjustable from 640–1600 A.
The breaker provides a rated ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC, with breaking capacity reaching 200 kA at 220–230 V AC.
The PR332/P-LSIRc electronic trip unit provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and residual-current protection for comprehensive protection of low-voltage distribution circuits.
Yes. The 1SDA063088R1 is a fixed, front-terminal, motorisable four-pole circuit breaker, making it suitable for installations requiring remote or automated switching.
ABB SACE Tmax moulded case circuit breakers are widely used in industrial, commercial and infrastructure power distribution systems where dependable electronic protection, high breaking capacity and configurable protection characteristics are required.