ABB 1SDA062987R1 T7V 1250 is a 1250 A four-pole fixed moulded case circuit breaker with a PR232/P-LSI electronic trip unit, stored-energy operating mechanism and 150 kA breaking capacity at 380–415 V AC for high-current low-voltage power distribution.
£12,180.27
The ABB 1SDA062987R1, extended product type T7V 1250 PR232/P LSI In=1250A 4p F F M, is a high-performance moulded case circuit breaker (MCCB) designed for protection and switching in demanding low-voltage electrical distribution systems. Part of the ABB SACE Tmax T7 series, it combines a 1250 A rated uninterrupted current, four-pole construction and a PR232/P-LSI solid-state electronic trip unit.
The PR232/P-LSI release provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. Adjustable protection thresholds allow the breaker characteristics to be coordinated with the electrical installation, making it suitable for high-current feeders, incomers and distribution circuits where selective protection and reliable fault interruption are required.
With a rated ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC, the T7V 1250 is engineered for installations with very high prospective fault currents. This version is a fixed four-pole breaker with front terminals and a stored-energy operating mechanism, providing a robust solution for industrial switchboards, infrastructure and high-capacity power distribution assemblies.
Moulded case circuit breakers such as the ABB Tmax T7V protect low-voltage electrical distribution systems against excessive currents caused by overload and short-circuit conditions. The four-pole construction makes the 1SDA062987R1 suitable for three-phase four-wire distribution systems where all four poles need to be incorporated into the circuit breaker arrangement.
The PR232/P-LSI electronic trip unit combines adjustable long-time overload, short-time delayed and instantaneous short-circuit protection. Together with the 150 kA breaking capacity at 380–415 V AC of the T7V platform and its stored-energy operating mechanism, the 1SDA062987R1 provides dependable protection and switching for high-current distribution networks with substantial prospective fault levels.
| Series | SACE Tmax T7 |
|---|---|
| ABB product group | 310511-T-Max T4 - T8 |
| Order code | 1SDA062987R1 |
| EAN | 8015644655365 |
| Product type | Moulded case circuit breaker (MCCB) |
| Breaker type | T7V 1250 |
| Rated uninterrupted current (Iu) | 1250 A |
| Number of poles | 4 |
| Trip unit | PR232/P-LSI electronic release |
| Release type | Solid-state electronic |
| Protection functions | Long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection |
| Overload release adjustment | 500–1250 A |
| Short-time delayed short-circuit release adjustment | 750–12500 A |
| Instantaneous short-circuit release adjustment | 1875–15000 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V |
| Ultimate breaking capacity (Icu) at 220–230 V AC | 200 kA |
| Ultimate breaking capacity (Icu) at 380–415 V AC | 150 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 130 kA |
| Ultimate breaking capacity (Icu) at 500 V AC | 100 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 60 kA |
| Service breaking capacity (Ics) at 380–415 V AC | 150 kA |
| Service breaking capacity (Ics) at 440 V AC | 130 kA |
| Service breaking capacity (Ics) at 500 V AC | 100 kA |
| Service breaking capacity (Ics) at 690 V AC | 45 kA |
| Rated short-time withstand current (Icw) | 15 kA for 1 s |
| Installation version | Fixed |
| Terminal position | Front |
| Main-circuit connection | Bolted connection |
| Operating mechanism | Stored-energy mechanism |
| Motor drive | Optional |
| Degree of protection | IP20 |
| Electrical durability | 3,000 cycles |
| Mechanical durability | 10,000 cycles |
| Dimensions (H × W × D) | 268 × 280 × 178 mm |
| Net weight | 14 kg |
| Country of origin | Italy |
| Standard | IEC |
The ABB 1SDA062987R1 is a 1250 A four-pole moulded case circuit breaker designed for switching and protection of high-current low-voltage electrical distribution circuits against overload and short-circuit conditions.
The circuit breaker has a rated uninterrupted current of 1250 A, with its overload release adjustable from 500–1250 A.
The breaker has a rated ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC, making it suitable for electrical systems with very high prospective fault currents.
The breaker is fitted with an ABB PR232/P-LSI electronic trip unit, providing long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection.
The 1SDA062987R1 is a fixed four-pole circuit breaker with front terminals and a stored-energy operating mechanism, designed for integration into low-voltage switchboards and power distribution assemblies.
ABB SACE Tmax moulded case circuit breakers are widely used in industrial, commercial and infrastructure power distribution systems where dependable electronic protection, high breaking capacity and configurable protection characteristics are required.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.