ABB 1SDA063009R1 SACE Tmax T7S 1600A four-pole moulded case circuit breaker with PR332/P-LSIG electronic trip unit for industrial low voltage power distribution.
£8,076.98
The ABB 1SDA063009R1 is a heavy-duty Tmax T7S moulded case circuit breaker (MCCB) designed for dependable protection of industrial low voltage power distribution systems. As part of the proven ABB SACE Tmax T7 series, this fixed four-pole circuit breaker is ideal for high-current switchboards, feeder circuits, transformer protection, generator installations and demanding industrial power distribution applications.
This model incorporates the advanced PR332/P-LSIG electronic trip unit, providing long-time, short-time, instantaneous and earth fault protection. The intelligent electronic release enables accurate fault detection, enhanced selectivity and dependable protection, helping maximise electrical system uptime while improving installation safety.
With a rated current of 1600 A, rated operational voltage up to 690 V AC and a fixed four-pole design with front terminals, the ABB 1SDA063009R1 delivers reliable protection for high-capacity industrial electrical systems.
The ABB Tmax T7S range provides dependable protection against overloads, short circuits and earth faults while supporting reliable operation of industrial electrical infrastructure. The PR332/P-LSIG trip unit enables advanced protection coordination for improved selectivity and reduced downtime.
Its robust four-pole construction and front terminal arrangement make it suitable for installation within industrial switchboards, motor control centres and main distribution assemblies where dependable protection is essential.
Tick the specs you need, then view products that match.
| Current | 1600 A | |
|---|---|---|
| Phase | Three Phase | |
| Poles | 4-pole | |
| Device Type | MCCB | |
| Breaking Capacity | 85 kA | |
| Trip Unit | Electronic | |
| Manufacturer | ABB | |
| Series | SACE Tmax T7S | |
| Part number | 1SDA063009R1 | |
| Extended product type | T7S 1600 PR332/P LSIG In=1600A 4p F F | |
| Product type | Moulded Case Circuit Breaker | |
| Rated current (In) | 1600 A | |
| Rated uninterrupted current (Iu) | 1600 A | |
| Number of poles | 4P | |
| Rated operational voltage | Up to 690 V AC | |
| Rated insulation voltage (Ui) | 1000 V | |
| Rated impulse withstand voltage (Uimp) | 8 kV | |
| Trip unit | PR332/P-LSIG | |
| Release type | Electronic | |
| Protection functions | LSIG | |
| Short-circuit performance level | S | |
| Rated ultimate breaking capacity (Icu) | 85 kA at 230 V AC, 50 kA at 400 V AC, 40 kA at 500 V AC, 30 kA at 690 V AC | |
| Rated short-time withstand current (Icw) | 20 kA for 1 second | |
| Mounting type | Fixed | |
| Terminal connection | Front terminals | |
| Operating mechanism | Lever operated | |
| Standard | IEC 60947-2 | |
| Dimensions (H × W × D) | approx. 268 × 280 × 154 mm | |
| Weight | approx. 12.5 kg |
It protects industrial low voltage electrical systems against overloads, short circuits and earth faults.
The circuit breaker has a rated current of 1600 A.
The breaker is equipped with the ABB PR332/P-LSIG electronic trip unit.
This model is supplied as a four-pole fixed MCCB.
It is commonly installed within industrial switchboards, power distribution panels, generator systems and transformer protection applications.
ABB SACE Tmax moulded case circuit breakers are trusted worldwide for delivering dependable protection, excellent selectivity and long service life across demanding industrial power distribution systems.