Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA062980R1 is a T7V 1250 three-pole moulded case circuit breaker with a 1250 A rating, PR331/P LSIG electronic protection, integrated earth-fault protection and 150 kA ultimate breaking capacity at 380–415 V AC.
£10,594.23
The ABB 1SDA062980R1 is a high-performance Tmax T7V 1250 moulded case circuit breaker (MCCB) designed for protection and switching of high-current low-voltage electrical distribution systems. Equipped with the advanced PR331/P LSIG electronic trip unit, this three-pole breaker provides adjustable long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection for demanding industrial and commercial installations.
As part of the ABB SACE Tmax T7 series, the T7V 1250 combines a high continuous current rating with exceptional fault-breaking performance. Its V performance level provides an ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC, while the rated uninterrupted current of 1250 A makes it suitable for major distribution boards, high-current feeders and industrial power distribution systems.
The 1SDA062980R1 is supplied as a fixed three-pole circuit breaker with front terminals and a stored-energy operating mechanism. With a rated voltage of 690 V AC, adjustable overload protection from 500–1250 A and integrated earth-fault protection, it provides flexible and dependable protection for demanding low-voltage installations.
Moulded case circuit breakers such as the ABB Tmax T7V protect electrical distribution systems against overloads, short circuits and earth faults while providing reliable isolation and switching of high-current circuits. The T7V performance level is particularly suited to installations with high prospective short-circuit currents, delivering an ultimate breaking capacity of 150 kA at 380–415 V AC.
The PR331/P LSIG electronic trip unit provides adjustable long-time, short-time delayed, instantaneous and ground-fault protection. These protection functions allow the breaker to be coordinated with downstream equipment and the characteristics of the electrical installation, supporting selective and dependable protection in sophisticated industrial distribution systems.
| Series | SACE Tmax T7 |
|---|---|
| Order code / MPN | 1SDA062980R1 |
| ABB product group | 310511-T-Max T4 - T8 |
| Product type | Moulded case circuit breaker (MCCB) |
| Frame size | T7 |
| Performance level | V |
| Rated current (In) | 1250 A |
| Rated uninterrupted current (Iu) | 1250 A |
| Rated voltage | 690 V AC |
| Number of poles | 3 |
| Trip unit | PR331/P LSIG |
| Release type | Electronic / solid-state |
| Protection functions | L, S, I and G |
| Overload setting range | 500–1250 A |
| Short-time delayed short-circuit setting range | 750–12500 A |
| Instantaneous short-circuit setting range | 1875–15000 A |
| Ultimate short-circuit breaking capacity (Icu) at 380–415 V AC | 150 kA |
| Integrated earth-fault protection | Yes |
| Protection rating | IP20 |
| Mounting type | Fixed circuit breaker |
| Terminal position | Front |
| Main circuit connection | Bolt connection |
| Operating mechanism | Stored-energy mechanism |
| Complete with protection unit | Yes |
| Motor operator | Optional |
This circuit breaker is designed to protect and switch high-current low-voltage electrical distribution circuits in industrial, commercial and infrastructure installations.
The 1SDA062980R1 has a rated uninterrupted current of 1250 A, with its overload protection adjustable from 500–1250 A.
The PR331/P LSIG electronic trip unit provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection.
The T7V version provides an ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC.
The breaker is supplied in a fixed three-pole configuration with front terminals and a stored-energy operating mechanism, with optional motor operation available.
ABB SACE Tmax circuit breakers are designed for demanding low-voltage power distribution applications where dependable switching, high fault-breaking performance and configurable electronic protection are required.
We use cookies