Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA062962R1 T7V 1250 is a 1250 A three-pole fixed moulded case circuit breaker with a PR231/P-LS/I electronic trip unit and 150 kA breaking capacity at 380–415 V AC for high-current low-voltage power distribution.
£8,501.00
The ABB 1SDA062962R1, extended product type T7V 1250 PR231/P LS/I In=1250A 3p F F, is a high-performance moulded case circuit breaker (MCCB) designed for protection and switching in high-current low-voltage electrical distribution systems. As part of the established ABB SACE Tmax T7 series, it combines a 1250 A rated uninterrupted current with a PR231/P-LS/I electronic trip unit for adjustable overload and short-circuit protection.
This T7V configuration is a fixed three-pole circuit breaker with front terminals and a lever operating mechanism, making it suitable for demanding industrial switchboards and power distribution assemblies. The PR231/P-LS/I electronic release provides long-time overload protection together with selectable short-time delayed or instantaneous short-circuit protection, allowing the protection characteristics to be coordinated with the requirements of the electrical installation.
With a rated uninterrupted current of 1250 A and a rated ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC, the T7V 1250 is engineered for installations with very high prospective fault currents. Its robust Tmax construction, configurable electronic protection and fixed front-terminal arrangement make it well suited to industrial plants, infrastructure and large low-voltage power distribution systems.
Moulded case circuit breakers such as the ABB Tmax T7V protect low-voltage electrical distribution systems against excessive currents caused by overload and short-circuit conditions. By rapidly interrupting dangerous fault currents, the breaker helps protect cables, switchgear and connected equipment while supporting the safety and continuity of the electrical installation.
The PR231/P-LS/I electronic trip unit provides adjustable long-time overload protection together with selectable short-time delayed or instantaneous short-circuit protection. Combined with the high breaking capacity of the T7V platform, the 1SDA062962R1 provides a robust solution for industrial power systems requiring configurable protection, selective coordination and dependable interruption of very high prospective fault currents.
| Series | SACE Tmax T7 |
|---|---|
| ABB product group | 310511-T-Max T4 - T8 |
| Order code | 1SDA062962R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Breaker type | T7V 1250 |
| Rated uninterrupted current (Iu) | 1250 A |
| Number of poles | 3 |
| Trip unit | PR231/P-LS/I electronic release |
| Protection functions | Long-time overload with selectable short-time delayed or instantaneous short-circuit protection |
| Long-time protection adjustment | 0.4–1 × In |
| Short-circuit protection adjustment | 1–10 × In |
| Short-time delay | 0.1 or 0.25 s at 10 × In |
| Rated operational voltage | 690 V AC, 50 / 60 Hz |
| Rated insulation voltage | 1000 V |
| Rated impulse withstand voltage | 8 kV |
| Ultimate breaking capacity (Icu) at 220–230 V AC | 200 kA |
| Ultimate breaking capacity (Icu) at 380–415 V AC | 150 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 130 kA |
| Ultimate breaking capacity (Icu) at 500 V AC | 100 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 60 kA |
| Service breaking capacity (Ics) at 380–415 V AC | 150 kA |
| Service breaking capacity (Ics) at 690 V AC | 45 kA |
| Rated short-time withstand current (Icw) | 15 kA for 1 s |
| Utilisation category | B |
| Installation version | Fixed |
| Terminal type | Front terminals |
| Operating mechanism | Lever operated |
| Dimensions (H × W × D) | 268 × 210 × 154 mm |
| Weight | approx. 9.7 kg |
| Mechanical durability | 10,000 operations |
| Electrical durability at 415 V AC | 3,000 operations |
| Operating temperature | -25 to +70 °C |
| Standard | IEC 60947-2 |
The ABB 1SDA062962R1 is a 1250 A moulded case circuit breaker used for switching and protection of high-current low-voltage electrical distribution circuits against overload and short-circuit conditions.
The circuit breaker has a rated uninterrupted current of 1250 A, with adjustable long-time protection from 0.4–1 × In.
The T7V configuration provides a rated ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC, making it suitable for electrical systems with very high prospective fault currents.
The breaker is fitted with an ABB PR231/P-LS/I electronic trip unit providing long-time overload protection together with selectable short-time delayed or instantaneous short-circuit protection.
This model is a fixed three-pole circuit breaker with front terminals and a lever operating mechanism, designed for installation in low-voltage switchboards and power distribution assemblies.
ABB SACE Tmax moulded case circuit breakers are widely used in industrial, commercial and infrastructure power distribution systems where dependable circuit protection, high breaking capacity and configurable electronic protection are required.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.