1SDA063084R1 ABB T7L 1600 PR331/P LSIG 1600 A 4-Pole MCCB

1SDA063084R1 ABB T7L 1600 PR331/P LSIG 1600 A 4-Pole MCCB

ABB 1SDA063084R1 is a T7L 1600 four-pole fixed moulded case circuit breaker with a 1600 A rating, PR331/P LSIG electronic protection, integrated earth-fault protection and 120 kA ultimate breaking capacity at 400 V AC.

SKU: 1SDA063084R1MPN: 1SDA063084R1
Price
List Price £21,789.51 ex VAT
Your Price (ex VAT) Save 25%
£16,342.13 25% OFF
You save £5,447.38 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £16,342.13
Trade pricing is personalised to your account

Manufacturer Lead Time

£16,342.13

Why Choose the ABB 1SDA063084R1 T7L 1600 Circuit Breaker?

The ABB 1SDA063084R1 is a high-performance Tmax T7L 1600 moulded case circuit breaker (MCCB) designed for protection and switching of high-current low-voltage electrical distribution systems. Equipped with the advanced PR331/P LSIG electronic trip unit, this four-pole breaker provides adjustable long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection for demanding industrial and commercial installations.

As part of the ABB SACE Tmax T7 series, the T7L 1600 combines a substantial continuous current rating with high fault-breaking performance. Its L performance level provides an ultimate short-circuit breaking capacity of 120 kA at 400 V AC, 50 Hz, while its 1600 A rated uninterrupted current makes it suitable for main distribution boards, high-current feeders and large industrial power systems.

The 1SDA063084R1 is supplied as a fixed four-pole circuit breaker with front terminals and a stored-energy operating mechanism. Rated for 690 V AC, with adjustable overload protection from 640–1600 A and integrated earth-fault protection, it provides flexible and dependable protection for demanding low-voltage distribution installations.

Key Advantages

  • High-capacity 1600 A moulded case circuit breaker for industrial power distribution.
  • 120 kA ultimate breaking capacity at 400 V AC, 50 Hz for demanding fault conditions.
  • Advanced PR331/P LSIG electronic trip unit with overload, short-time, instantaneous and earth-fault protection.
  • Four-pole fixed construction suitable for three-phase distribution systems requiring four-pole switching.
  • Adjustable overload protection from 640–1600 A for flexible system coordination.
  • Stored-energy operating mechanism and optional motor drive support integration into sophisticated power distribution systems.

Key Features

  • ABB SACE Tmax T7L 1600 series.
  • 1600 A rated uninterrupted current.
  • PR331/P LSIG solid-state electronic release.
  • 120 kA Icu at 400 V AC, 50 Hz.
  • Adjustable overload protection from 640–1600 A.
  • Adjustable short-time delayed short-circuit protection from 960–16000 A.
  • Adjustable instantaneous short-circuit protection from 2400–19200 A.
  • Integrated earth-fault protection.
  • Fixed mounting with front terminals and stored-energy operating mechanism.

Advanced Circuit Protection for Power Distribution

Moulded case circuit breakers such as the ABB Tmax T7L protect electrical distribution systems against overloads, short circuits and earth faults while providing reliable isolation and switching of high-current circuits. The T7L performance level is designed for demanding installations where substantial prospective fault currents require dependable interruption capability.

The PR331/P LSIG electronic trip unit combines adjustable long-time overload, short-time delayed, instantaneous short-circuit and ground-fault protection. These functions allow protection settings to be coordinated with connected equipment and downstream protective devices, while the four-pole configuration supports comprehensive switching in suitable three-phase distribution systems.

Typical Applications

  • Main low-voltage distribution boards and switchboards.
  • Four-pole three-phase power distribution systems.
  • High-current industrial feeder protection.
  • Transformer secondary distribution systems.
  • Manufacturing plants and process facilities.
  • Electrical installations requiring integrated earth-fault protection.

Technical Specifications

Series SACE Tmax T7
Order code / MPN 1SDA063084R1
ABB product group 310511-T-Max T4 - T8
EAN / GTIN 8015644656331
Product type Moulded case circuit breaker (MCCB)
Frame size T7
Performance level L
Rated current (In) 1600 A
Rated uninterrupted current (Iu) 1600 A
Rated voltage 690 V AC
Number of poles 4
Trip unit PR331/P LSIG
Release type Electronic / solid-state
Protection functions L, S, I and G
Overload setting range 640–1600 A
Short-time delayed short-circuit setting range 960–16000 A
Instantaneous short-circuit setting range 2400–19200 A
Ultimate short-circuit breaking capacity (Icu) at 400 V AC, 50 Hz 120 kA
Integrated earth-fault protection Yes
Protection rating IP20
Mounting type Fixed circuit breaker
Terminal position Front
Main circuit connection Bolt connection
Operating mechanism Stored-energy mechanism
Complete with protection unit Yes
Motor operator Optional
Integrated motor operator No
Integrated undervoltage release No
DIN rail mounting No
Dimensions (H × W × D) 268 × 280 × 178 mm
Net weight approx. 14 kg

Frequently Asked Questions

What is the ABB 1SDA063084R1 used for?

This circuit breaker is designed to protect and switch high-current low-voltage electrical distribution circuits in industrial, commercial and infrastructure installations.

What is the rated current of the ABB T7L 1600?

The ABB 1SDA063084R1 has a rated uninterrupted current of 1600 A, with its overload protection adjustable from 640–1600 A.

What protection functions does the PR331/P LSIG trip unit provide?

The PR331/P LSIG electronic trip unit provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection.

What is the breaking capacity of the 1SDA063084R1?

The T7L version provides an ultimate short-circuit breaking capacity of 120 kA at 400 V AC, 50 Hz.

How is the ABB 1SDA063084R1 installed?

The breaker is supplied in a fixed four-pole configuration with front terminals and a stored-energy operating mechanism, with optional motor operation available.

Trusted for Industrial Power Distribution

ABB SACE Tmax circuit breakers are designed for demanding low-voltage power distribution applications where dependable switching, high fault-breaking performance and configurable electronic circuit protection are required.