1SDA063078R1 ABB T7L 1600 PR332/P LSI 1600 A 3-Pole MCCB

1SDA063078R1 ABB T7L 1600 PR332/P LSI 1600 A 3-Pole MCCB

ABB 1SDA063078R1 is a T7L 1600 three-pole fixed moulded case circuit breaker with a 1600 A rating, PR332/P LSI electronic protection and 120 kA ultimate breaking capacity at 380–415 V AC.

SKU: 1SDA063078R1MPN: 1SDA063078R1
Price
List Price £17,089.19 ex VAT
Your Price (ex VAT) Save 25%
£12,816.89 25% OFF
You save £4,272.30 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £12,816.89
Trade pricing is personalised to your account

Manufacturer Lead Time

£12,816.89

Why Choose the ABB 1SDA063078R1 T7L 1600 Circuit Breaker?

The ABB 1SDA063078R1 is a high-performance Tmax T7L 1600 moulded case circuit breaker (MCCB) designed for protection and switching of high-current low-voltage electrical distribution systems. Equipped with the advanced PR332/P LSI electronic trip unit, this three-pole breaker provides adjustable long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection for demanding industrial and commercial installations.

As part of the ABB SACE Tmax T7 series, the T7L 1600 combines a substantial continuous current rating with high fault-breaking performance. Its L performance level provides an ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC, while its 1600 A rated uninterrupted current makes it suitable for main distribution boards, high-current feeders and large industrial power systems.

The 1SDA063078R1 is supplied as a fixed three-pole circuit breaker with front terminals and a stored-energy operating mechanism. Rated for operation up to 690 V AC, with adjustable overload protection from 640–1600 A, it provides flexible and dependable protection for demanding low-voltage power distribution applications.

Key Advantages

  • High-capacity 1600 A moulded case circuit breaker for industrial power distribution.
  • 120 kA ultimate breaking capacity at 380–415 V AC for demanding fault conditions.
  • Advanced PR332/P LSI electronic trip unit with overload, short-time and instantaneous short-circuit protection.
  • Three-pole fixed construction with front terminal connections.
  • Adjustable overload protection from 640–1600 A for flexible system coordination.
  • Stored-energy operating mechanism supports dependable switching of high-current circuits.

Key Features

  • ABB SACE Tmax T7L 1600 series.
  • 1600 A rated uninterrupted current.
  • PR332/P LSI solid-state electronic release.
  • 120 kA Icu at 380–415 V AC.
  • Adjustable overload protection from 640–1600 A.
  • Adjustable short-time delayed short-circuit protection from 960–16000 A.
  • Adjustable instantaneous short-circuit protection from 2400–19200 A.
  • 690 V AC rated voltage.
  • Fixed mounting with front terminals and stored-energy operating mechanism.

Advanced Circuit Protection for Power Distribution

Moulded case circuit breakers such as the ABB Tmax T7L protect electrical distribution systems against overloads and short circuits while providing reliable isolation and switching of high-current circuits. The T7L performance level is designed for demanding installations where substantial prospective fault currents require dependable interruption capability.

The PR332/P LSI electronic trip unit combines adjustable long-time overload, short-time delayed and instantaneous short-circuit protection. These functions allow protection settings to be coordinated with connected equipment and downstream protective devices, supporting selective and dependable protection across sophisticated industrial low-voltage distribution systems.

Typical Applications

  • Main low-voltage distribution boards and switchboards.
  • High-current industrial feeder protection.
  • Transformer secondary distribution systems.
  • Manufacturing plants and process facilities.
  • Commercial and infrastructure power distribution.
  • Large industrial electrical distribution networks.

Technical Specifications

Series SACE Tmax T7
Order code / MPN 1SDA063078R1
ABB product group 310511-T-Max T4 - T8
Product type Moulded case circuit breaker (MCCB)
Frame size T7
Performance level L
Rated current (In) 1600 A
Rated uninterrupted current (Iu) 1600 A
Rated voltage 690 V AC
Number of poles 3
Trip unit PR332/P LSI
Release type Electronic / solid-state
Protection functions L, S and I
Overload setting range 640–1600 A
Short-time delayed short-circuit setting range 960–16000 A
Instantaneous short-circuit setting range 2400–19200 A
Ultimate short-circuit breaking capacity (Icu) at 220–230 V AC 200 kA
Ultimate short-circuit breaking capacity (Icu) at 380–415 V AC 120 kA
Ultimate short-circuit breaking capacity (Icu) at 440 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 500 V AC 85 kA
Ultimate short-circuit breaking capacity (Icu) at 690 V AC 50 kA
Protection rating IP20
Mounting type Fixed circuit breaker
Terminal position Front
Main circuit connection Bolt connection
Operating mechanism Stored-energy mechanism
Complete with protection unit Yes
Motor operator Optional
Dimensions (H × W × D) 268 × 210 × 178 mm
Weight approx. 11 kg

Frequently Asked Questions

What is the ABB 1SDA063078R1 used for?

This circuit breaker is designed to protect and switch high-current low-voltage electrical distribution circuits in industrial, commercial and infrastructure installations.

What is the rated current of the ABB T7L 1600?

The ABB 1SDA063078R1 has a rated uninterrupted current of 1600 A, with its overload protection adjustable from 640–1600 A.

What protection functions does the PR332/P LSI trip unit provide?

The PR332/P LSI electronic trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection.

What is the breaking capacity of the 1SDA063078R1?

The T7L version provides an ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC.

How is the ABB 1SDA063078R1 installed?

The breaker is supplied in a fixed three-pole configuration with front terminals and a stored-energy operating mechanism, with optional motor operation available.

Trusted for Industrial Power Distribution

ABB SACE Tmax circuit breakers are designed for demanding low-voltage power distribution applications where dependable switching, high fault-breaking performance and configurable electronic circuit protection are required.