Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA062965R1 is a SACE Tmax T7V 1250 A three-pole fixed moulded-case circuit breaker with a PR332/P LI electronic trip unit and 150 kA ultimate short-circuit breaking capacity at 400 V AC for adjustable overload and instantaneous short-circuit protection.
£8,520.81
The ABB 1SDA062965R1, designated T7V 1250 PR332/P LI In=1250A 3p F F, is a high-performance three-pole moulded-case circuit breaker (MCCB) designed for protection and switching in demanding low-voltage power distribution systems. Part of the established ABB SACE Tmax T7 series, it combines a rated uninterrupted current of 1250 A with the advanced PR332/P LI solid-state electronic trip unit for adjustable overload and instantaneous short-circuit protection.
The T7V version is engineered for installations with very high prospective fault currents, providing a rated ultimate short-circuit breaking capacity of 150 kA at 400 V AC, 50 Hz. Its PR332/P LI electronic release provides adjustable long-time overload and instantaneous short-circuit protection, allowing protection characteristics to be configured for demanding industrial and commercial distribution networks.
With its three-pole configuration, fixed construction, front terminals and lever operating mechanism, the 1SDA062965R1 is designed for straightforward integration into professional low-voltage switchboards. Its combination of 1250 A continuous current capability, advanced electronic protection and high breaking capacity makes it particularly suitable for main distribution and high-current feeder applications.
The ABB Tmax T7V platform is designed for high-current low-voltage systems where substantial fault interruption capability is essential. With a rated uninterrupted current of 1250 A and an ultimate short-circuit breaking capacity of 150 kA at 400 V AC, 50 Hz, the 1SDA062965R1 provides robust protection for electrical distribution networks with high prospective short-circuit currents.
The PR332/P LI electronic trip unit combines adjustable long-time overload protection from 500–1250 A with instantaneous short-circuit protection adjustable from 1875–18750 A. This flexibility allows protection settings to be coordinated with the characteristics of the protected circuit while the fixed three-pole construction provides a robust solution for high-current three-phase distribution.
| Series | SACE Tmax T7 |
|---|---|
| ABB order code | 1SDA062965R1 |
| ABB product group | 310511-T-Max T4 - T8 |
| EAN / GTIN | 8015644655143 |
| Product type | Moulded-case circuit breaker (MCCB) |
| Frame | T7V 1250 |
| Rated uninterrupted current Iu | 1250 A |
| Number of poles | 3 |
| Trip unit | PR332/P LI |
| Release type | Solid-state electronic |
| Protection functions | LI – long-time overload and instantaneous short-circuit protection |
| Overload release current setting | 500–1250 A |
| Instantaneous short-circuit release adjustment | 1875–18750 A |
| Rated voltage | 690 V AC |
| Ultimate short-circuit breaking capacity Icu at 400 V AC, 50 Hz | 150 kA |
| Installation | Fixed |
| Terminal position | Front |
| Main circuit connection | Bolt connection |
| Operating mechanism | Lever / toggle |
| Integrated motor drive | No |
| DIN rail mounting | No |
| Degree of protection | IP20 |
| Country of origin | Italy |
| Weight | approx. 11.2 kg |
The ABB 1SDA062965R1 is a 1250 A three-pole moulded-case circuit breaker designed for switching and protection against overload and short-circuit conditions in high-current three-phase low-voltage electrical distribution systems.
The circuit breaker is fitted with an ABB PR332/P LI solid-state electronic trip unit, providing adjustable long-time overload and instantaneous short-circuit protection.
The ABB T7V 1250 1SDA062965R1 has a rated ultimate short-circuit breaking capacity of 150 kA at 400 V AC, 50 Hz, making it suitable for installations with very high prospective fault currents.
The overload release can be adjusted from 500–1250 A, while the instantaneous short-circuit release can be adjusted from 1875–18750 A.
The breaker is typically installed in main low-voltage switchboards, industrial distribution panels, transformer secondary circuits and infrastructure power systems requiring 1250 A three-pole protection and very high short-circuit interruption performance.
ABB Tmax moulded-case circuit breakers are widely used in industrial, commercial and infrastructure power distribution systems, providing dependable circuit protection, flexible electronic trip functionality and high short-circuit interruption performance.
We use cookies