Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA063069R1 T7L 1600 is a 1600 A four-pole fixed moulded case circuit breaker with a PR332/P-LI electronic trip unit and 120 kA breaking capacity at 380–415 V AC for high-current low-voltage power distribution.
£13,932.80
The ABB 1SDA063069R1, extended product type T7L 1600 PR332/P LI In=1600A 4p F F, is a high-performance moulded case circuit breaker (MCCB) designed for protection and switching in demanding low-voltage electrical distribution systems. Part of the ABB SACE Tmax T7 series, it combines a 1600 A rated uninterrupted current, four-pole construction and a PR332/P-LI solid-state electronic trip unit.
The PR332/P-LI release provides long-time overload and instantaneous short-circuit protection for high-current power distribution circuits. Its adjustable protection thresholds allow the breaker characteristics to be matched to the requirements of the installation, with overload protection adjustable from 640–1600 A and instantaneous short-circuit protection adjustable from 2400–24000 A.
With a rated ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC, the T7L 1600 is designed for installations with high prospective fault currents. This version is supplied as a fixed four-pole circuit breaker with front terminals and a lever operating mechanism, making it a robust solution for industrial switchboards, infrastructure and high-capacity power distribution assemblies.
Moulded case circuit breakers such as the ABB Tmax T7L protect low-voltage electrical distribution systems against excessive currents caused by overload and short-circuit conditions. The four-pole construction makes the 1SDA063069R1 suitable for three-phase four-wire distribution systems where all four poles need to be incorporated into the circuit breaker arrangement.
The PR332/P-LI electronic trip unit combines adjustable long-time overload protection with instantaneous short-circuit protection. Together with the 120 kA breaking capacity at 380–415 V AC of the T7L platform, the 1SDA063069R1 provides dependable protection for high-current distribution networks requiring robust fault interruption and configurable electronic protection.
| Series | SACE Tmax T7 |
|---|---|
| ABB product group | 310511-T-Max T4 - T8 |
| Order code | 1SDA063069R1 |
| EAN | 8015644656188 |
| Product type | Moulded case circuit breaker (MCCB) |
| Breaker type | T7L 1600 |
| Rated uninterrupted current (Iu) | 1600 A |
| Number of poles | 4 |
| Trip unit | PR332/P-LI electronic release |
| Release type | Solid-state electronic |
| Protection functions | Long-time overload and instantaneous short-circuit protection |
| Overload release adjustment | 640–1600 A |
| Instantaneous short-circuit release adjustment | 2400–24000 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V |
| Ultimate breaking capacity (Icu) at 220–230 V AC | 200 kA |
| Ultimate breaking capacity (Icu) at 380–415 V AC | 120 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 100 kA |
| Ultimate breaking capacity (Icu) at 500 V AC | 85 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 50 kA |
| Service breaking capacity (Ics) at 220–230 V AC | 200 kA |
| Service breaking capacity (Ics) at 380–415 V AC | 120 kA |
| Service breaking capacity (Ics) at 440 V AC | 100 kA |
| Service breaking capacity (Ics) at 500 V AC | 64 kA |
| Service breaking capacity (Ics) at 690 V AC | 37.5 kA |
| Rated short-time withstand current (Icw) | 20 kA for 1 s |
| Installation version | Fixed |
| Terminal position | Front |
| Main-circuit connection | Bolted connection |
| Operating mechanism | Lever operated |
| Degree of protection | IP20 |
| Dimensions (H × W × D) | 268 × 235 × 154 mm |
| Net weight | approx. 9.9 kg |
| Country of origin | Italy |
| Standard | IEC |
The ABB 1SDA063069R1 is a 1600 A four-pole moulded case circuit breaker designed for switching and protection of high-current low-voltage electrical distribution circuits against overload and short-circuit conditions.
The circuit breaker has a rated uninterrupted current of 1600 A, with its overload release adjustable from 640–1600 A.
The breaker provides a rated ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC, with a capacity of up to 200 kA at 220–230 V AC.
The breaker is fitted with an ABB PR332/P-LI electronic trip unit, providing adjustable long-time overload and instantaneous short-circuit protection.
Yes. The 1SDA063069R1 is a four-pole fixed circuit breaker with front terminals, making it suitable for high-current three-phase four-wire distribution systems requiring four-pole switching.
ABB SACE Tmax moulded case circuit breakers are widely used in industrial, commercial and infrastructure power distribution systems where dependable electronic protection, high breaking capacity and robust switching performance are required.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.