1SDA062971R1 ABB T7V 1250 PR232/P LSI 1250 A 4-Pole Moulded Case Circuit Breaker

1SDA062971R1 ABB T7V 1250 PR232/P LSI 1250 A 4-Pole Moulded Case Circuit Breaker

ABB T7V 1250 PR232/P LSI 4-pole moulded case circuit breaker with a 1250 A rated current, fixed front-terminal configuration, adjustable LSI electronic protection and 150 kA breaking capacity at 380/415 V AC.

SKU: 1SDA062971R1MPN: 1SDA062971R1
Price
List Price £14,763.83 ex VAT
Your Price (ex VAT) Save 25%
£11,072.87 25% OFF
You save £3,690.96 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £11,072.87
Trade pricing is personalised to your account

Manufacturer Lead Time

£11,072.87

Why Choose the ABB T7V 1250 PR232/P LSI Moulded Case Circuit Breaker?

The ABB T7V 1250 PR232/P LSI is a high-performance 4-pole moulded case circuit breaker (MCCB) designed for demanding low-voltage power distribution systems. Part of the proven ABB Tmax T7 series, it combines a 1250 A rated uninterrupted current with electronic protection and very high short-circuit breaking capability.

Equipped with the PR232/P LSI solid-state electronic release, the T7V 1250 provides long-time, short-time and instantaneous protection functions. Adjustable overload and short-circuit settings support effective protection coordination with cables, switchgear and downstream electrical equipment in high-capacity distribution networks.

With an ultimate short-circuit breaking capacity of 150 kA at 380/415 V AC, a rated operational voltage of 690 V AC and a fixed four-pole construction with front terminals and lever operating mechanism, the T7V 1250 is engineered for switchboards where dependable protection against high prospective fault currents is essential.

Key Advantages

  • High-performance ABB Tmax T7 moulded case circuit breaker.
  • 1250 A rated uninterrupted current for high-capacity distribution circuits.
  • 150 kA Icu at 380/415 V AC for demanding fault conditions.
  • PR232/P LSI electronic trip unit for adjustable overload and short-circuit protection.
  • 500–1250 A adjustable overload protection range.
  • 750–12500 A short-time delayed short-circuit adjustment range.
  • 1875–15000 A instantaneous short-circuit adjustment range.
  • 4-pole construction suitable for three-phase distribution systems incorporating a neutral conductor.
  • Fixed mounting with front terminals for switchboard integration.

Key Features

  • ABB Tmax T7 series.
  • T7V 1250 performance level.
  • 1250 A rated uninterrupted current.
  • 4-pole construction.
  • PR232/P LSI solid-state electronic release.
  • Long-time overload protection.
  • Short-time delayed short-circuit protection.
  • Instantaneous short-circuit protection.
  • 150 kA ultimate short-circuit breaking capacity at 380/415 V AC.
  • 690 V AC rated operational voltage.
  • 1000 V rated insulation voltage.
  • 15 kA rated short-time withstand current for 1 s.
  • Fixed mounting with front terminals.
  • Lever operating mechanism.

Reliable Circuit Protection for Power Distribution

Moulded case circuit breakers such as the ABB Tmax T7 protect low-voltage electrical distribution circuits against overload and short-circuit conditions. The electronic protection unit monitors circuit current and initiates interruption when configured protection thresholds are exceeded, helping protect conductors, switchgear and connected electrical equipment.

The T7V 1250 combines a high 1250 A current rating with 150 kA breaking capability at 380/415 V AC and adjustable PR232/P LSI protection. Its four-pole construction and fixed front-terminal configuration make it well suited to high-capacity three-phase distribution systems requiring coordinated electronic circuit protection.

Typical Applications

  • Industrial low-voltage distribution switchboards.
  • Main incomer and feeder circuit protection.
  • High-current four-pole three-phase distribution systems.
  • Commercial and infrastructure electrical distribution.
  • Manufacturing and process-industry electrical systems.
  • Power distribution centres and switchgear assemblies.
  • High-fault-level low-voltage electrical networks.

Technical Specifications

Series Tmax T7
ABB order code 1SDA062971R1
EAN 8015644655204
Product type Moulded case circuit breaker
Rated uninterrupted current (Iu) 1250 A
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Number of poles 4
Trip unit PR232/P
Protection functions LSI
Ultimate short-circuit breaking capacity (Icu) 200 kA at 220/230 V AC
Service short-circuit breaking capacity (Ics) 150 kA at 380/400/415 V AC
Rated short-time withstand current (Icw) 15 kA for 1 s
Overload release adjustment range 500–1250 A
Short-time delayed short-circuit adjustment range 750–12500 A
Instantaneous short-circuit adjustment range 1875–15000 A
Mounting type Fixed
Terminal configuration Front terminals
Operating mechanism Lever
Motor drive integrated No
Dimensions (W × H × D) 280 × 268 × 154 mm
Product net weight 12.5 kg
ABB product group 310511-T-Max T4 - T8

Frequently Asked Questions

What is the ABB T7V 1250 PR232/P LSI used for?

This moulded case circuit breaker is designed to protect high-current low-voltage distribution circuits against overload and short-circuit conditions in demanding industrial, commercial and infrastructure electrical systems.

What is the rated current of ABB order code 1SDA062971R1?

The ABB T7V 1250 1SDA062971R1 has a rated uninterrupted current of 1250 A, with an adjustable overload release range of 500–1250 A.

What is the breaking capacity of the ABB T7V 1250 1SDA062971R1?

The breaker has an ultimate short-circuit breaking capacity of 150 kA at 380/400/415 V AC and up to 200 kA at 220/230 V AC.

Which trip unit is fitted to the ABB T7V 1250 1SDA062971R1?

This model is equipped with the ABB PR232/P LSI solid-state electronic release, providing long-time, short-time and instantaneous protection functions.

How many poles does the ABB T7V 1250 1SDA062971R1 have?

This version has a 4-pole configuration, making it suitable for three-phase low-voltage distribution systems incorporating a neutral conductor.

How is the ABB 1SDA062971R1 configured for installation?

ABB order code 1SDA062971R1 is a fixed four-pole circuit breaker with front terminals and a lever operating mechanism.

Trusted by Electrical Professionals Worldwide

ABB Tmax moulded case circuit breakers are widely used by electrical engineers, panel builders and industrial operators for dependable circuit protection, power distribution and control in demanding low-voltage installations.