1SDA062973R1 ABB T7V 1250 PR332/P-LI 1250 A 4-Pole MCCB

1SDA062973R1 ABB T7V 1250 PR332/P-LI 1250 A 4-Pole MCCB

ABB 1SDA062973R1 T7V 1250 is a 1250 A four-pole fixed moulded case circuit breaker with a PR332/P-LI electronic trip unit and 150 kA breaking capacity at 400 V AC for high-current low-voltage power distribution.

SKU: 1SDA062973R1MPN: 1SDA062973R1
Price
List Price £13,839.99 ex VAT
Your Price (ex VAT) Save 25%
£10,379.99 25% OFF
You save £3,460.00 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £10,379.99
Trade pricing is personalised to your account

Manufacturer Lead Time

£10,379.99

Why Choose the ABB 1SDA062973R1 T7V 1250 Circuit Breaker?

The ABB 1SDA062973R1, extended product type T7V 1250 PR332/P LI In=1250A 4p F F, is a high-performance moulded case circuit breaker (MCCB) designed for protection and switching in demanding low-voltage electrical distribution systems. Part of the ABB SACE Tmax T7 series, this model combines a 1250 A rated uninterrupted current, four-pole construction and the advanced PR332/P-LI electronic trip unit.

The PR332/P-LI solid-state release provides long-time overload and instantaneous short-circuit protection, allowing the breaker to protect high-current feeders and distribution circuits against damaging overcurrent conditions. Its electronic protection system provides adjustable settings that allow the protection characteristics to be matched more closely to the electrical installation than a fixed trip arrangement.

With a rated ultimate short-circuit breaking capacity of 150 kA at 400 V AC, 50 Hz, the T7V 1250 is particularly well suited to installations with very high prospective fault currents. This version is supplied as a fixed four-pole breaker with front terminals and a lever operating mechanism, providing a robust solution for industrial switchboards, infrastructure and high-capacity power distribution assemblies.

Key Advantages

  • High-performance ABB SACE Tmax T7V moulded case circuit breaker for demanding low-voltage distribution systems.
  • 1250 A rated uninterrupted current for high-current applications.
  • Four-pole construction enables simultaneous switching of three phases and neutral.
  • 150 kA ultimate breaking capacity at 400 V AC, 50 Hz for installations with very high prospective fault currents.
  • Advanced PR332/P-LI electronic trip unit for overload and instantaneous short-circuit protection.
  • Overload release adjustable across 500–1250 A.
  • Fixed configuration with front terminals for integration into low-voltage switchboards and distribution assemblies.

Key Features

  • ABB SACE Tmax T7V 1250 series MCCB.
  • 1250 A rated uninterrupted current.
  • Four-pole construction.
  • PR332/P-LI solid-state electronic release.
  • Long-time overload protection.
  • Instantaneous short-circuit protection.
  • Overload release adjustable from 500–1250 A.
  • Instantaneous short-circuit release adjustable from 1875–18750 A.
  • 150 kA Icu at 400 V AC, 50 Hz.
  • 690 V AC rated voltage.
  • Fixed installation format.
  • Front-side main circuit connections.
  • Bolted main circuit connection.
  • Lever operating mechanism.
  • IP20 degree of protection.

Four-Pole Protection for High-Current Power Distribution

The four-pole construction of the ABB Tmax T7V 1250 enables the breaker to switch all three phases together with the neutral conductor. This makes the 1SDA062973R1 particularly suitable for three-phase four-wire distribution systems where simultaneous isolation of the neutral is required as part of the switching arrangement.

The PR332/P-LI electronic trip unit combines adjustable long-time overload protection with instantaneous short-circuit protection. Together with the 150 kA breaking capacity at 400 V AC of the T7V platform, this provides dependable protection for high-current distribution systems where substantial prospective fault levels can occur.

Typical Applications

  • Main and sub-main low-voltage distribution boards.
  • Three-phase four-wire electrical distribution systems.
  • Industrial switchboards and power distribution assemblies.
  • Main incomers and high-current feeder circuits.
  • Manufacturing and process plants.
  • Commercial and infrastructure power distribution.
  • Electrical networks with very high prospective short-circuit currents.

Technical Specifications

Series SACE Tmax T7
ABB product group 310511-T-Max T4 - T8
Order code 1SDA062973R1
EAN 8015644655228
Product type Moulded case circuit breaker (MCCB)
Breaker type T7V 1250
Rated uninterrupted current (Iu) 1250 A
Number of poles 4
Trip unit PR332/P-LI electronic release
Release type Solid-state electronic
Protection functions Long-time overload and instantaneous short-circuit protection
Overload release adjustment 500–1250 A
Instantaneous short-circuit release adjustment 1875–18750 A
Rated voltage 690 V AC
Ultimate breaking capacity (Icu) at 400 V AC, 50 Hz 150 kA
Installation version Fixed
Terminal position Front
Main circuit connection Bolted connection
Operating mechanism Lever operated
Degree of protection IP20
Complete device with protection unit Yes
Country of origin Italy
Weight approx. 14 kg

Frequently Asked Questions

What is the ABB 1SDA062973R1 used for?

The ABB 1SDA062973R1 is a 1250 A four-pole moulded case circuit breaker designed for switching and protection of high-current low-voltage electrical distribution circuits against overload and short-circuit conditions.

What is the current rating of the ABB T7V 1250 1SDA062973R1?

The circuit breaker has a rated uninterrupted current of 1250 A, with its overload release adjustable from 500–1250 A.

What breaking capacity does the ABB T7V 1250 1SDA062973R1 provide?

The breaker has a rated ultimate short-circuit breaking capacity of 150 kA at 400 V AC, 50 Hz, making it suitable for electrical systems with very high prospective fault currents.

What trip unit is fitted to the ABB 1SDA062973R1?

The breaker is fitted with an ABB PR332/P-LI electronic trip unit, providing long-time overload and instantaneous short-circuit protection.

Is the ABB 1SDA062973R1 a four-pole circuit breaker?

Yes. The 1SDA062973R1 is a four-pole fixed circuit breaker with front main-circuit connections, making it suitable for three-phase four-wire distribution systems requiring four-pole switching.

Trusted by Electrical Professionals Worldwide

ABB SACE Tmax moulded case circuit breakers are widely used in industrial, commercial and infrastructure power distribution systems where dependable electronic protection, high breaking capacity and robust switching performance are required.