ABB 1SDA063067R1 is a Tmax T7L1600 four-pole fixed moulded case circuit breaker rated at 1600 A with a PR232/P LSI electronic trip unit and 120 kA breaking capacity at 415 V AC.
£14,411.21
The ABB 1SDA063067R1 is a high-performance Tmax T7L moulded case circuit breaker (MCCB) designed for protection and control of high-current low-voltage power distribution circuits. As part of the proven ABB Tmax T7 series, this fixed circuit breaker combines a 1600 A rated current, four-pole configuration and electronic protection for demanding commercial and industrial electrical installations.
This T7L circuit breaker is equipped with an ABB PR232/P LSI electronic trip unit, providing long-time overload, selective short-circuit and instantaneous short-circuit protection. The electronic release enables dependable circuit protection while supporting selective coordination within complex low-voltage distribution systems.
With an ultimate short-circuit breaking capacity of 120 kA at 415 V AC, the T7L1600 is engineered for installations with high prospective fault currents. This version features a fixed four-pole construction with front terminals, making it suitable for switchboards, distribution panels and industrial power systems requiring robust four-pole protection.
Moulded case circuit breakers such as the ABB Tmax T7 protect electrical distribution systems against overloads and short circuits while providing reliable circuit switching and isolation. Their high current capability makes them particularly suitable for main distribution boards, industrial switchboards and large electrical installations.
The PR232/P electronic trip unit provides LSI protection comprising long-time, short-time selective and instantaneous functions. This combination allows the circuit breaker to respond appropriately to different fault conditions while helping maintain discrimination between protective devices in coordinated distribution systems.
| Series | Tmax T7 |
|---|---|
| ABB order code | 1SDA063067R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Frame | T7L 1600 |
| Rated current | 1600 A |
| Number of poles | 4 |
| Trip unit | PR232/P |
| Protection functions | LSI |
| Ultimate breaking capacity (Icu) at 415 V AC | 120 kA |
| Mounting type | Fixed |
| Terminal arrangement | Front terminals |
| ABB product group | 310511-T-Max T4 - T8 |
This Tmax T7L moulded case circuit breaker is used to protect and control high-current low-voltage power distribution circuits against overloads and short circuits.
The ABB 1SDA063067R1 has a rated current of 1600 A.
The PR232/P trip unit provides LSI protection, comprising long-time overload, selective short-circuit and instantaneous short-circuit protection.
This T7L version has an ultimate short-circuit breaking capacity of 120 kA at 415 V AC.
This model is a fixed four-pole circuit breaker with front terminals, intended for integration into low-voltage switchboards and power distribution assemblies.
ABB Tmax circuit breakers are widely used in commercial and industrial power distribution systems where dependable protection, high breaking capacity and robust electrical performance are required.