ABB 1SDA063011R1 SACE Tmax T7S 1600 A three-pole fixed moulded case circuit breaker with PR232/P-LSI electronic trip unit, front terminals and stored energy operating mechanism for industrial low voltage power distribution protection.
£8,806.31
The ABB 1SDA063011R1 is a heavy-duty Tmax T7S moulded case circuit breaker (MCCB) designed for dependable protection of industrial low voltage power distribution systems. Part of the proven ABB SACE Tmax T7 series, this fixed three-pole circuit breaker is suitable for high-current switchboards, feeder circuits, transformer protection, generator applications and demanding industrial distribution systems.
This model is fitted with the advanced PR232/P-LSI electronic trip unit, providing long-time, short-time and instantaneous protection functions for AC applications. The solid-state release supports accurate fault detection, improved selectivity and reliable tripping performance, helping engineers maintain safe and efficient operation across critical electrical installations.
With a rated current of 1600 A, rated operational voltage up to 690 V AC, a three-pole fixed configuration with front terminals and a stored energy operating mechanism, the ABB 1SDA063011R1 is built for high-capacity electrical systems requiring robust performance, strong breaking capacity and long-term reliability.
ABB Tmax T7S circuit breakers are engineered to protect low voltage electrical systems against overload and short-circuit fault conditions while supporting reliable power continuity. The PR232/P-LSI trip unit provides adjustable electronic protection functions, helping improve coordination and selectivity across complex industrial power distribution networks.
The fixed three-pole construction with front terminals and stored energy operating mechanism makes this breaker suitable for integration into switchboards, distribution panels and power assemblies. Its high current rating, robust mechanical design and IEC compliance make it a dependable choice for industrial, commercial and infrastructure applications.
Tick the specs you need, then view products that match.
| Current | 1600 A | |
|---|---|---|
| Phase | Three Phase | |
| Poles | 3-pole | |
| Device Type | MCCB | |
| Breaking Capacity | 85 kA | |
| Trip Unit | Electronic | |
| Manufacturer | ABB | |
| Series | SACE Tmax T7S | |
| Part number | 1SDA063011R1 | |
| Extended product type | T7S 1600 PR232/P LSI In=1600A 3p F F M | |
| Product type | Moulded Case Circuit Breaker | |
| Rated current (In) | 1600 A | |
| Rated uninterrupted current (Iu) | 1600 A | |
| Number of poles | 3P | |
| Rated operational voltage | 690 V AC | |
| Rated insulation voltage (Ui) | 1000 V | |
| Rated impulse withstand voltage (Uimp) | 8 kV | |
| Release | PR232/P-LSI | |
| Release type | Electronic | |
| Short-circuit performance level | S | |
| Rated ultimate breaking capacity (Icu) | 85 kA at 220/230 V AC, 50 kA at 380 to 440 V AC, 40 kA at 500 V AC, 30 kA at 690 V AC | |
| Rated service breaking capacity (Ics) | 85 kA at 220/230 V AC, 50 kA at 380 to 440 V AC, 40 kA at 500 V AC, 30 kA at 690 V AC | |
| Rated short-time withstand current (Icw) | 20 kA for 1 second | |
| Electrical durability | 2,000 cycles | |
| Mechanical durability | 10,000 cycles | |
| Power loss | 77 W per pole at rated operating conditions | |
| Mounting type | Fixed | |
| Terminal connection | Front terminals | |
| Operating mechanism | Stored energy operating mechanism | |
| Standards | IEC 60947-2 | |
| Dimensions (H × W × D) | approx. 268 × 210 × 178 mm | |
| Weight | approx. 11 kg | |
| EAN | 8015644655600 |
The ABB 1SDA063011R1 is used to protect high-current low voltage distribution systems, including industrial switchboards, feeders, transformers and generator circuits.
This model has a rated current of 1600 A.
The breaker is fitted with a PR232/P-LSI electronic trip unit, providing long-time, short-time and instantaneous protection functions.
The ABB 1SDA063011R1 is a three-pole fixed moulded case circuit breaker.
This circuit breaker uses a stored energy operating mechanism for dependable switching in industrial power distribution systems.
ABB SACE Tmax circuit breakers are widely trusted by engineers, panel builders and electrical contractors for dependable circuit protection, strong breaking performance and long-term reliability in demanding power distribution applications.