1SDA062966R1 ABB T7V 1250 PR332/P LSI 1250A 3P Circuit Breaker

1SDA062966R1 ABB T7V 1250 PR332/P LSI 1250A 3P Circuit Breaker

ABB 1SDA062966R1 is a SACE Tmax T7V 1250 A three-pole fixed moulded-case circuit breaker with a PR332/P LSI electronic trip unit and 150 kA ultimate short-circuit breaking capacity at 380–415 V AC for adjustable overload and short-circuit protection.

SKU: 1SDA062966R1MPN: 1SDA062966R1
Price
List Price £12,209.26 ex VAT
Your Price (ex VAT) Save 25%
£9,156.95 25% OFF
You save £3,052.32 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £9,156.95
Trade pricing is personalised to your account

Manufacturer Lead Time

£9,156.95

Why Choose the ABB T7V 1250 PR332/P LSI 1250A Circuit Breaker?

The ABB 1SDA062966R1, designated T7V 1250 PR332/P LSI In=1250A 3p F F, is a high-performance three-pole moulded-case circuit breaker (MCCB) designed for protection and switching in demanding low-voltage power distribution systems. Part of the established ABB SACE Tmax T7 series, it combines a rated uninterrupted current of 1250 A with the advanced PR332/P LSI solid-state electronic trip unit for adjustable overload and short-circuit protection.

The T7V performance level provides very high short-circuit interruption capability, including a rated ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC. Its PR332/P LSI electronic release provides long-time, short-time and instantaneous protection functions, allowing the breaker to protect high-current circuits against sustained overloads and severe short-circuit conditions while supporting coordinated protection throughout the distribution system.

With its three-pole configuration, fixed construction, front terminals and lever operating mechanism, the 1SDA062966R1 is designed for reliable integration into professional low-voltage switchboards. Its combination of 1250 A continuous current capability, configurable electronic protection and high breaking capacity makes it particularly suitable for industrial, commercial and infrastructure distribution systems with substantial prospective fault currents.

Key Advantages

  • High-performance 1250 A moulded-case circuit breaker for demanding low-voltage distribution systems.
  • 150 kA ultimate short-circuit breaking capacity at 380–415 V AC for high fault-level installations.
  • Advanced PR332/P LSI solid-state electronic trip unit.
  • Provides adjustable long-time, short-time and instantaneous protection.
  • Three-pole configuration designed for three-phase electrical distribution systems.
  • Fixed construction with front terminals and lever operation for dependable switchboard integration.

Key Features

  • ABB SACE Tmax T7V 1250 series.
  • 1250 A rated uninterrupted current.
  • PR332/P LSI electronic protection trip unit.
  • 150 kA Icu at 380–415 V AC.
  • Three-pole configuration.
  • 500–1250 A adjustable overload release range.
  • 750–12500 A adjustable short-time delayed short-circuit release range.
  • 1875–18750 A adjustable instantaneous short-circuit release range.
  • Fixed installation with front main-circuit terminals.
  • Bolt-connected main circuit.
  • Manual lever operating mechanism.
  • Optional motor drive capability.
  • IP20 degree of protection.

Advanced LSI Protection for High-Power Distribution

The ABB Tmax T7V platform is designed for high-current low-voltage systems where substantial fault interruption capability and configurable electronic protection are required. With a rated uninterrupted current of 1250 A and an ultimate breaking capacity of 150 kA at 380–415 V AC, the 1SDA062966R1 provides robust protection for electrical distribution networks with very high prospective short-circuit currents.

The PR332/P LSI electronic trip unit combines adjustable long-time overload protection from 500–1250 A, short-time delayed short-circuit protection from 750–12500 A and instantaneous short-circuit protection from 1875–18750 A. These independently defined protection functions support effective coordination and selectivity while the fixed three-pole construction provides a robust solution for high-current three-phase distribution.

Typical Applications

  • Main low-voltage distribution switchboards.
  • Industrial power distribution systems.
  • Manufacturing and process plants.
  • Commercial buildings and infrastructure installations.
  • Transformer secondary and high-current feeder protection.
  • Three-phase electrical distribution networks.
  • High fault-level power distribution systems.

Technical Specifications

Series SACE Tmax T7
ABB order code 1SDA062966R1
ABB product group 310511-T-Max T4 - T8
EAN / GTIN 8015644655150
Product type Moulded-case circuit breaker (MCCB)
Frame T7V 1250
Short-circuit performance level V
Rated uninterrupted current Iu 1250 A
Number of poles 3
Trip unit PR332/P LSI
Release type Solid-state electronic
Protection functions LSI – long-time, short-time and instantaneous
Overload release current setting 500–1250 A
Short-time delayed short-circuit release adjustment 750–12500 A
Instantaneous short-circuit release adjustment 1875–18750 A
Rated operational voltage 690 V AC
Rated insulation voltage Ui 1000 V
Rated impulse withstand voltage Uimp 8 kV
Ultimate short-circuit breaking capacity Icu at 220–230 V AC 200 kA
Ultimate short-circuit breaking capacity Icu at 380–415 V AC 150 kA
Ultimate short-circuit breaking capacity Icu at 440 V AC 130 kA
Ultimate short-circuit breaking capacity Icu at 500 V AC 100 kA
Ultimate short-circuit breaking capacity Icu at 690 V AC 60 kA
Service short-circuit breaking capacity Ics at 380–415 V AC 150 kA
Rated short-time withstand current Icw 15 kA for 1 s
Installation Fixed
Terminal position Front
Main circuit connection Bolt connection
Operating mechanism Lever / toggle
Integrated motor drive No
Optional motor drive Yes
DIN rail mounting No
Degree of protection IP20
Country of origin Italy
Weight approx. 11.2 kg

Frequently Asked Questions

What is the ABB 1SDA062966R1 used for?

The ABB 1SDA062966R1 is a 1250 A three-pole moulded-case circuit breaker designed for switching and protection against overload and short-circuit conditions in high-current three-phase low-voltage electrical distribution systems.

What trip unit is fitted to the ABB T7V 1250 1SDA062966R1?

The circuit breaker is fitted with an ABB PR332/P LSI solid-state electronic trip unit, providing adjustable long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection.

What is the breaking capacity of the ABB 1SDA062966R1?

The ABB T7V 1250 1SDA062966R1 has a rated ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC, making it suitable for electrical installations with very high prospective fault currents.

What are the protection adjustment ranges of the ABB 1SDA062966R1?

The overload release is adjustable from 500–1250 A, the short-time delayed short-circuit release from 750–12500 A, and the instantaneous short-circuit release from 1875–18750 A.

Where is the ABB 1SDA062966R1 typically installed?

The breaker is typically installed in main low-voltage switchboards, industrial distribution panels, transformer secondary circuits and infrastructure power systems requiring 1250 A three-pole protection and very high short-circuit interruption performance.

Trusted Protection from ABB

ABB Tmax moulded-case circuit breakers are widely used in industrial, commercial and infrastructure power distribution systems, providing dependable circuit protection, flexible electronic trip functionality and high short-circuit interruption performance.